29
Matrix
"
Redefining Modularity"
MTX4.5
MTX3.5EC
Basic Protection Unit
Communication Modules
(Modbus, Profibus, Zigbee)
Smart Card Module
Power Metering Module
Matrix releases designed for “Flexibility, Scalability & Customization” offer wide variety of withdrawable modules
such as Modbus, Profibus, Zigbee, Smart Configurator & Power metering. To start with one can go for a basic version
of MTX3.5 release and based on future needs and system demands, one can upgrade the protection release with
Power metering & Communication modules.
?
?
30
Matrix
Protection and Control Units
•
•
•
•
•
•
•
•
•
•
•
•
2
Overload, Short-circuit &
I t ON curve for Short-circuit
Inbuilt rating-plug through
Instantaneous protection with
& Earth-fault protection
DIP switches
adjustable current & time-
Current Metering in
Test button to check the
delay settings
MTX1.5G/1.5Gi through
health of protection release
Inbuilt Earth-Fault & neutral
3-line O-LED display
Self-powered protection
protection in MTX1G/1Gi &
Local fault annunciation
Inbuilt Zone Selective
MTX1.5G/1.5Gi
through LED indication &
Interlocking (ZSI) in MTX1Gi
Switchable thermal memory
pre-trip alarm
& MTX1.5Gi
for cable protection on
Front accessible test port
repetitive overloads
Query button for last trip
record
Features:
Protection parameters:
Parameters
MTX1.0
MTX1G
MTX1.5G
MTX1.5Gi
MTX1Gi
Protection: Enable/Disable
ü
ü
ü
ü
ü
OFF- 0.4-0.5-0.6-0.7-0.8-0.85-0.9-0.95-1
2
Pick-up (Ir)=In x... for I t
Instantaneous
Earth-Fault
2
I t OFF (tg)
-
0.1-0.2-0.3-0.4-1
Overload (Neutral)
Delay (tr) in s
-
Same as Overload Phase
Short-Circuit
Delay (ts)
20-100-200-300-400 ms
Overload (Phase)
Pre-alarm
-
0.8 x (fixed)
I
N
Pre-alarm
0.9 x (fixed)
Ir
Pre-alarm
0.5 x Is (fixed)
-
-
-
-
-
Pre-alarm
Short Circuit Enable/Disable
Earth Fault Enable/Disable
0.8 x Ig (fixed)
-
2
I t ON (tg)
0.1-0.2-0.3-0.4
Delay (tr) in sec
0.5-1-2-4-6-12-18-24-30
10
Thermal Memory ON/OFF
ü
ü
ü
ü
ü
Protection: Enable/Disable
-
ü
ü
ü
ü
2
I t ON/OFF
ü
ü
ü
ü
ü
ü
Protection: Enable/Disable
ü
ü
ü
ü
-
Protection: Enable/Disable
ü
ü
ü
ü
-
2
I t : ON/OFF
ü
ü
ü
ü
ü
ü
ü
ü
Protection: Enable/Disable
-
-
-
-
-
-
50%-100%-150%-200%
Pick-up (I )=Ir x...
N
0.6-1-1.5-2-3-4-6-8-10-12
Pick-up (Is)=In x...
OFF-1.5-2-3-4-6-8-10-12-15
Pick-up (Ip)=In x...
-
OFF-0.2-0.3-0.4-0.5-0.6
Pick-up (Ig)=In x...
Inbuilt-ZSI
-
-
?
UW-MTX 1.5G
?
UW-MTX 1.5Gi
UW-MTX1.0
?
UW-MTX1G/1Gi
UW-MTX1.5G/1.5Gi
?
UW-MTX 1G
?
UW-MTX 1Gi
Summary of Contents for OMEGA
Page 2: ...Stabilise systems with technology ...
Page 4: ...Change course quickly ...
Page 6: ...Match performance with prudence ...
Page 8: ...Adopt technological brilliance ...
Page 10: ...Keep an eye on upkeep ...
Page 26: ...Matrix Protection Control Units T UW M X4 5 ...
Page 70: ...Accessories ...
Page 84: ...Control Circuit Wiring ...
Page 92: ...Mounting Termination ...
Page 135: ...SP 50567 R5 ...