background image

1.3

SELECTING COUNTER LOCATION (SEE FIGURE 1)

WARNING

THIS APPLIANCE MUST BE EARTHED.  THIS DISPENSER MUST BE ELECTRICALLY
GROUNDED TO AVOID DANGER TO THE OPERATOR.  THE POWER CORD PROVIDED HAS
A THREE PRONG GROUNDED PLUG.  IF A THREE HOLED GROUNDED ELECTRICAL
OUTLET IS NOT AVAILABLE, USE AN APPROVED METHOD OF INSURING A PROPER
GROUND TO THE DISPENSER.

CAUTION

FAILURE TO DISCONNECT THE MOTOR POWER SUPPLY WILL DAMAGE THE CARBONATOR
MOTOR AND PUMP AND VOID THE WARRANTY.

A. Select a location close to a properly grounded 20 Amp electrical outlet, convenient to an open

type drain, access for soda, water, and syrup lines.  It should have sufficient clearance above
the unit to provide for servicing.

1.

If at all possible, location should be away from direct sunlight or other heat sources.

2.

Connecting lines may be run through access in back of the unit or extend down through a
counter cutout.

3.

Check the dispenser serial number plate for correct electrical requirements of unit.  

Do not

plug into wall electrical outlet unless the current shown on the serial number plate agrees with local
current available.

4.

The counter must support the weight of the dispenser, ice, and possibly an icemaker.  

Total

weight may exceed 800 pounds (363.6 kg).

B. Unit may be installed directly on the countertop or on optional leg kit (PN 82-3484).  If installed

directly on the counter, the unit must be sealed to the countertop.  

If an icemaker is to be 

mounted on top of dispenser, do not install dispenser on legs.

NOTE

Water pipe connections and fixtures directly connected to a potable water supply must all be
sized, installed, and maintained according to Federal, State, and Local laws.

The water supply must be protected by means of an air gap, a backflow prevention device
(located upstream of the CO

2

injection system) or another approved method to comply with NSF

standards.  A backflow prevention device must comply with ASSE and local standards.  

It is the

responsibility of the installer to ensure compliance.

C.

Location must insure sufficient clearance

on sides, top and back of unit is provided for 

ventilation and air circulation (see Figure 1).

D. Additionally, if an ice maker is not top mounted on the unit, sufficient clearance should be 

provided [a minimum of 16 inches (40.6 cm) is recommended] to allow filling the unit with ice
from a five (5) gallon (19 liter) container (see Figure 1).

1.4

INSTALLING THE DISPENSER

A. Remove Cup Rest, Drip Tray, Splash Plate, and Top Cover.
B. Remove Cover Plate at rear of unit if not a through-the-counter installation.
C. Connect plain water supply line and water supply for carbonator to the 3/8 inch barb fittings at

the front of the unit (See Figure 2).

D. For the 

plain water supply line

, the inlet water 

flowing pressure

should be 

at least 75 PSI

.

If the water pressure is lower than 75 psi flowing, a Water Booster system must be used

.

NOTE:

The Lancer Water Booster/Tank, PN 

MC-163172

, is offered as a kit.

The Water Booster must be installed as close as possible to the plain water circuit inlet.

If the water flowing pressure is lower than 75 PSI at the plain water inlet, and a water booster
is NOT installed, all water products will not hold a proper flow rate and/or water/syrup ratio.
Additionally, flow conditions at the nozzle may be affected, for example, poor nozzle coning and
mixing.

2

Summary of Contents for 14800 Series

Page 1: ...WIDE 8 BRANDS 12 FLAVORS 115V 60Hz 85 14810 12 ICE BEVERAGE DISPENSER ABOVE COUNTER MULTI BRAND 30 INCH WIDE 10 BRANDS 12 FLAVORS 115V 60Hz 85 14810N 12 ICE BEVERAGE DISPENSER ABOVE COUNTER MULTI BRA...

Page 2: ...TATION IT MAY ACTIVATE UNEXPECTEDLY DO NOT PLACE HANDS OR FOREIGN OBJECTS IN THE ICE STORAGE COMPARTMENT WHEN UNIT IS BEING SERVICED CLEANED OR SANITIZED UNPLUG DISPENSER FROM THE POWER SOURCE NOTE La...

Page 3: ...vd San Antonio TX 78219 Phone 800 729 1500 Local Service Name __________________________________________ Local Service Phone ________________________________________ ii TABLE OF CONTENTS SPECIFICATION...

Page 4: ...arton and remove interior packing D Lift carton up and off of the dispenser E Remove wood shipping base from the bottom of the dispenser Support dispenser while removing shipping base to prevent damag...

Page 5: ...a potable water supply must all be sized installed and maintained according to Federal State and Local laws The water supply must be protected by means of an air gap a backflow prevention device loca...

Page 6: ...g at the front of the unit See Figure 3 Check for leaks G Connect syrup supply lines to the 3 8 inch barb inlet fittings at the front of the unit See Figure 4 using BIB Bag In Box pumps Check for leak...

Page 7: ...asures syrup vacuum in the Pump Inlet Line When the Syrup Package is empty the Pump increases vacuum causing the device to shut off the gas pressure to stop the Pump The Lancer Sold Out automatically...

Page 8: ...tion may be used as long as it is prepared in accordance with the manufacturer s written recommendations and safety guidelines and provides 50 to 100 parts per million PPM available chlorine Sanitizin...

Page 9: ...ll the shroud up and out see Figure 8 Figure 7 Figure 8 H Using cleaning solution described in Section 2 2 and a clean cloth or soft brush clean all removable parts sides of Ice Bin Ice Chute and surf...

Page 10: ...tank and pressurize L Activate valve and draw sanitizing solution through line for a minimum of 60 seconds This will ensure line is flushed and filled with sanitizing solution Allow line to stand for...

Page 11: ...RATE AND ADJUST THE LANCER FS30 3 1 NORMAL OPERATION A Fill cup with desired amount of ice B Place cup under nozzle below desired brand C Select up to two 2 desired bonus flavors from those available...

Page 12: ...Y DISPENSE DELAY V 1 B1 DLY1 FS 16 SETUP PC MODE SET PC MODE OFF ON FS 16 SETUP PC TIME ON TIME MSEC 05000 FS 16 SETUP ICE STIR OFF OFF TIME MIN 00060 ON TIME MSEC 02000 CARB SENSORS UPPER LOWER 307 5...

Page 13: ...the relief valve Allow pressure on the regulator to drop and then lock the relief valve lever into place D Turn the pressure adjusting screw on the CO2 regulator clockwise until there is resistance Op...

Page 14: ...t of the pump 5 Unscrew the mounting bracket 6 Part should easily slide out for replacement maintenance 3 8 PRIMING THE SYRUP PUMP AT THE CORRECT PRESSURE For the Syrup Pump to operate correctly it is...

Page 15: ...d C PC Board defective C Replace PC Board D Solenoid bracket screwed D Unscrew solenoid bracket raise too low and not opening solenoid and re screw bracket completely 4 6 Push Chute Ice Door A Dispens...

Page 16: ...yrup A Check pressure and adjust supply not at minimum flowing pressure B Foreign debris in water and or B Remove flow control from syrup flow control suspected valve and clean out any foreign materia...

Page 17: ...ly seated B Reattach door assembly to dispenser 4 22 Circuit breaker tripping A Valve wire harness es A Detect short by disconnecting valve shorted to itself or Faucet harnesses from Switch Panel Plat...

Page 18: ...carbonator C Replace carbonator pump pump D Backflow preventer not D Replace backflow preventer allowing water to flow noting the flow direction arrow from pump to coldplate E Probe malfunctioning E R...

Page 19: ...16 NOTES Please refer to the Lancer web site www lancercorp com for information relating to Lancer Installation and Service Manuals Instruction Sheets Technical Bulletins Service Bulletins etc...

Page 20: ...1 2 3 4 11 10 9 5 13 14 6 8 7 12 20 19 18 15 16 17 21 23 22 24 25 29 27 26 28 30 31 32 34 35 36 38 37 39 40 41 33 6 ILLUSTRATIONS AND PARTS LISTINGS 6 1 FINAL ASSEMBLY 17...

Page 21: ...14 82 3286 01 Switch Assy MB 2L 2R 15 19 0262 01 Valve Assy LFCV 0 2 Syrup Injection Natural 16 19 0261 02 Valve Assy LFCV 4 5 Soda Water Gray Item Part No Description 18 Item Part No Description 17 1...

Page 22: ...9 8 11 ITEM PART NO DESCRIPTION QTY X X 1 02 0577 Grommet Rubber 3 G3002 X X 2 03 0368 Retainer Pin 1 Agitator IBD X X R 3 05 2293 01 Ice Shroud IC 1 X X R 4 23 1401 Agitator Assy 1 Helical IC HEX X 5...

Page 23: ...UMP BIN AGITATE ICE DOOR ICE MAKER OPTIONAL LOW ALARM ICE SWITCH BIN SWITCH OPTIONAL CANCEL ENTER LANCER FS16 KEY CARB PUMP TOP VIEW ICE LINK MDB ADDRESS SWITCH NUMBER SWITCH NUMBER 1 X O O O 2 O X O...

Page 24: ...T T I N G S CO 2 IS3 3 IS4 2 IS4 1 IS3 2 IS3 1 IS2 3 IS2 2 IS2 1 IS1 3 IS1 2 IS1 1 S1 3 S1 2 S1 1 S2 2 S2 1 S1 4 S3 1 S2 4 S2 3 S3 2 S3 3 S3 4 S4 2 S4 3 S4 4 S4 1 SODA1 SODA2 WATER2 SODA3 SODA4 WATER3...

Reviews: