KYRA D 30 SI UNIT COND
A73022660
38
EN
fi
g.13 - Curve parallel offset
Press the
mode
button (detail 10 -
fi
g.1) again to exit parallel curve adjustment
mode.
If the room temperature is lower than the required value, it is advisable to set a
higherorder curve and vice versa. Proceed by increasing or decreasing in steps of
one andcheck the result in the room.
fi
g.14 - Compensation curves
fi
g.15 - Example of compensation parallel curve offset
Adjustments from Remote Timer Control
If the Remote Timer Control (optional) is connected to the boiler, the
above adjustments are managed according to that given in table1.
Also, the control panel display (detail 5 -
fi
g.1) shows the actual room
temperature detected by the Remote Timer Control.
Table. 1
Heating tempera-
ture setting
Adjustment can be made from the Remote Timer Control
menu and the boiler control panel.
DHW temperature
adjustment
Adjustment can be made from the Remote Timer Control
menu and the boiler control panel.
Summer/Winter
Switchover
Summer mode has priority over a possible Remote Timer
Control heating demand.
Eco/Comfort
selection
On disabling DHW from the Remote Timer Control menu,
the boiler selects the Economy mode. In this condition, the
button 7
-
fi
g.1 on the boiler panel is disabled
On enabling DHW from the Remote Timer Control menu,
the boiler selects the Comfort mode. In this condition it is
possible select one of the two modes with the
button 7
-
fi
g.1 on the boiler panel.
Sliding Tempe-
rature
Both the Remote Timer Control and the boiler card mana-
ge Sliding Temperature adjustment: of the two, the Sliding
Temperature of the boiler card has priority.
Water system pressure adjustment
The
fi
lling pressure with system cold, read on the display, must be approx. 1.0 bar.
If thesystem pressure falls to values below minimum, the boiler card will activate
fault F37(
fi
g.16).
fi
g.16 - Low system pressure fault
Once the system pressure is restored, the boiler will activate the
120-secondair venting cycle indicated on the display by FH.
3. INSTALLATION OF THE APPLIANCE
3.1 General Instructions
BOILER INSTALLATION MUST ONLY BE PERFORMED BY QUALIFIED PER-
SONNEL, IN ACCORDANCE WITH ALL THE INSTRUCTIONS GIVEN IN THIS
TECHNICAL MANUAL, THE PROVISIONS OF CURRENT LAW, THE PRESCRIP-
TIONS OF NATIONAL AND LOCAL STANDARDS AND THE RULES OF PROPER
WORKMANSHIP.
3.2 Place of installation
The boiler unit must be installed in a speci
fi
c room with ventilation openings to the
out-side as prescribed by current regulations. If there are several burners or suction
units that can work together in the same room, the ventilation openings must be
sized for simultaneous operation of all the units. The place of installation must be
free of
fl
ammable materials or objects, corrosive gases, powders or volatile sub-
stances that, conveyed by the burner fan, can obstruct the internal lines of the burn-
er or the combustion head. Theroom must be dry and not exposed to rain, snow
or frost.
If the unit is enclosed in a cabinet or mounted alongside, a space must
be provided for removing the casing and for normal maintenance opera-
tions.
3.3 Plumbing connections
The heating capacity of the unit must be previously established by calculating the
building’s heat requirement according to the current regulations. The system must
be provided with all the components for correct and regular operation.
It is advisable to installshutoff valves between the boiler and heating system allow-
ing the boiler to be isolated from the system if necessary.
The safety valve outlet must be connected to a funnel or collection pipe
to prevent water spurting onto the
fl
oor in case of overpressure in the
heating circuit.Otherwise, if the discharge valve cuts in and
fl
oods the
room, the boiler manufacturer cannot be held liable.
Do not use the water system pipes to earth electrical appliances.
Before installation,
fl
ush all the pipes of the system thoroughly to remove any resid-
uals or impurities that could affect proper operation of the unit.
Carry out the relevant connections according to the diagram in cap. 5 and the sym-
bols given on the unit.
High ef
fi
ciency circulating pump
Circulating pump adjustment with boiler connected to an external storage tank.
The circulating pump is factory set to “Constant Speed III” mode. This mode
satis
fi
es most installations. However, it can be set speci
fi
cally according to the type
of system.
Botón multifunción
fi
g.17