![lancer Sensation 44 Operation Manual Download Page 11](http://html.mh-extra.com/html/lancer/sensation-44/sensation-44_operation-manual_672772011.webp)
11
Dispenser Setup
1. Turn on water source.
2. Open the pressure relief valve located on the front of the
unit, by flipping up on the valve cap lever. Hold open until
water flows from the relief valve then close (flip down) the
relief valve.
The dispenser must be properly electrically grounded
to avoid serious injury or fatal electrical shock. The
power cord has a three-prong grounded plug. If a
three-hole grounded electrical outlet is not available,
use an approved method to ground the unit. Follow
all local electrical codes when making connections.
Each dispenser must have a separate electrical circuit.
Do not use extension cords. Do not connect multiple
electrical devices on the same outlet.
F
WARNING
6. Test the motor operation by pushing both ice chute levers
until agitator motor begins to turn.
7.
Activate each valve to ensure a good flow of water is
achieved.
8.
Ensure pump deck is turned OFF before turning on CO
2
.
A. Regulator Adjustment Screw
B. Adjust to 110 psi (0.758 MPa)
C. Wrench
A
B
C
The pump deck has a 3 minute timeout feature. If the
timeout occurs, turn the deck OFF then ON by flipping
the switch on the control box.
NOTE
To check for CO
2
leaks, close the valve on the CO
2
cylinder and observe if the pressure to the system
drops with the cylinder valve closed for five minutes.
Open the cylinder valve after check.
NOTE
14. Activate each valve to purge air from the syrup lines.
9. Turn on CO
2
at the source then, using a screwdriver, adjust
the high pressure regulator at the source to 110 psi (0.758
MPa) then tighten locknut with wrench.
7. Repeat Step 6 for both low pressure CO
2
regulators on the
regulator manifold routed to the unit and the syrup pumps.
DO NOT TURN ON CO
2
SUPPLY AT THIS TIME
!
WARNING
6. Using a wrench, loosen lock nut on the regulator
adjustment screw of the high pressure CO
2
regulator
connected to the source, then using a screwdriver back out
lock nut screw all the way.
A. CO
2
Regulator
B. Screwdriver
C. Regulator Adjustment Screw
A
B
C
A
B
C
D
A. Line to Dispenser
B. Line to Syrup Pumps
C. Line to CO
2
Regulator
D. CO
2
Regulator Manifold
5. Connect tubing routed from the tee at the syrup pumps
to the second outlet of the low pressure CO
2
regulator
manifold.
A
B
A. Pressure Relief Valve
B. CO
2
Inlet
3. Verify all Bag-In-Box contains syrup and check all
connections for leaks.
4.
Place enough ice in the ice bin to fill approximately 1/2 of
the bin before plugging in the unit.
5. Connect unit power cord to grounded electrical outlet.
10. Adjust both of the low pressure regulators on the regulator
manifold to 75 psi (0.517 MPa) then tighten locknut with
wrench.
11. Activate each valve until gas-out.
12. Plug in the remote carbonator pump deck, if not already
done so, and turn the switch to the ON position.
13. Activate each valve until the carbonator pump comes on.
Release the button, allow carbonator to fill and stop.
Repeat this process until a steady flow of carbonated water
is achieved.
Summary of Contents for Sensation 44
Page 25: ...25 Flavor Shot Box Plumbing Diagram Unit Plumbing Diagram ...
Page 26: ...26 Wiring Diagram 115 Volt ...
Page 27: ...27 Wiring Diagram 220 240 Volt ...
Page 29: ...29 ...