background image

11

Ground source heat pumps since 1983

2.9. Electricity check list 

Check that 

•  all phases going to the switchboard are in the correct phase sequence

•  the fuse size is correct (slow)

2.10. Startup

Before startup, check that:

•  the heating system has been connected, filled and deaerated appropriately

•  the ground loop has been installed, filled and deaerated appropriately 

•  electrical connections have been made appropriately and the outdoor sensor (room sensor, optional accessory) 

has been installed

Possible problems during startup

Problem

Cause

Solution

Fuses always blow when the 
compressor is being started.

You are using the wrong type of fuse.

Check that the fuse is automatic: C or D/ceramic 
fuse: SLOW or with a snail icon.

Temporary connections at the site are causing an 
overload on the fuses.

Reduce load.

The ground loop pump does 
not start.

The regulator may not be getting any power.

Check the regulator fuse.

The regulator is not authorised to start the pump. Check the measured/set values.

The ground loop pump is rotating in the wrong 
direction.

Switch the location of the two phases.

Shut-off valves are in the fill position.

Check that the deaeration and fill valves are in 
the ‘closed’ position and that the intermediate 
valve is open.

The compressor runs for a 
little while and the steam 
pressure switch goes off.

There may still be air in the ground loop.

Deaerate the ground loop.

There may be a leak in the refrigerant loop.

Contact the manufacturer.

The fluid level in the ground 
loop fill container drops 
suddenly after startup.

There is a leak in the system (the smell of ethyl 
alcohol is strong), there is a leak in the ground 
loop or there is still air in the ground loop.

Check the condition of valves in the deaeration 
group on the air lock and the shaft seal on the 
ground loop pump and, if possible, the ground 
loop extension joints, or deaerate. 

Thermal relays go off when 
starting.

The compressor or the ground loop pump is short-
circuited or one of the phases is not activated.

Check electrical connections.

Fuses in the master switchboard of the building 
are faulty.

Check and replace fuses as required. 

Summary of Contents for V 13.0

Page 1: ...1 Ground source heat pumps since 1983 USER MANUAL L MP SS V 7 0 30 0 L MP SS 3 2010 As Long As the Sun Exists Let Mother Earth Heat Your Home...

Page 2: ...2...

Page 3: ...nd loop 7 2 4 Filling and de aeration of the ground loop 8 2 5 Heating connection 9 2 6 Domestic water connection and circulation of water 9 2 7 HEPAC check list 10 2 8 Electrical installation and out...

Page 4: ...4...

Page 5: ...first time Press the motor protective switch down and switch on the power This stops the compressor starting and enables the electrical immersion to heat up the compressor and water in the storage ta...

Page 6: ...dhw Ground source heat pump The heat collection pipe is a plastic pipe PEM 40 10 with a water and ethyl alcohol or glycol water mixture circulating inside It is placed 1 1 2 metres deep in the ground...

Page 7: ...ound loop pipes and the feed pipes have been installed correctly 2 2 Pipe laying Assemblies on top of the heat pump Assemblies V7 0 V15 0 V20 0 V30 0 1 2 4 3 6 5 8 7 9 10 Sensor Electrical supply Dome...

Page 8: ...fluid mixture ethyl alcohol water or glycol with a frost resistance of 17 degrees Celsius 8 turn on the submersible pump 9 add the water and ethyl alcohol mixture to the mixing container until no mor...

Page 9: ...ork These connections stop sound from passing into the pipes All heating connections for example a heating radiator for an air conditioner or a heated towel rail must be made to the heat piping When t...

Page 10: ...OR TYPE Outdoor sensor TMO T1 2 X 0 7 mm2 Room sensor TMR T3 2 X 0 7 mm2 Size of the feeder cable part 5 X 2 5 mm2 6 0 mm2 If installation conditions require long cabling a 5 x 6 mm2 cable should be u...

Page 11: ...ump Check the measured set values The ground loop pump is rotating in the wrong direction Switch the location of the two phases Shut off valves are in the fill position Check that the deaeration and f...

Page 12: ...is a characteristic hea ting curve of exactly the correct shape The shape of the heating curve depends on three different values which determine the temperature of the water going to the heater when o...

Page 13: ...2 Settings The L mp ss regulator is controlled using set values The available set values depend on the sensor connections and geothermal heating options Browsing the set values and changing them is do...

Page 14: ...ting circuit L2 is not closed Minimum limit for the temperature for the upper part of the water tank 55 C 5 75 C If the temperature for the upper water tank measurement 9 falls below the set value the...

Page 15: ...r temperature Outdoor temperature 50 50 C 2 L1 Output water The temperature of output water in regulating circuit 1 0 130 C 3 L1 Room Room temperature in regulating circuit 1 room compensation 10 80 C...

Page 16: ...h the regulator No action required The compressor has been stopped for less than 5 minutes No action required Fuse problem Check the condition of the fuses in the master switchboard The compressor doe...

Page 17: ...n required The compressor is on all the time or for long periods of time A lot of heat is needed for example the outdoor tempera ture is very low or the structure is drying during the first year s use...

Page 18: ...ow part A 3 x 16 3 x 16 3 x 16 20 3 x 16 20 3 x 16 20 3 x 20 3 x 25 Electrical connection 230 V 1N Supplied output 35 50 C kW 7 55 7 05 9 45 8 85 11 2 10 45 Supplied input 35 50 C kW 1 66 2 17 2 18 2...

Page 19: ...existence of an appropriately completed and issued warranty certificate and a certificate signed by the user stating that the mechanic instructed the user on how to operate the equipment 6 APPENDIX Cu...

Page 20: ...position OFF 2 Adjust hyseresis current and delay srews from the front main fuse 25A Hysteresis 21 Current 25 28 Delay 1s Relay need external power 24 240 V AC External power connect connectors A1 an...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ......

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ...L MP SS IS A TRADEMARK OF SUOMEN L MP PUMPPUTEKNIIKKA OY ALL RIGHTS RESERVED SUOMEN L MP PUMPPUTEKNIIKKA OY PO BOX 49 FIN 62101 LAPUA WWW LAMPOASSA COM R...

Reviews: