Operations

Union Location

A 1/8" N.P.T. plugged tapping accessible for test gauge 

connection shall be installed immediately upstream of 

the gas supply connection for the purpose of deter

-

mining gas supply pressure to the burner, and to 

prevent damage to gas valve.
If a manual gas shut off valve is not in the gas supply 

line within six feet of the machine and in an accessible 

location, one shall be installed.
A manual shut-off valve shall be installed in the gas 

supply line external to the appliance. See Figure 2. The 

gas line should be a separate supply direct from the 

meter to the burner. It is recommended that new pipe 

be used and located so that a minimum amount of work 

will be required in future servicing. The piping should be 

so installed as to be durable, substantial and gas tight. 

It should be clear and free from cutting burrs and 

defects in structure of threading. Cast iron fittings or 

aluminum tubing should not be used for the main gas 

circuit. Joint compounds (pipe dope) should be used 

sparingly on male threads only and be approved for all 

gases.

Propane Gas

The following pipe and stack sizes are just recommen

-

dations. Always consult a local plumber and venting 

contractor for local codes and regulations during instal

-

lation.
The following tables are maximum capacity of final 

stage pipe in thousands of Btu/hr of commercial 

propane

From first stage regulator (at tank) to second stage 

regulator

The chart below is based on incoming gas pressure of 

10 PSI and a pressure drop of 1 PSI. Numbers are for 

straight schedule 40 pipe; fittings further reduce 

capacity.

Length of Pipe 

(ft.)

Iron Pipe Size

1/2"

3/4"

10

3339

6982

20

2295

4799

30

1843

3854

40

1577

3298

50

1398

2923

60

1267

2649

70

1165

2437

80

1084

2267

90

1017

2127

100

961

2009

150

772

1613

200

660

1381

250

585

1224

300

530

1109

350

488

1020

400

454

949

450

426

890

500

402

841

Landa NG 3000 Operator’s Manual  8.913-942.0 - E

Location of union and drip 

leg for connecting conversion 

burner to house piping

Floor Level

1/8 in. N.P.T. Plugged 
Pressure Gauge Port

Flow

Union

Control Manifold

Manual 

Shut-off 

Valve

Tee

3 in. (76.2 mm)

MINIMUM

Pipe Cap

Summary of Contents for NG-3000

Page 1: ...8 913 942 0 E 08 20 21 NG Hot Water Generator Operator s Manual Heater Module MODELS NG 3000 1 103 901 0 For the Landa Dealer nearest you consult our web page at www landa com...

Page 2: ...2 Landa NG 3000 Operator s Manual 8 913 942 0 E Machine Data Label...

Page 3: ...uctions 18 Maintenance Preventative Maintenance 19 Winterizing Procedure 19 High Limit Hot Water Thermostat 19 Heating Coils 19 Gas Valve Regulator 20 Electrode Adjustment 20 Pilot Burner Adjustment 2...

Page 4: ...ts in good working condition They are listed in this general order Winterizing Procedure High Limit Hot Water Thermostat Heating Coils Gas Valve Regulator Electrode Adjustment Pilot Burner Adjustment...

Page 5: ...g parts please specify model and serial number Use only identical replacement parts This machine is to be used only by trained operators Important Safety Information NOTE This heater module NG 3000 is...

Page 6: ...machine with wet hands or while standing in water Always disconnect power before servicing WARNING Flammable liquids can create fumes which can ignite causing property damage or severe injury AVERTISS...

Page 7: ...ult in injury from a whipping wand AVERTISSEMENT Agripper la lance de nettoyage avec les deux mains avant de commencer Le non respect de cette consigne pourrait mener des blessures caus es par le mouv...

Page 8: ...ent 22 Never expose a spark or flame where there may be unburned gas present CAUTION This product incorporates parts that produce sparks and therefore when located in a garage it should be in a room o...

Page 9: ...High Pressure Nozzle not included Electric Cold Water Pressure Washer not included Vent according to local codes not included Burner Switch Spray Gun not included High Pressure Hose Not included Use...

Page 10: ...officials regarding any specific code or regu lations governing the installation The installation must conform to local codes The gas pressure coming out of the regulator and going to the burner ring...

Page 11: ...uit Joint compounds pipe dope should be used sparingly on male threads only and be approved for all gases Propane Gas The following pipe and stack sizes are just recommen dations Always consult a loca...

Page 12: ...rter Input BTU Per Hour Draft Hood Flue Pipe Size 250 000 320 000 8 inch 320 000 410 000 9 inch NOTE If the flue pipe exceeds 10 ft in length or contains more than two elbows use next size larger pipe...

Page 13: ...nd Testing Gas Piping The building structure should not be weakened by installing the gas piping The piping should not be supported by other piping but should be firmly supported with gas hooks straps...

Page 14: ...a soap solution With the main burner on coat pipe and tubing joints gaskets etc Bubbles indicate leaks 14 If the machine is installed in an enclosed room care should be taken to ensure that an adequa...

Page 15: ...Is there ample water supply Have all flammable liquids or gases been removed from installation location Is there adequate gas supply for the BTU rating of the burner Is incoming gas supply pressure to...

Page 16: ...from Pressure Washer Inlet Connector Control Knob Red Ignitor STEP 5 Depress control knob all the way and hold it in After five 5 seconds depress the red ignitor until you hear a loud click Repeat 3...

Page 17: ...If painted surfaces are peeling or chipping use extreme caution as pressure washer may remove the loose paint from the surface Keep the spray nozzle a safe distance from the surface you plan to clean...

Page 18: ...4 Turn water off Drain water from coil to prevent freezing STEP 2 Rinse detergent with fresh water if attached pressure washer is able to apply detergent STEP 3 After water has cooled turn the attache...

Page 19: ...o the discharge coupling fitting and by injecting compressed air all water will be blown out of the system The use of a draft diverter will prevent the wind chill factor from freezing the coil High Li...

Page 20: ...ly to prevent blockage Propane Gas Optional Conversion Kit General Safety Precautions Have a qualified gas service person assist in any gas burner installation or service Few maintenance people or mec...

Page 21: ...nning time desired Burner Features Operated Automatic Valve This machine is equipped with a thermopile self powered combination gas control This system is designed as a constant burning pilot Lighting...

Page 22: ...follows B Thermopile Output Reading Check B Reading Switch contacts OPEN Main burner OFF If the minimum 250 millivolt reading is not obtainable readjust pilot for maximum millivolt output If millivol...

Page 23: ...Restricted pilot line or clogged pilot orifice Clean pilot tubing and orifices PILOT LIT BUT MAIN BURNER WON T COME ON Faulty wiring Test wiring Low pilot flame Check inlet pressure pilot orifice pos...

Page 24: ...24 Notes Landa NG 3000 Operator s Manual 8 913 942 0 E...

Page 25: ...25 Parts Parts LANDA NG 3000 Landa NG 3000 Operator s Manual 8 913 942 0 E...

Page 26: ...913 942 0 E 35 41 37 25 36 33 34 14 28 27 26 42 47 50 62 63 30 49 32 48 31 29 30 68 16 3 4 5 10 9 7 6 2 8 38 13 40 37 21 60 52 15 19 71 20 53 37 25 36 44 50 22 17 18 72 11 12 39 53 37 69 43 51 66 67 2...

Page 27: ...18 9 802 678 0 1 IGNITOR PIEZO 19 8 719 968 0 1 HOLDER WAND ZINC PLATED 20 9 802 807 0 9 WASHER 3 8 SAE FLAT 21 9 802 779 0 8 NUT 3 8 ESNA 22 9 800 031 0 1 LABEL PILOT LIGHT WARNING 23 8 706 236 0 1...

Page 28: ...EL MANUFACTURER S CLEANING SOLUTION 56 9 800 021 0 1 LABEL HOT WATER OUTLET 57 9 803 563 0 1 CONNECTOR 1 4 TUBE X 1 8 MPT 58 8 706 910 0 1 BUSHING 1 4 X 1 8 PIPE 59 9 802 682 0 1 TAB GROUND 60 9 802 7...

Page 29: ...29 Landa NG 3000 Operator s Manual 8 913 942 0 E Notes...

Page 30: ...8 913 942 0 Printed in U S A...

Reviews: