Lambrecht EOLOS-IND Manual Download Page 11

Manual
Weather Sensor EOLOS-IND Modbus 

(1643) EOLOS-IND Modbus 

  

 

      Manual

Register 
address

Parameter name 

Unit

Factor Description

Data 
type

Func-
tion-
code

Storage-
type 
>16 bit

30001 Wind speed 

instantaneous value

m/s

10

1 decimal place

INT

0x04

Big-Endian 
WORD

30201 Wind direction 

instantaneous value

°

10

1 decimal place

INT

0x04

Big-Endian 
WORD

30401 Air temperature 

instantaneous value

°C

10

1 decimal place

INT

0x04

Big-Endian 
WORD

30601 Humidity 

instantaneous value

% r.F.

10

1 decimal place

INT

0x04

Big-Endian 
WORD

30701 Dew point 

instantaneous value

°C

10

1 decimal place

INT

0x04

Big-Endian 
WORD

30801 Air pressure 

instantaneous value

hPa

10

1 decimal place

INT

0x04

Big-Endian 
WORD

31001 Precipitation amount 

total

mm

10

1 decimal place

INT

0x04

Big-Endian 
WORD

31101 Precipitation amount 

total (High-WORD)

mm

1000

3 decimal places

LONG

0x04

Big-Endian 
WORD

31102 Precipitation amount 

total (Low-WORD)

3 decimal places
Registers 31101 + 31102 can 
only be read out together. 
(function code 0x04)

0x04

Big-Endian 
WORD

31201 Precipitation intensity 

1-minute sliding

mm/min

1000

= average (1-min.)
3 decimal places
Time base = 1 min.
Meas. rate = 6x per min.

INT

0x04

Big-Endian 
WORD

31401 Global radiation 

instantaneous value

W/m

2

10

1 decimal place

INT

0x04

Big-Endian 
WORD

31501 Global radiation 

instantaneous values 
(High-WORD)
(temperature compen-
sated)

W/m

2

100

2 decimal places
Registers 31501 + 31502 can 
only be read out together. 
(function code 0x04)

LONG

0x04

Big-Endian 
WORD

31502 Global radiation 

instantaneous values 
(Low-WORD)
(temperature compen-
sated)

0x04

Big-Endian 
WORD

31591 Global radiation 

instantaneous values 
(High-WORD)
(uncompensated)

W/m

2

100

2 decimal places
Registers 31591 + 31592 can 
only be read out together. 
(function code 0x04)

LONG

0x04

Big-Endian 
WORD

31592 Global radiation 

instantaneous values 
(Low-WORD)
(uncompensated)

0x04

Big-Endian 
WORD

11

Summary of Contents for EOLOS-IND

Page 1: ...egrated overvoltage protection Simple space saving assembly on 50 mm standard pipe The Perfect Weather Sensor For industrial use as well as under extreme environmen tal conditions 5 1 1 parameters in...

Page 2: ...Mounting 2 7 1 North Alignment of Wind Sensor 2 7 2 Power and Signal Connection 2 7 3 Safety Regulations 3 Maintenance 3 1 Regular Maintenance and Calibration 3 2 Visual Check and Cleaning 4 Transport...

Page 3: ...is method Lightweight mass and immovable measuring elements to enable very low starting values distance and attenuation constants as well as a very high repetition accuracy The sensor can be installed...

Page 4: ...t the mast if available If needed you can turn in or unscrew the pin by means of allen key 2 7 1 North Alignment of Wind Sensor For wind direction measurements the north mark on the sen sor must be al...

Page 5: ...signal of the sensor corresponds to the RS 485 standard The signal levels allow transmission via shielded signal cables up to a maximum length of 1 200 meters or 4 000 feet The cable lengths depend o...

Page 6: ...ngsscraube M8 fastening screw Erdscraube M6 earthing screw 10 1 5 6 0 1 P40 min P50 P48 3 5 6 0 1 10 1 min 40 P40 min 50 9 P 0 1 Aufnahmerohr f r den Sensor sensor seat pipe N Schlitz im Mastende baus...

Page 7: ...ensor EOLOS IND Modbus 1643 EOLOS IND Modbus Manual 7 IN 24 V DC f r Elektronik for electronic Schirm shield Erde earth 287 56 0RGEXV 578 1 2 3 4 1 2 3 4 br wt bl bk PIN color 5 5 N A br ws bl sw Farb...

Page 8: ...is transmitted in the order 0x12 0x34 Example big endian 32 bit or 64 bit Register size value 32 bits 0x12345678 is transmitted in the order 0x12 0x34 0x56 0x78 6 2 Device Address The addresses 1 247...

Page 9: ...stantaneous value r h 10 1 decimal place INT 30602 Humidity mean value since last retrieval r h 10 1 decimal place INT 30603 Humidity maximum value r h 10 1 decimal place INT 30604 Humidity minimum va...

Page 10: ...HT meteo o er the possibility of autocon guration This is supported e g by the data logger met LOG For autocon guration the register addresses of the measured values and sensor data available in the r...

Page 11: ...imal places LONG 0x04 Big Endian WORD 31102 Precipitation amount total Low WORD 3 decimal places Registers 31101 31102 can only be read out together function code 0x04 0x04 Big Endian WORD 31201 Preci...

Page 12: ...s 1 Dew point maximum value INT 46020 30703 Register address 1 Dew point minimum value INT 46021 30801 Register address 1 Air pressure instantaneous value INT 46022 30802 Register address 1 Air pressu...

Page 13: ...100 r h Parameters Wind direction Measuring range 0 360 Accuracy 3 RMS Resolution 1 Wind speed Measuring range 0 1 50 m s Accuracy 0 5 m s 5 RMS of the meas value at 5 1 40 m s Resolution 0 1 m s Air...

Reviews: