26
Call 1-888-370-6531 for Technical Support
The wires should be approximately centered between the nozzle and retention head
opening.
The leading edge of the Flame Retention Head is recessed approximately 1/16” (1.5
mm) into the Air Tube.
Retention Head is centered within the Air Tube. If not centered, straighten the centering
Tabs of the Retention Head if they are bent. Loosen the panel nut, center the Retention
Head and retighten the panel nut if necessary.
Make sure Air Distribution Plate is properly installed, as shown above.
Make sure to perform startup (5.4.2) and system checks (5.4.3) after every
maintenance cycle. Record the checks, maintenance performed, and gauge readings in the
maintenance log.