ELECTRIC CONNECTIONS
READ THE G EN ER A L STANDARDS ON PAGE 3 CA REFULLY
- NEUTRAL TO EARTH: in the case of power supply mains with NEUTRAL CONNECTED TO EARTH connect
the mains power supply NEUTRAL to the appliance NEUTRAL.
- INSULATED NEUTRAL: in the case of mains power supply with INSULATED NEUTRAL it is necessary to use
an insulation transformer. Connect a terminal of the insulation transformer secondary to the appliance EARTH and
NEUTRAL.Now connect the other terminal of the transformer secondary to the appliance LINE.
- PHASE-PHASE: in the case of PHASE-PHASE mains power supply, it is necessary to use an insulation tran
sformer. Connect a terminal of the insulation transformer secondary to the appliance EARTH and NEUTRAL.Now
connect the other terminal of the transformer secondary to the appliance LINE.
EA
KEY
L Line
N Neutral
L1 Three phase line
L2 Three phase line
L3 Three phase line
M Burner motor
R Motor contactor
TR Ignition transformer
MS Servo-motor
PG Gas pressure switch
PA Air pressure switch
CE Control unit
CT Sealing control
P S Release button
LB Lock out lamp
TC Boiler thermostat
Tmf Modulating thermostat flame
€
i
О
2
©
3
0
о
MS
©
e
0
7
0
8
©
9
Tmf
TC
I I I I I
I I I I I
L
M
1
й
GB
70
M