LAMBERTI ELEKTRONIK DFW HZR Operating And Commissioning Manual Download Page 9

 

 

P

a

g

e

 9

 

 

 

Setpoint 
value 

Meaning 

On the 
display 

Adjustable values 

Factory 
setting 

Your 
setting 

 

Setpoint 
value hot 
water 

Desired hot water temperature  
 
 
 

 

   The maximum value is adjustable by 

the heating specialist: max (factory setting) 
= 60 °C 

 WW 

Min: 10 °C  
Max: 60 °C 
 

55 °C 

 

 

Lowered 
setpoint 
value hot 
water 

Desired reduced hot water temperature 
between the primary running times 
 

 

 Only adjustable, when this function is 

enabled by the heating specialist! 

 WW 

 

Min: 10 °C  

Max: adjusted set-
point value hot water 

40 °C 

 

 

Steepness 
1. heating 
circuit 

Only with weather-controlled regulation: 
the heating can be adjusted to your build-
ing with the steepness value. It is adjust-
able instead of the P-value. 

 ST 

or 

 

No 1 

Min: 0,3 Max: 3,0 
 

 

 

1,2 
 

 

 

 

 

Steepness 
2. heating 
circuit 

As steepness 1. heating circuit 
 

 

 Only adjustable in:  

configuration 5 or 6. 

 No 2  Min: 0,3 Max: 3,0 

1,2 

 

 

P- value 
1. heating 
circuit 

Proportional range: Only adjustable with 
room proportional regulation instead of the 
steepness value. 

 PR 

or 

No.1 

Min: 1,0 Max: 6,0 
 

2,0 

 

 

P-value 
2. heating 
circuit 

As proportional range 1. heating circuit. 
 

 

 Only adjustable in: 

configuration 5 or 6 and allocation of T

INNEN

 

for heating circuit 2 (E3-3/6). 

 No 2  Min: 1,0 Max: 6,0 

 

2,0 

 

 

13.

 

Submenu operating modes 

 

 

Change to the submenu operating modes by pressing the key            . Press the keys             and            , until 
the flashing cursor is located below the desired operating mode. Acknowledge your choice with the key           . 

 

 

Attention! 

The operating modes public holiday        and vacation       (marked grey in the chart on the following 
page) are only available in the two automatic operating modes. 

!

 

 

OK 

 

-- 

Submenu setpoint values 

OK 

Summary of Contents for DFW HZR

Page 1: ...Page 1 OPERATING AND COMMISSIONING MANUAL...

Page 2: ...cal connection of the remote control at the heating controller 5 9 Disassembly and disposal 6 10 Your digital remote control is structured like this 6 11 Functions and adjustments 7 11 1 Basic informa...

Page 3: ...t wall construction housing 1 2 Technical data Connection eBus max 24 V 50 mA DC 2wire connection pole independent Sensors NTC temperature sensors 8 2 k at 25 C Protection degree IP 20 according to DI...

Page 4: ...d liability All regulations about warranty and liability are defined in the general terms and conditions of the manufacturer or in the particular contractual relationship Warranty and liability claims...

Page 5: ...ply of the heating controller every time before the clamp cover is opened Make sure that the controller cannot be switched on DNAGER Connect the remote control to the heating controller Use a 2 wire w...

Page 6: ...lectronic equipment act or ElektroG 10 Your digital remote control is structured like this Your remote control has a clearly arranged display which indicates information e g about actual tempera tures...

Page 7: ...e always priority to the adjustments at the heating controller Please also consider the operating and the commissioning manual of the heating controller for all works and adjustments at your digital r...

Page 8: ...re During the data transfer adjustments via the keys are blocked That means you have to wait until the data transfer has been completed if you want to change values 11 5 Leave a submenu With the key y...

Page 9: ...0 3 Max 3 0 1 2 Steepness 2 heating circuit As steepness 1 heating circuit Only adjustable in configuration 5 or 6 No 2 Min 0 3 Max 3 0 1 2 P value 1 heating circuit Proportional range Only adjustable...

Page 10: ...ating mode day OFF or day night When adjusting this operating mode you are asked to enter a start date and an end date OFF Heating and hot water support are off Only hot water The hot water support ru...

Page 11: ...n the controller The cursor below the symbol of the adjusted operating mode flashes Manual change to tem perature regulation econ omy level In this mode you leave the automatic temperature regulation...

Page 12: ...ystem and its configuration which sensors are mounted at your heating system For this reason it is possible that your controller does not display all values that are shown in the following chart Comin...

Page 13: ...ction Factory setting Range Your setting 1 Controller address 1 1 8 2 Controller type only display 3 HZR C 2 HZR E 3 Controller configuration only display 1 8 E3 2 Correction value No Action Factory s...

Page 14: ...nformation on the display check if the device is connected correctly 3 Check if there is an error that is described in the commissioning manual of the heating controller Replace the digital remote con...

Page 15: ...Page 15 Notes...

Page 16: ...ng manual is not allowed to be duplicated distributed altered transferred and translated into another language or to be used otherwise The information in this oper ating and commissioning manual has b...

Reviews: