![Landis+Gyr Gridstream IV Series User And Installation Manual Download Page 62](http://html1.mh-extra.com/html/landis-gyr/gridstream-iv-series/gridstream-iv-series_user-and-installation-manual_673736062.webp)
Gyr
Chapter 6 - Performing System Upgrades
Concentrator User and Installation Guide
98-1031 Rev AA
59
Concentrator Verification
Verify that the concentrator has booted up with the latest firmware.
1.
Open a command window on your PC.
2.
Use your administrative credentials to login as control user.
3.
Type
oms -op getattr -class mcc -mccad 30000.1 -attrnm fWRevision -
remote
Bankcopy MCC
The Concentrator can send image data from B to memory location A. The Concentrator must be
running from location B to ensure the operation is successful.
Copy the image by typing
./utlICDownload - mccad 3000.1 -session 2 -bankcopy
Restarting a Download
You can interrupt a download to substitute a newer file than the one currently being downloaded.
1.
Suspend the client program by typing
C C
2.
Send a disconnect command. At the prompt type
utlICDownload -mccad 30000.1 -session 2 -disconnect
3.
Hot boot the concentrator.
Upgrading Concentrator Firmware Directly via Cable
You can connect a cable to the concentrator and upgrade interior components via direct cable
connection or through a wired intranet or hub. Following are direct upgrade procedures. To perform
these tasks you need:
•
a concentrator
•
a serial cable
•
an AC power cable
•
an intranet connection
•
a hub (optional)
•
an upgrade CD or link that includes rom.bin and image.bin files
•
Hyperterminal
•
a command prompt
•
Network Configuration Manager