Adjust the minimum pressure with the screw "E", clockwise to decrease it and anti-
clockwise to increase it.
•
Reconnect the faston detached from the modureg on the gas valve.
•
Check that the maximum pressure has not changed.
•
Refit the protection cap "D".
•
To terminate the TEST mode, repeat the activation sequence or wait 15 minutes.
A
After checking or adjusting the pressure, make sure to seal the adjust-
ment screw with paint or a specific seal.
fig. 20 - Gas valve
A =
Upstream pressure point -
B =
Downstream pressure point
C =
Modureg electrical connection -
D =
Protection cap
E =
Min. pressure adjustment -
F =
Modureg
G =
Max. pressure adjustment -
I =
Electrical connection Gas valve
M =
Pressure gauge -
R =
Gas outlet
S =
Gas inlet
Heating power adjustment
To adjust the heating power, switch the boiler to TEST mode (see sec. 4.1). Press the
heating buttons fig. 1 (details 3 and 4 - ) to increase or decrease the power (min. = 00 -
max. = 100). Press the RESET button within 5 seconds and the max. power will remain
that just set. Exit TEST mode (see sec. 4.1).
Lighting power adjustment
To adjust the lighting power, switch the boiler to TEST mode (see sec. 4.1). Press the
DHW buttons (details 1 and 2 - fig. 1) to increase or decrease the power (min. = 00 - max.
= 60). Press the RESET button within 5 seconds and the lighting power will remain that
just set. Exit TEST mode (see sec. 4.1).
User interface
The user interface is developed on display cards
DSP05
,
DSP06
or
DSP08
, which com-
municate with card
INTERF_U
via a flat cable.
If replacing the card
INTERF_U
, in order to manage the display card
DSP08
, a parame-
ter must be changed.
This occurs by pressing the and Summer/Winter buttons together for 5 seconds.
Service menu
The card is equipped with two Menus: one for configuration and the other defined Service.
The configuration Menu is accessed by pressing the DHW buttons together for 10 sec-
onds. 2 parameters, modifiable only from card, are available.
To exit the configuration Menu, press the DHW buttons together for 10 seconds.
The card Service Menu is accessed by pressing the Reset button for 10 seconds. Press
the Heating buttons to select "tS", "In", "Hi" or "rE". "tS" means Transparent Parameters
Menu, "In" Information Menu, "Hi" History Menu, and "rE" History Menu Reset. After se-
lecting the Menu, press the Reset button to access it.
"tS" - Transparent Parameters Menu
The card is equipped with 24 transparent parameters also modifiable from Remote Con-
trol (Service Menu):
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to modify the value of a parameter: the change will be au-
tomatically saved.
The Max. Heating Power and Lighting Power parameters can be modified in Test Mode
(see relevant section).
Press the Reset button to return to the Service Menu. Press the Reset button for 10 sec-
onds to exit to the card Service Menu.
"In" -Information menu
The card can display the following information:
Press the Heating buttons to scroll the list of information. In case of damaged sensor, the
card displays hyphens.
Press the Reset button to return to the Service Menu. Press the Reset button for 10 sec-
onds to exit to the card Service Menu.
Remote
control
Card
Description
Transparent Parameters
Range
Default
NO
P01
Exchanger type selection
0=Copper,
1=Cast iron
0=Copper
NO
P02
Boiler shell Warm-up activation temperature (P02=1)
0-80°C
0°C
Boiler shell Warm-up activation temperature (P02=2)
0-80°C
0°C
Boiler shell Warm-up activation temperature (P02=3)
0-80°C
0°C
+
M
D
E
G
C
F
F
I
B
A
R
S
Remote
control
Card
Description
Transparent Parameters
Range
Default
01
P01
Gas type selection
0=Natural
Gas,1=LPG
0=Natural
Gas
02
P02
Boiler type selection
1=Heating only
2=Storage with probe
3= Storage with ther-
mostat
1=heating
only
03
P03
Absolute min. power
0-100%
0%
04
P04
Lighting power
0-60%
50%
05
P05
System water pressure protection
0=Pressure switch,
1=Pressure Trans-
ducer
1=Pressure
transducer
06
P06
Heating train
1-20°C/min
5 °C/min
07
P07
Heating pump post-circulation
0-20 minutes
6 minutes
08
P08
Heating standby time
0-10 minutes
2 minutes
09
P09
Max. heating power
0-100%
100%
10
P10
pump operation
0=Post-Circulation
1=Continuous
0=Post-Circu-
lation
11
P11
Pump deactivation temperature during Post-Circulation
(P02=1)
0-100°C
20°C
Pump deactivation temperature during Post-Circulation
(P02=2)
0-100°C
20°C
Pump deactivation temperature during Post-Circulation
(P02=3)
0-100°C
20°C
12
P12
Heating user max. set point
31-85°C
85°C
13
P13
DHW pump post-circulation
0-255 seconds
30 seconds
14
P14
DHW standby time
0-255 seconds
120 seconds
15
P15
DHW max. power
0-100%
100%
16
P16
No function (P02=1)
--
--
DHW user max. set point (P02=2)
55-65°C
65°C
No function (P02=3)
--
--
17
P17
No function (P02=1)
--
--
Hot water tank activation hysteresis temperature (P02=2) 0-20°C
2°C
No function (P02=3)
--
--
18
P18
No function (P02=1)
--
--
Hot water tank preparation delivery temperature (P02=2) 70-85°C
80°C
Hot water tank preparation delivery temperature (P02=3) 70-85°C
80°C
19
P19
Not implemented
--
--
20
P20
System minimum pressure value
0-8 bar/10
4 bar/10
21
P21
System nominal pressure value
5-20 bar/10
8 bar/10
22
P22
No function (P02=1)
--
--
Legionella protection (P02=2)
0-7
0
No function (P02=3)
--
--
23
P23
Not implemented
--
--
24
P24
Mains Voltage Frequency
0=50Hz,1=60Hz
0=50Hz
t01
NTC Heating sensor (°C)
between 05 and 125°C
t02
NTC DHW sensor (°C)
(Only with Parameter P02=2, boiler with storage)
between 05 and 125°C
t03
NTC Safety sensor (°C)
between 05 and 125°C
t04
NTC External sensor (°C)
between -30 and 70°C
(Negative values flash)
L05 Actual burner power (%)
00%=Min., 100%=Max.
P06 Actual system water pressure (bar/10)
00=With Pressure Switch open,
14=With Pressure Switch closed,
00-99 bar/10 with Pressure Transducer
F07 Actual ionisation current (uA)
00-99 uA (00=burner off)