background image

14

The most common set values:

Set value

Setting range Comment

Room temperature

21.5°C 5–45°C

Room temperature set value set by the user. During the night reduction, the 
regulator uses the calculated room temperature value.

Effect of night reduc-
tion

0°C

0–35°C

The amount of night reduction for output water activated using a timer, an exter-
nal home/away switch or GSM control.

Minimum limit

15°C

5–95°C

The lowest permitted temperature for output water. Setting the minimum level 
of floor heating for tiled floors to 20–25°C ensures comfortable heating and the 
evaporation of moisture in the summer.

Maximum limit

45°C

15–125°C

The highest permitted temperature for output water. The maximum limit can be 
used to prevent temperatures that are too high (for example, caused by an error 
when setting the control characteristic) as well as possibly damage to the piping 
and surface materials. For floor heating, set at 35–40°C.

Room compensation 
ratio

1.5°C 0–7.0°C

If the room temperature diverges from the set value, the room compensation function 
adjusts the temperature of the output water. For example, when the compensation 
setting is at 4, the function reduces the temperature of the output water by 6°C after an 
increase of 1.5°C in room temperature (4 x 1.5°C = 6°C).

Autumn drying

1°C

0–15°C

The autumn drying function automatically increases the temperature of output 
water in the autumn for 20 days. The function is switched on when the average 
daily temperature has been over 7°C for at least 20 consecutive days and then 
drops below 7°C.  The function is on for the following 20 days when the average 
daily temperature is below 7°C. The set value for the function shows how much the 
function increases the temperature of the output water. The factory setting is 1°C.

Closing the valve for 
the summer

20°C

5–50°C

The outdoor temperature limit at which the regulator closes the valve for regu-
lating circuit L1. Regulating circuit L2 is often used for heating humid spaces. 
Humid spaces also need to dry in the summer, so the valve in regulating circuit 
L2 is not closed.

Minimum limit for the 
temperature for the 
upper part of the water 
tank

55°C

5–75°C

If the temperature for the upper water tank (measurement 9) falls below the set 
value, the measurement allows the compressor to start. The compressor will start 
provided the temperature in the lower tank (measurement 10) does not prevent 
it doing so.

Minimum limit for the 
temperature for the lower 
part of the water tank

45°C

20–50°C

The regulator starts the compressor if the temperatures of the upper water tank 
(measurement 9) and the lower water tank (measurement 10) fall below the 
minimum limit.

Water for use

55°C

5–80°C

Set value for water for use. (Recommendation > +55°C)

The  operating  efficiency  of  the  device  may  vary  due  to  the  geographical  location.  The  annual  operating  efficiency 
reaches its optimal point when the water tank temperature is maintained at the correct level. The factory setting for 
the minimum set value for the lower part of the water tank is +45°C (30–50). The factory setting for the minimum set 
value for the upper part of the water tank is +55°C (5–55). As a rule, the set values of the water tank are kept as low 
as possible to allow for the best annual operating efficiency possible.

During the winter, when the need for heating is great, the set value for the lower part of the water tank should be 
determined in relation to the temperature of the output water. The temperature of the upper part of the water tank 
increases after a long period of use and the threshold value for the compressor to run is 95°C. 

This is due to the super-heating properties of the water tank structure. This is why a mixing valve for hot water must 
be used in order to prevent any risk of burns from the scalding hot water. The compressor is controlled, as a rule, 
according to the minimum setting of the lower part of the water tank.

During the summer, when there is no need for heating (with the exception of humid rooms), the compressor is seldom 
on and there is not enough super-heating to produce hot water for use. In this case, the minimum temperature of the 
upper part of the water tank can be maintained at +55°C and the compressor will be controlled according to the 
minimum temperature of the upper part of the water tank.

Summary of Contents for V 13.0

Page 1: ...1 Ground source heat pumps since 1983 USER MANUAL L MP SS V 7 0 30 0 L MP SS 3 2010 As Long As the Sun Exists Let Mother Earth Heat Your Home...

Page 2: ...2...

Page 3: ...nd loop 7 2 4 Filling and de aeration of the ground loop 8 2 5 Heating connection 9 2 6 Domestic water connection and circulation of water 9 2 7 HEPAC check list 10 2 8 Electrical installation and out...

Page 4: ...4...

Page 5: ...first time Press the motor protective switch down and switch on the power This stops the compressor starting and enables the electrical immersion to heat up the compressor and water in the storage ta...

Page 6: ...dhw Ground source heat pump The heat collection pipe is a plastic pipe PEM 40 10 with a water and ethyl alcohol or glycol water mixture circulating inside It is placed 1 1 2 metres deep in the ground...

Page 7: ...ound loop pipes and the feed pipes have been installed correctly 2 2 Pipe laying Assemblies on top of the heat pump Assemblies V7 0 V15 0 V20 0 V30 0 1 2 4 3 6 5 8 7 9 10 Sensor Electrical supply Dome...

Page 8: ...fluid mixture ethyl alcohol water or glycol with a frost resistance of 17 degrees Celsius 8 turn on the submersible pump 9 add the water and ethyl alcohol mixture to the mixing container until no mor...

Page 9: ...ork These connections stop sound from passing into the pipes All heating connections for example a heating radiator for an air conditioner or a heated towel rail must be made to the heat piping When t...

Page 10: ...OR TYPE Outdoor sensor TMO T1 2 X 0 7 mm2 Room sensor TMR T3 2 X 0 7 mm2 Size of the feeder cable part 5 X 2 5 mm2 6 0 mm2 If installation conditions require long cabling a 5 x 6 mm2 cable should be u...

Page 11: ...ump Check the measured set values The ground loop pump is rotating in the wrong direction Switch the location of the two phases Shut off valves are in the fill position Check that the deaeration and f...

Page 12: ...is a characteristic hea ting curve of exactly the correct shape The shape of the heating curve depends on three different values which determine the temperature of the water going to the heater when o...

Page 13: ...2 Settings The L mp ss regulator is controlled using set values The available set values depend on the sensor connections and geothermal heating options Browsing the set values and changing them is do...

Page 14: ...ting circuit L2 is not closed Minimum limit for the temperature for the upper part of the water tank 55 C 5 75 C If the temperature for the upper water tank measurement 9 falls below the set value the...

Page 15: ...r temperature Outdoor temperature 50 50 C 2 L1 Output water The temperature of output water in regulating circuit 1 0 130 C 3 L1 Room Room temperature in regulating circuit 1 room compensation 10 80 C...

Page 16: ...h the regulator No action required The compressor has been stopped for less than 5 minutes No action required Fuse problem Check the condition of the fuses in the master switchboard The compressor doe...

Page 17: ...n required The compressor is on all the time or for long periods of time A lot of heat is needed for example the outdoor tempera ture is very low or the structure is drying during the first year s use...

Page 18: ...ow part A 3 x 16 3 x 16 3 x 16 20 3 x 16 20 3 x 16 20 3 x 20 3 x 25 Electrical connection 230 V 1N Supplied output 35 50 C kW 7 55 7 05 9 45 8 85 11 2 10 45 Supplied input 35 50 C kW 1 66 2 17 2 18 2...

Page 19: ...existence of an appropriately completed and issued warranty certificate and a certificate signed by the user stating that the mechanic instructed the user on how to operate the equipment 6 APPENDIX Cu...

Page 20: ...position OFF 2 Adjust hyseresis current and delay srews from the front main fuse 25A Hysteresis 21 Current 25 28 Delay 1s Relay need external power 24 240 V AC External power connect connectors A1 an...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ......

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ...L MP SS IS A TRADEMARK OF SUOMEN L MP PUMPPUTEKNIIKKA OY ALL RIGHTS RESERVED SUOMEN L MP PUMPPUTEKNIIKKA OY PO BOX 49 FIN 62101 LAPUA WWW LAMPOASSA COM R...

Reviews: