Advanced protection in UW-MTX 3.5/3.5EC/3.5H/4.5 Series
Under Current
Current Unbalance
Under Voltage
Over Voltage
Parameter
Protection: Enable/Disable
Pick-Up=lr x ...
Delay
Mode: Trip/Alarm/Both
Protection: Enable/Disable
Pick-Up=ln x ...
Delay
Mode: Trip/Alarm/Both
Protection: Enable/Disable
Pick-Up(Vs)=Vn x ...
Delay
Vs reset
Mode: Trip/Alarm/Both
Protection: Enable/Disable
Pick-Up(Vs)=Vn x ...
Delay
Vs reset
UW-MTX 4.5
Mode: Trip/Alarm/Both
0.2 to 0.8 in step of 0.05
1 to 255sec in step of 1sec
10 to 90% in step of 5%
500 ms to 60s in step of 0.5s
0.7 to 0.95 in steps of 0.01
100 ms to 5s in step of 100 ms
1.01/1.02/1.03/1.04 x Vs
1.05 to 1.5 Vn in step of 0.01
100 ms to 5s in steps of 100 ms
0.95 to 0.99 Vs in step of 0.01
Voltage Unbalance
Residual Voltage
Under Frequency
Over Frequency
Rev Power
Earth Leakage**
Restricted EF**
Protection: Enable/Disable
Pick-Up(Vs)=Vn x ...
Delay
Vs reset
Mode: Trip/Alarm/Both
Protection: Enable/Disable
Pick-Up (Vs)=Vn x ...
Delay
Vs Reset
Mode: Trip/Alarm/Both
Protection: Enable/Disable
Pick-Up (Fn)
Delay
Reset Freq
Mode: Trip/Alarm/Both
Protection: Enable/Disable
Pick-Up (Fn)
Delay
Reset Freq
Mode: Trip/Alarm/Both
Protection: Enable/Disable
Pick-Up=Pn x ...
Delay
Mode: Trip/Alarm/Both
Mode: Trip/Alarm/Both
Protection: Enable/Disable
Pick-Up(lr)
Delay
Protection: Enable/Disable
2
I t: OFF/ON
Pick-Up(lg)=ln x ...
2
l t OFF (tg)
2
l t ON (tg)
Pre-alarm
Cold Pick-Up: ON/OFF
5 to 20% in step of 1%
500ms to 60s in step of 0.5s
0.95 to 0.99 Vs in step of 0.01
0.15/0.2/0.25/0.3/0.4
100ms to 5s in step of 100 ms
0.95 to 0.99 Vs in step of 0.01
45-50 Hz in step of 0.1Hz
1-30sec in step of 0.1sec
1.01 to 1.05 Fn in step of 0.01
50-55 Hz in step of 0.1 Hz
1-30sec in step of 0.1sec
0.95 to 0.99 Fn in step of 0.01
0.05 to 0.4 in step of 0.01
100ms-20s in step of 0.1s
0.3 to 30A in step of 0.1 A
100-200-300-400-500 ms
0.1 to 0.6 in step of 0.1
100 ms to 5sec in step of 0.1s
100-200-300-400 ms
0.5 to 0.95 in step of 0.05 x lg
60 ms to 10s in step of 20ms
Mode: Trip/Alarm/Both
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
UW-MTX3.5EC
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
35
Matrix
Protection and Control Units
* Requires Power Metering module for
**
Advanced Voltage based Protection
Requires additional modules
UW-MTX3.5*
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
Available
UW-MTX3.5H
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
36
Matrix
Protection and Control Units
Metering Functions
Advanced Protection in UW-MTX 3.5/3.5EC/3.5H/4.5 Series
Parameter
Protection: Enable/Disable
Pick-Up=Pf x ...
Delay
Mode: Trip/Alarm/Both
Protection: Enable/Disable
Pick-Up=Pf x ...
Delay
Mode: Trip/Alarm/Both
Protection: Enable/Disable
Type
Pick-Up=En x ...
Mode: Trip/Alarm/Both
Protection: Enable/Disable
Type
Pick-Up=En x ...
Mode: Trip/Alarm/Both
Protection: Enable/Disable
Type
Pick-Up=En x ...
Mode: Trip/Alarm/Both
Protection: Enable/Disable
Delay
Mode: Trip/Alarm/Both
Protection: Enable/Disable
Delay
UW-MTX3.5*
P
P
P
P
P
P
P
P
P
P
P
P
P
UW-MTX4.5
P
P
P
P
P
P
P
P
P
P
P
P
P
UW-MTX3.5EC
0.5 to 0.99 in step of 0.01
1/2/3/4/5 s
0.5 to 0.99 in step of 0.01
1/2/3/4/5 s
Deliver/Receive
0.4 to 1 in step of 0.01
Deliver/Receive
0.4 to 1 in step of 0.01
Deliver/Receive
0.4 to 1 in step of 0.01
100ms to 5s in step of 100ms
P
P
P
P
P
P
P
P
P
P
P
P
P
50ms to 2sec in step of 0.05sec
Leading PF
Lagging PF
MD Active
MD Reactive
MD Apparent
Phase Sequence
Breaker Failure
* Requires Power Metering module # Requires Temperature module
Parameter
Current
Voltage
Frequency
Power Factor
Power
Energy
Max Demand
#
Temperature
Harmonics Metering
Details
Phase, Neutral and Earth
Earth Leakage, Restricted EF Current
Maximum Running Current Per Phase
Percentage Loading Per Phase
Average Phase Current
Phase-Neutral Voltage
Maximum Voltage Per Phase
Ph-Ph Voltage
Maximum Ph-Ph Voltage
Average Ph-Ph Voltage
Average Ph-N Voltage
System Frequency
System Power Factor
Active Power Per Phase and Total (kW)
Reactive Power Per Phase and Total (kVar)
Apparent Power Per Phase and Total (kVA)
Active Energy Per Phase and Total (kwh)
Reactive Energy Per Phase and Total (kVArh)
Apparent Energy Per Phase and Total (kVAh)
Active Energy
Reactive Energy
Apparent Energy
0
Temperature Per Phase & Neutral ( C)
Phase-1, 2 & 3-Total, Fundamental, THD
Screen abbreviation
l
$
l , lREF
Δ
l max
% Load
Avg.I
V
Max V
V12
Max V12
Avg. Vp-p
Avg Vp-n
F
PF
W
VAr
VA
Wh
VArh
VAh
Wh
VArh
VAh
Ø
MTX 3.5EC
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
MTX 3.5
P
P
P
P
P
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
P
MTX4.5
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
MTX3.5H
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
-
-
THD, Current &
Voltage components
* Requires Power Metering module for Advanced protections
P
Available
P
Available
UW-MTX3.5H
P
P
P
P
P
P
P
P
P
P
P
P
P
$ requires additional REF module
Summary of Contents for OMEGA
Page 2: ...Stabilise systems with technology ...
Page 4: ...Change course quickly ...
Page 6: ...Match performance with prudence ...
Page 8: ...Adopt technological brilliance ...
Page 10: ...Keep an eye on upkeep ...
Page 26: ...Matrix Protection Control Units T UW M X4 5 ...
Page 70: ...Accessories ...
Page 84: ...Control Circuit Wiring ...
Page 92: ...Mounting Termination ...
Page 135: ...SP 50567 R5 ...