Series IV Concentrator U and I Guide
98-1031 Rev AA
101
Power Cable Installation
Power Connection and Termination
Figure G - 1. Improper Power Termination
If power connections of this type are to be made, the 105627-000 and 105627-001 must be used.
Note that a drip loop at both at both ends of the cable is needed.
If using the 105704-000, 105704-001, 105704-002, or 105704-003 cables, the
end of the cable opposite the connector (the unterminated end) must be
installed in a junction box or other suitable enclosure.
Leaving the end of the cable exposed may allow water to migrate into the
cable and into the Concentrator.
See below for power cable installation procedures and details.