Lambrecht EOLOS-IND Manual Download Page 8

Manual
Weather Sensor EOLOS-IND Modbus 

(1643) EOLOS-IND Modbus 

  

 

      Manual 

Modbus Protocol

The Lambrecht meteo Modbus sensors and the met[LOG] follow the specifi cation of the Modbus organization: “MODBUS 
APPLICATION PROTOCOL SPECIFICATION V1.1b3” (see www.modbus.org).

6.1 

Data Encoding

MODBUS uses the „big-endian“ format for addresses and data. This means that if a value is transmit-ted with a number 
format that is larger than a single byte, the „most signifi cant byte“ is sent fi rst. For values that go beyond one register (e.g. 
32 bit) this is not clearly specifi ed for the Modbus. In these cases (32 bit or 64 bit) the LAMBRECHT Modbus sensors follow 
the big-endian number format.

Example Big-Endian:

Register size value 
16 - bits 0x1234 is transmitted in the order: 0x12 0x34.

Example big-endian (32 bit or 64 bit):

Register size value 
32 - bits 0x12345678 is transmitted in the order: 0x12 0x34 0x56 0x78.

6.2 

Device Address

The addresses 1...247 are permitted for Modbus.

6.3 

Standard Confi guration - Default

Baud rate: 

19200 Baud

Address: 

Each sensor type (or family) has its own default address. 

Default addresses of the LAMBRECHT sensors:

Address Sensor

1 Wind speed
2 Wind direction
3 Precipitation rain[e]
4 THP
5 EOLOS IND
6 com[b]
7 PREOS
8 ARCO
9 u[sonic]

10 Pyranometer 2nd Class

11  Secondary standard Pyranometer

12 PT100 to Modbus converter (temperature)

Byte frame according to MODBUS standard for RTU mode: 
8E1 (1 start bit, 8 data bits, 1 parity bit (even parity), 1 stop bit)

6.4 

Modbus Command Set

The LAMBRECHT Modbus sensors support the following commands:
•  Read Input Register” command:   

0x04

 (measured data)

•  Write Multiple Register” command: 

0x10

 (Write sensor data)

8

Summary of Contents for EOLOS-IND

Page 1: ...egrated overvoltage protection Simple space saving assembly on 50 mm standard pipe The Perfect Weather Sensor For industrial use as well as under extreme environmen tal conditions 5 1 1 parameters in...

Page 2: ...Mounting 2 7 1 North Alignment of Wind Sensor 2 7 2 Power and Signal Connection 2 7 3 Safety Regulations 3 Maintenance 3 1 Regular Maintenance and Calibration 3 2 Visual Check and Cleaning 4 Transport...

Page 3: ...is method Lightweight mass and immovable measuring elements to enable very low starting values distance and attenuation constants as well as a very high repetition accuracy The sensor can be installed...

Page 4: ...t the mast if available If needed you can turn in or unscrew the pin by means of allen key 2 7 1 North Alignment of Wind Sensor For wind direction measurements the north mark on the sen sor must be al...

Page 5: ...signal of the sensor corresponds to the RS 485 standard The signal levels allow transmission via shielded signal cables up to a maximum length of 1 200 meters or 4 000 feet The cable lengths depend o...

Page 6: ...ngsscraube M8 fastening screw Erdscraube M6 earthing screw 10 1 5 6 0 1 P40 min P50 P48 3 5 6 0 1 10 1 min 40 P40 min 50 9 P 0 1 Aufnahmerohr f r den Sensor sensor seat pipe N Schlitz im Mastende baus...

Page 7: ...ensor EOLOS IND Modbus 1643 EOLOS IND Modbus Manual 7 IN 24 V DC f r Elektronik for electronic Schirm shield Erde earth 287 56 0RGEXV 578 1 2 3 4 1 2 3 4 br wt bl bk PIN color 5 5 N A br ws bl sw Farb...

Page 8: ...is transmitted in the order 0x12 0x34 Example big endian 32 bit or 64 bit Register size value 32 bits 0x12345678 is transmitted in the order 0x12 0x34 0x56 0x78 6 2 Device Address The addresses 1 247...

Page 9: ...stantaneous value r h 10 1 decimal place INT 30602 Humidity mean value since last retrieval r h 10 1 decimal place INT 30603 Humidity maximum value r h 10 1 decimal place INT 30604 Humidity minimum va...

Page 10: ...HT meteo o er the possibility of autocon guration This is supported e g by the data logger met LOG For autocon guration the register addresses of the measured values and sensor data available in the r...

Page 11: ...imal places LONG 0x04 Big Endian WORD 31102 Precipitation amount total Low WORD 3 decimal places Registers 31101 31102 can only be read out together function code 0x04 0x04 Big Endian WORD 31201 Preci...

Page 12: ...s 1 Dew point maximum value INT 46020 30703 Register address 1 Dew point minimum value INT 46021 30801 Register address 1 Air pressure instantaneous value INT 46022 30802 Register address 1 Air pressu...

Page 13: ...100 r h Parameters Wind direction Measuring range 0 360 Accuracy 3 RMS Resolution 1 Wind speed Measuring range 0 1 50 m s Accuracy 0 5 m s 5 RMS of the meas value at 5 1 40 m s Resolution 0 1 m s Air...

Reviews: