Overheating of the Bus-bar can reduce the life of the
insulation sleeves, Bus-bar / cables & even Breakers. Periodic
loading conditions can cause the metal to heat and cool
continuously resulting in the deterioration of the Bus-bar
material and loosening of the joints. This becomes even
more critical in case if Bus-bars consist of metals of different
heat coefficient.
C
a
u
s
e
s
o
f
o
v
e
r
h
e
a
t
i
n
g
:
Any of the following reasons can lead to heat generation at
the breaker terminal
i.
Improper termination
ii. Improper Bus-bar design
iii. Loosen Joints
iv. De-rating not considered while selection of breaker
v. Eddy currents
S
p
e
c
i
f
i
c
a
t
i
o
n
s
:
O
O
i.
Pick up (Tp) - 85 C to 115 C
ii. Pre alarm - 0.5Tp to 0.95Tp in the steps of 0.05Tp
iii. Delay - 0 Min to 15 Mins in Steps of 1 Min (It delays the tripping of the breaker by the set delay time.)
iv. Input supply - 24V DC (Directly at Module Terminals)
Temperature Module senses the real time temperature at the Cradle terminals and displays on the Matrix release
screen. TM module can be used to give alarm on the release or to trip the breaker with the temperature pickup
o
o
range from 85 C to 115 C, which can be configured through Matrix release.
The module is to be fitted on the Breaker and is a factory fitted option.
AS+
: Auxiliary 24V DC
AS-
: Ground
CAN- H : CAN-High
CAN- L : CAN-Low
}
CAN-H
CAN L
AS+
AS-
CAN-L
AS+
AS-
CAN H
T1-T4
connection to breaker terminals
SIC
IN
TE
R C
O
N
N
EC
TIO
N
}
?
Temperature
O
Phase1 : 45 C
O
Phase2 : 47 C
O
Phase3 : 50 C
Summary of Contents for OMEGA
Page 2: ...Stabilise systems with technology ...
Page 4: ...Change course quickly ...
Page 6: ...Match performance with prudence ...
Page 8: ...Adopt technological brilliance ...
Page 10: ...Keep an eye on upkeep ...
Page 26: ...Matrix Protection Control Units T UW M X4 5 ...
Page 70: ...Accessories ...
Page 84: ...Control Circuit Wiring ...
Page 92: ...Mounting Termination ...
Page 135: ...SP 50567 R5 ...