9
2.2
Front Panel Display
After the ESCR125 has completed start up, the “AC ON” indicator on the front panel and either the “Float” or
“Equalize” indicator on the front panel will be lit. The LCD will display the system DC output voltage and DC
output current on line one. Line two of the LCD displays the status of ESCR125.
Figure 9 –
Front Panel Display
2.2.1 Controls
Up/Down Arrows
– The Up and Down arrows offer no function outside of Configuration Mode. When in
Configuration Mode, the up and down arrows allow the user to navigate menus and increase or decrease
values.
Float/Equalize Button
– The Float/Equalize button allows the user to manually switch between Float Mode
and Equalize Mode. When the ESCR125 is in Equalize Mode, line two of the display will alternate between
“EQUALIZE MODE” and the time remaining.
Lamp Test Button
– The Lamp Test button allows the user to check the function of all of the front panel LEDs
without affecting the operation of the charger. While the lamp test is running, all of the LEDs flash and a
sequence of numbers is written to the display.
Reset/Back Button
– The back button allows the user to navigate to a previous screen or out of the
configuration.
Holding the back button will reset the charger. Upon restarting, the ESCR125 will once again go
through the start-up sequence describe in section 2.1.3.
Configure/OK Button
– The Configure/OK button brings the ESCR125 into Configuration Mode. This allows
the user to set charger parameters in Basic Settings as well as Float Voltage, Equalize Voltage, Equalize Timer,
Current Limit, Temperature Compensation and Alarm settings. Once in Configuration Mode, this button becomes
the OK button which is used to make selections with in the menus.