53
EN
Cod. 3541Z090 - Rev. 05 - 05/2022
IDOLA S 3.2
Menu
Level 1
Menu
Level 2
Menu
Level 3
Menu
Level 4
Description
Lower
limit
Upper
limit
Remedy
Unit of
measure-
ment
Default
value
For Serviceman 14 Power Input
Limitation
14.1 POWER LIMITATION
To limit the power absorbed by the heat pump
(refer to “Table. 6 - Max current input (A) for
different level of power input limitation" on page
53.
0
8
1
/
0
For Serviceman 15 Input Define
15.1 On/Off(M1M2)
Reserved
Yes
No
/
/
No
15.2 Smart Grid
Enables or disables SMART GRID
Yes
No
/
/
No
15.3 T1B(Tw2)
Enables or disables temperature probe T1B
(Tw2)
Yes
No
/
/
No
15.4 Tbt1
Enables or disables temperature probe Tbt1
Yes
No
/
/
No
15.5 Tbt2
Reserved
-
-
/
/
No
15.7 Solar Input
SOLAR ENABLE
Enables solar input
Yes
No
/
/
No
IN SOLAR
Type of solar input;
Tsolar (to enable the Tsolar solar panel probe
temperature);
SL1SL2 = do not use
Tsolar SL1SL2
/
/
SL1SL2
15.8 F-Pipe Length
Reserved
Yes
No
/
/
No
15.10 Rt/Ta_Pcb
Reserved
Yes
No
/
/
No
For Serviceman 17 FW Update
USB
17.1 Program fw
/
/
/
/
/
/
/
17.2 Verify Download --%
/
BMS address setting of the heat pump
1
16
1
/
0
NOTE
* It allows you to enable or disable the functions that can be restarted in the event of a power failure.
Table. 6 - Max current input (A) for different level of power input limitation
Limitation level of input power
0
1
2
3
4
5
6
7
8
4-6
18
18
16
15
14
13
12
12
12
8-10
19
19
18
16
14
12
12
12
12
12-14
30
30
28
26
24
22
20
18
16
16
30
30
29
27
25
23
21
19
17
12T-14T-16T
14
14
13
12
11
10
9
9
9