Floor Mounting
To floor-mount the ESCR 125, install four anchor bolts into the floor. Place the charger on the anchor bolts, add
appropriate mounting hardware onto the floor-mounting anchor bolts, and tighten securely. Refer to Figure 3
for hardware specifications and floor-mounting dimensions. All dimensions are given in inches.
Figure 3
–
Floor Mounting Dimensions
1.1.3 Rack Mounting (4 Enclosure Only)
The ESCR125 can be installed in most relay racks with standard EIA hole spacing. If a relay rack is needed, they
are available for purchase from La Marche. The 4 enclosures are shipped from the factory with the necessary
brackets installed for rear mounting on a 19” relay rack (The same bracket is used for wall mounting and cannot
be removed). If center mounting is desired, a rack-mounting kit is available for the 4 enclosure. Before installing
the charger on the rack, locate the placement of the conduit entrances and assure the knockouts on the sides
or bottom of the charger are accessible after the charger is rack-mounted. The table and figure below shows
rack-mounting options for ESCR125.
Rack Mounting Procedure
To rack mount the ESCR125, first mount the charger onto the
rack-mounting brackets using the hardware supplied. Second,
install the brackets onto the rack. Provide at minimum 6in
(152mm) of air space above and below to allow for cooling.
Figure 4 –
Rack-Mounting
Configurations
Table 2 –
Available Rack Mount Configurations