background image

KYRA D 30 SI UNIT COND

37

A73022660

EN

 2.3 Lighting and turning off

Boiler not electrically powered

fi

 g.5 - Boiler not electrically powered

The antifreeze system does not work when the power and/or gas to the 
unit areturned off. To avoid damage caused by freezing during long idle 
periods in winter, it is advisable to drain all water from the boiler, DHW 
circuit and system; ordrain just the DHW circuit and add a suitable anti-
freeze to the heating system,complying with that prescribed in sec.3.3.

Boiler lighting

•  Open the fuel on-off valves.
•  Switch on the power to the unit.

fi

 g.6 - Boiler lighting

•  For the following 120 seconds the display will show FH which identi

fi

 es the heat-

ingsystem air venting cycle.

During 

the 

fi

 rst 5 seconds the display will also show the card software version.

•  When the message FH disappears, the boiler is ready to operate automatically-

whenever domestic hot water is drawn or in case of a room thermostat demand.

Turning the boiler off

Press the on/off button (detail 9 - 

fi

 g.1) for 1 second.

fi

 g.7 - Turning the boiler off

When the boiler is turned off, the PCB is still powered.
Domestic hot water and heating are disabled. 
The antifreeze system remains activated.To relight the boiler, press the on/off button 
(detail 9 - 

fi

 g.1) again for 1 second.

fi

 g.8

The boiler will be immediately ready to operate whenever domestic hot water is 
drawnor in case of a room thermostat demand.

 2.4 Adjustments

Summer/Winter Switchover

Press the 

summer/winter

 button (detail 6 - 

fi

 g.1) for 1 second.

fi

 g.9

The display activates the Summer symbol (detail 27 - 

fi

 g.1): the boiler will only deliv-

erdomestic hot water. The antifreeze system remains activated.
To deactivate the Summer mode, press the summer/winter button (part. 6 - 

fi

 g.1) 

againfor 1 second.

Heating temperature setting

Use the 

heating buttons

 (details 3 and 4 - 

fi

 g.1) to adjust the temperature from a 

min.of 30°C to a max. of 80°C.

In any case it is advisable not to operate the boiler below 45°C. 

fi

 g.10

DHW temperature adjustment

Use the DHW buttons -/+ (details 1 and 2 - 

fi

 g.1) to adjust the temperature from a 

min.of 10°C to a max. of 65°C.

fi

 g.11 

Room temperature adjustment (with optional room thermostat)

Using the room thermostat, set the temperature desired in the rooms. If the room 
thermostat is not installed the boiler will keep the heating system at its setpoint 
temperature.

Room temperature adjustment (with optional remote timer control)

Using the remote timer control, set the temperature desired in the rooms. The boiler 
unitwill set the system water according to the required room temperature. For infor-
mation onthe remote timer control, please refer to its user’s manual.

Sliding temperature

When the optional external probe is installed the control panel display (detail 5 - 

fi

 g.1)shows the actual outside temperature read by the probe. The boiler control 

system operates with “Sliding Temperature”. In this mode,  the temperature of the 
heating systemis adjusted according the outside weather conditions, in order to en-
sure high comfort andenergy saving throughout the year. In particular, as the outside 
temperature increases,the system delivery temperature is decreased according to a 
speci

fi

 c “compensationcurve”.

With Sliding Temperature adjustment, the temperature set with the heating buttons 
-/+(details 3 and 4 - 

fi

 g.1) becomes the maximum system delivery temperature. It is 

advisable to set a maximum value to allow system adjustment throughout its useful 
operatingrange.
The boiler must be adjusted at the time of installation by quali

fi

 ed personnel. Pos-

sibleadjustments can in any case be made by the user to improve comfort.

Compensation curve and curve offset

Press the mode button (detail 10 - 

fi

 g.1) once to display the actual compensation 

curve(

fi

 g.11), which can be modi

fi

 ed with the DHW buttons (details 1 and 2 - 

fi

 g.1).

Adjust the required curve from 1 to 10 according to the characteristic (

fi

 g.13).

By setting the curve to 0, sliding temperature adjustment is disabled.

fi

 g.12 - Compensation curve

Press the 

heating buttons

 (details 3 and 4 - 

fi

 g.1) to access parallel curve offset(-

fi

 g.14), modi

fi

 able with the 

DHW buttons

 (details 1 and 2 - 

fi

 g.1).

Summary of Contents for KYRA D 30 SI UNIT COND

Page 1: ...1 204 63 61 4712 77 13 04 4742 52 20 81 3519 55 03 13 495 268 04 70 8152 59 64 93 8552 20 53 41 831 429 08 12 3843 20 46 81 383 227 86 73 3812 21 46 40 4862 44 53 42 3532 37 68 04 8412 22 31 16 342 20...

Page 2: ...40 3 5 Electrical connections 40 3 6 Connection to the flue 41 3 7 Condensate drain connection 41 4 SERVICE AND MAINTENANCE 41 4 1 Adjustments 41 4 2 Commissioning 43 4 3 Maintenance 44 4 4 Troublesho...

Page 3: ...mplified representation of the product In this representation there may be slight and insignificant differences with re spect to the product supplied 2 OPERATING INSTRUCTIONS 2 1 Introduction Dear Cus...

Page 4: ...C fig 10 DHW temperature adjustment Use the DHW buttons details 1 and 2 fig 1 to adjust the temperature from a min of 10 C to a max of 65 C fig 11 Room temperature adjustment with optional room therm...

Page 5: ...FORMED BY QUALIFIED PER SONNEL IN ACCORDANCE WITH ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL MANUAL THE PROVISIONS OF CURRENT LAW THE PRESCRIP TIONS OF NATIONAL AND LOCAL STANDARDS AND THE RULES OF...

Page 6: ...ATTENTION After venting the LED indicator shows the pump set values Set the adjustment mode Select the adjustment mode The LED selection of the adjustment mode and the corresponding characteristic cur...

Page 7: ...nd exclusively if their manufacturer provides a guarantee ensuring that the products are suitable for use and do not cause damage to the boiler exchanger or to other components and or materials of the...

Page 8: ...ore starting the unit Verify Periodically check the water in the trap fig 23 Condensate drain 4 SERVICE AND MAINTENANCE All adjustment conversion commissioning and maintenance operations described bel...

Page 9: ...press the Reset button to access it tS Transparent Parameters Menu The card is equipped with 27 transparent parameters also modifiable from Remote Control Service Menu Index Description Range Default...

Page 10: ...ccurred relevant to Ht H5 Fault code Time fault occurred relevant to Ht H6 Fault code Time fault occurred relevant to Ht H7 Fault code Time fault occurred relevant to Ht H8 Fault code Time fault occur...

Page 11: ...The gas and water systems must be airtight The water pressure in the cold water system must be approx 1 bar otherwise bringit to that value The circulating pump must not be blocked The expansion tank...

Page 12: ...p nozzle Clean Pump unprimed Prime and find the cause of unpriming Ignition electrodes not properly adjusted or dirty Adjust or clean them Nozzle clogged dirty or deformed Replace Unsuitable head and...

Page 13: ...temperature F40 Incorrect system water pressure Pressure too high Check the system Check the safety valve Check the expansion vessel A41 Sensor positioning Delivery sensor not inser ted in boiler shel...

Page 14: ...utomatic air vent 38 Flow switch 42 DHW temperature sensor optional 56 Expansion vessel 74 Charging key 191 Smoke temperature sensor 246 Pressure transducer 275 Key download heating circuit 278 Double...

Page 15: ...iency class according to directive 92 42 CE Max working pressure in heating bar 3 PMS Min working pressure in heating bar 0 8 Max heating temperature C 80 tm x Heating water content liters 49 Heating...

Page 16: ...emperature regime 1 97 5 Auxiliary electricity consumption At full load elmax kW 0 188 At part load elmin kW 0 075 In standby mode PSB kW 0 003 Other items Standby heat loss Pstby kW 0 100 Ignition bu...

Page 17: ...3 204 51 73 343 384 55 89 4932 77 34 06 3412 26 03 58 395 279 98 46 843 206 01 48 4012 72 03 81 4842 92 23 67 3842 65 04 62 8332 68 02 04 861 203 40 90 391 204 63 61 4712 77 13 04 4742 52 20 81 3519 5...

Reviews: