background image

KYRA D 30 SI UNIT COND

A73022660

38

EN

fi

 g.13 - Curve parallel offset

Press the 

mode

 button (detail 10 - 

fi

 g.1) again to exit parallel curve adjustment 

mode.
If the room temperature is lower than the required value, it is advisable to set a 
higherorder curve and vice versa. Proceed by increasing or decreasing in steps of 
one andcheck the result in the room.

fi

 g.14 - Compensation curves

fi

 g.15 - Example of compensation parallel curve offset

Adjustments from Remote Timer Control

If the Remote Timer Control (optional) is connected to the boiler, the 
above adjustments are managed according to that given in table1. 
Also, the control panel display (detail 5 - 

fi

 g.1) shows the actual room 

temperature detected by the Remote Timer Control.

Table. 1

Heating tempera-
ture setting

Adjustment can be made from the Remote Timer Control 
menu and the boiler control panel.

DHW temperature 
adjustment 

Adjustment can be made from the Remote Timer Control 
menu and the boiler control panel.

Summer/Winter 
Switchover

Summer mode has priority over a possible Remote Timer 
Control heating demand.

Eco/Comfort 
selection

On disabling DHW from the Remote Timer Control menu, 
the boiler selects the Economy mode. In this condition, the 

button 7

 - 

fi

 g.1 on the boiler panel is disabled

On enabling DHW from the Remote Timer Control menu, 
the boiler selects the Comfort mode. In this condition it is 
possible select one of the two modes with the 

button 7

 - 

fi

 g.1 on the boiler panel.

Sliding Tempe-
rature

Both the Remote Timer Control and the boiler card mana-
ge Sliding Temperature adjustment: of the two, the Sliding 
Temperature of the boiler card has priority.

Water system pressure adjustment

The 

fi

 lling pressure with system cold, read on the display, must be approx. 1.0 bar. 

If thesystem pressure falls to values below minimum, the boiler card will activate 
fault F37(

fi

 g.16). 

fi

 g.16 - Low system pressure fault

Once the system pressure is restored, the boiler will activate the 
120-secondair venting cycle indicated on the display by FH.

  3. INSTALLATION OF THE APPLIANCE

 3.1 General Instructions

BOILER INSTALLATION MUST ONLY BE PERFORMED BY QUALIFIED PER-
SONNEL, IN ACCORDANCE WITH ALL THE INSTRUCTIONS GIVEN IN THIS 
TECHNICAL MANUAL, THE PROVISIONS OF CURRENT LAW, THE PRESCRIP-
TIONS OF NATIONAL AND LOCAL STANDARDS AND THE RULES OF PROPER 
WORKMANSHIP.

 3.2 Place of installation

The boiler unit must be installed in a speci

fi

 c room with ventilation openings to the 

out-side as prescribed by current regulations. If there are several burners or suction 
units that can work together in the same room, the ventilation openings must be 
sized for simultaneous operation of all the units. The place of installation must be 
free of 

fl

 ammable materials or objects, corrosive gases, powders or volatile sub-

stances that, conveyed by the burner fan, can obstruct the internal lines of the burn-
er or the combustion head. Theroom must be dry and not exposed to rain, snow 
or frost.

If the unit is enclosed in a cabinet or mounted alongside, a space must 
be provided for removing the casing and for normal maintenance opera-
tions.

 3.3 Plumbing connections

The heating capacity of the unit must be previously established by calculating the 
building’s heat requirement according to the current regulations. The system must 
be provided with all the components for correct and regular operation.
It is advisable to installshutoff valves between the boiler and heating system allow-
ing the boiler to be isolated from the system if necessary.

The safety valve outlet must be connected to a funnel or collection pipe 
to prevent water spurting onto the 

fl

 oor in case of overpressure in the 

heating circuit.Otherwise, if the discharge valve cuts in and 

fl

 oods  the 

room, the boiler manufacturer cannot be held liable.
Do not use the water system pipes to earth electrical appliances.

Before installation, 

fl

 ush all the pipes of the system thoroughly to remove any resid-

uals or impurities that could affect proper operation of the unit.
Carry out the relevant connections according to the diagram in cap. 5 and the sym-
bols given on the unit.

High ef

fi

 ciency circulating pump

Circulating pump adjustment with boiler connected to an external storage tank.

The circulating pump is factory set to “Constant Speed III” mode. This mode 
satis

fi

 es most installations. However, it can be set speci

fi

 cally according to the type 

of system.

Botón multifunción

fi

 g.17

Summary of Contents for KYRA D 30 SI UNIT COND

Page 1: ...1 204 63 61 4712 77 13 04 4742 52 20 81 3519 55 03 13 495 268 04 70 8152 59 64 93 8552 20 53 41 831 429 08 12 3843 20 46 81 383 227 86 73 3812 21 46 40 4862 44 53 42 3532 37 68 04 8412 22 31 16 342 20...

Page 2: ...40 3 5 Electrical connections 40 3 6 Connection to the flue 41 3 7 Condensate drain connection 41 4 SERVICE AND MAINTENANCE 41 4 1 Adjustments 41 4 2 Commissioning 43 4 3 Maintenance 44 4 4 Troublesho...

Page 3: ...mplified representation of the product In this representation there may be slight and insignificant differences with re spect to the product supplied 2 OPERATING INSTRUCTIONS 2 1 Introduction Dear Cus...

Page 4: ...C fig 10 DHW temperature adjustment Use the DHW buttons details 1 and 2 fig 1 to adjust the temperature from a min of 10 C to a max of 65 C fig 11 Room temperature adjustment with optional room therm...

Page 5: ...FORMED BY QUALIFIED PER SONNEL IN ACCORDANCE WITH ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL MANUAL THE PROVISIONS OF CURRENT LAW THE PRESCRIP TIONS OF NATIONAL AND LOCAL STANDARDS AND THE RULES OF...

Page 6: ...ATTENTION After venting the LED indicator shows the pump set values Set the adjustment mode Select the adjustment mode The LED selection of the adjustment mode and the corresponding characteristic cur...

Page 7: ...nd exclusively if their manufacturer provides a guarantee ensuring that the products are suitable for use and do not cause damage to the boiler exchanger or to other components and or materials of the...

Page 8: ...ore starting the unit Verify Periodically check the water in the trap fig 23 Condensate drain 4 SERVICE AND MAINTENANCE All adjustment conversion commissioning and maintenance operations described bel...

Page 9: ...press the Reset button to access it tS Transparent Parameters Menu The card is equipped with 27 transparent parameters also modifiable from Remote Control Service Menu Index Description Range Default...

Page 10: ...ccurred relevant to Ht H5 Fault code Time fault occurred relevant to Ht H6 Fault code Time fault occurred relevant to Ht H7 Fault code Time fault occurred relevant to Ht H8 Fault code Time fault occur...

Page 11: ...The gas and water systems must be airtight The water pressure in the cold water system must be approx 1 bar otherwise bringit to that value The circulating pump must not be blocked The expansion tank...

Page 12: ...p nozzle Clean Pump unprimed Prime and find the cause of unpriming Ignition electrodes not properly adjusted or dirty Adjust or clean them Nozzle clogged dirty or deformed Replace Unsuitable head and...

Page 13: ...temperature F40 Incorrect system water pressure Pressure too high Check the system Check the safety valve Check the expansion vessel A41 Sensor positioning Delivery sensor not inser ted in boiler shel...

Page 14: ...utomatic air vent 38 Flow switch 42 DHW temperature sensor optional 56 Expansion vessel 74 Charging key 191 Smoke temperature sensor 246 Pressure transducer 275 Key download heating circuit 278 Double...

Page 15: ...iency class according to directive 92 42 CE Max working pressure in heating bar 3 PMS Min working pressure in heating bar 0 8 Max heating temperature C 80 tm x Heating water content liters 49 Heating...

Page 16: ...emperature regime 1 97 5 Auxiliary electricity consumption At full load elmax kW 0 188 At part load elmin kW 0 075 In standby mode PSB kW 0 003 Other items Standby heat loss Pstby kW 0 100 Ignition bu...

Page 17: ...3 204 51 73 343 384 55 89 4932 77 34 06 3412 26 03 58 395 279 98 46 843 206 01 48 4012 72 03 81 4842 92 23 67 3842 65 04 62 8332 68 02 04 861 203 40 90 391 204 63 61 4712 77 13 04 4742 52 20 81 3519 5...

Reviews: