12
Temperature Compensation
– Allows enable or disable of the Temperature Compensation feature.
1.
Select TEMP. COMP. from Configuration Menu
o
Select DISABLE or ENABLE
NOTE:
For internal compensation, enable the setting and place JP4 jumper across pins 1 and 2. For external
compensation, disable the setting and place jumper across 2 and 3 (refer to Figure 10 and 11).
Alarm Settings
– Allows setting the alarm thresholds for the provided alarms and the alarm time delay
1.
Select ALARM SETTING from the Configuration Menu.
o
ALARM DELAY
Select the alarm delay in seconds. Delay can be set from 1 second to 30 seconds
o
DC LOW VOLTAGE
Select the desired low voltage alarm point in V/C (volts per cell)
o
DC HIGH VOLTAGE
Select the desired high voltage alarm point in V/C (volts per cell)
o
AC FAIL VOLTAGE
Select AC Mains High
Alarm will activate when the AC voltage is the percentage selected above the
nominal voltage.
Select AC Mains Low
Alarm will activate when the AC voltage is the percentage selected below the
nominal voltage.
Default Settings
– Allows the user to reset all settings to how they were programmed from the factory. To
reset the ESCR125 settings to the original default settings, scroll to DEFAULT SETTING in the configuration
menu. Select DEFAULT SETTING. Press the Configure/OK button to confirm.
Figure 10 –
Internal Temperature
Compensation Setup
Figure 11 –
External Temperature
Compensation Setup
JP4
JP4