The Power-Tronics ABF10 Automatic 
Battery Flash Module is a convenient and 
compact optional automated flashing 
module for all Power-Tronics voltage 
regulating products and is compatible with 
many other manufacturers’ voltage 
regulators.  The ABF10 offers an easy 
method to add a fully automatic 
aftermarket battery flash unit to any 
generator. 
 
The ABF10 is designed specifically for 
automated battery flashing of a generator’s 
control field.  A reduced wire count and 
generic installation make the ABF10 
suitable for use on a wide range of 
applications.  Automating the battery field 
flash improves reliability and greatly 
improves safety for the operator. 
 
Like the rest of our products, the ABF10 
Automatic Battery Flash Module is 
designed and manufactured with heavy 
duty components to withstand the harshest 
environmental conditions and provide 
extreme reliability.  Onboard fusing and an 
encapsulated design mean the ABF10 will 
stand up to extreme operating conditions. 
 
Indicator lights help the operator know the 
status of the flashing module and a voltage 
operated design helps guarantee reliable 
voltage buildup and a safe flashing 
process. 
 

Specifications 

 

Sensing Voltage:

 

 

 

100-240vac 

Frequency:

 

 

 

 

50-400Hz 

Buildup Pullout Voltage:

   

 

10-15vac 

Battery Voltage:

  

 

 

12-28VDC 

Maximum Continuous Output:

 

 

5adc 

Minimum Field Resistance:

 

 

1Ω  

Battery Source:

   

 

 

Customer-Supplied Battery 

Fusing:

   

 

 

 

Internal, GDB 5A @ 250V 

Current Limiting Resistor:

 

 

20Ω @ 50W (Internal) 

Physical Size:

   

 

 

4.1 x 3.1 x 1.675 in. 

Weight: 

 

 

 

 

7oz. 

 

ABF10 

Automatic Battery Flash Module 

 

Summary of Contents for ABF10

Page 1: ...perator Like the rest of our products the ABF10 Automatic Battery Flash Module is designed and manufactured with heavy duty components to withstand the harshest environmental conditions and provide extreme reliability Onboard fusing and an encapsulated design mean the ABF10 will stand up to extreme operating conditions Indicator lights help the operator know the status of the flashing module and a...

Page 2: ...Table of Contents Introduction and Functional Description 3 Common 12 Lead Generator Wiring Diagrams 4 Hookup Diagram 5 Sequence of Operation 6 Initial Setup and Commissioning 6 Application Troubleshooting 7 Bench Check Procedures 8 Installation Warranty Form 9 Product Warranty Certificate 10 ...

Page 3: ... ABF10 Automatic Battery Flash Module is a proven design based on industry standard flashing procedures and safety policies The ABF10 provides a very compact automatic flashing or battery flashing source to any voltage regulation system quickly easily and safely When the generator is first energized the voltage regulator typically begins its buildup mode where it brings the generator up to a given...

Page 4: ...39V Parallel Wye 208 240V 3ø Voltage L L 208 240V Voltage L N 120 139V NOTE 208V is Standard Voltage Series Delta 240V 3ø Voltage L L 240V Voltage L1 L2 N 120V Voltage L3 N 208V NOTE L3 N is a High Leg 208V instead of 120V Double Delta 120 240V 1ø Voltage L L 240V Voltage L N 120V Preferred Single Phase Connection Don t Use Zig Zag if Possible NOTE Derate generator by 1 3 rated capacity when using...

Page 5: ...ash Unit is 240VAC DO NOT input 277VAC into the ABF10 Severe damage to the unit will result For use on 480V systems either connect the unit to the winding center taps T7 and T8 or use a 480 240V step down transformer Note 1 Customer supplied battery and charging system An isolated battery is strongly recommended Note 2 Flash Enable switch Should be open whenever the exciter is not operating Rate a...

Page 6: ...nd the Operating light will illuminate at this time The voltage regulator should operate and raise terminal voltage to the regulator s setpoint Initial Setup and Commissioning 1 Connect the ABF10 to the exciter field as shown in the instructions on Page 5 or to a slave relay as shown on Page 6 2 Verify wiring connections and start the generator 3 Close the Flash Enable switch and observe that the ...

Page 7: ...ve generator 4 Flash Enable switch is open 5 Open diode in exciter or shorted rotor in generator 6 Loose component in voltage regulator 7 Loose wiring connections 8 Input voltage to regulator is too low 9 Exciter field is grounded 10 Non linear load or wrong selection for regulator hookup 11 Exciter fields are reversed 12 Wrong selection of regulator wiring configuration 13 Defective voltage regul...

Page 8: ... F on the ABF10 and the Flashing lamp should be illuminated 4 Apply 120VAC to terminals AC1 and AC2 on the ABF10 You should hear a click and read 0VDC on F and F on the ABF10 The Operating lamp should be illuminated at this time and the Flashing lamp should be dark 5 Remove the 120VAC from terminals AC1 and AC2 on the ABF10 After approximately 1 second You should hear a click and read battery volt...

Page 9: ... History Please be detailed Ship To Address City State Zip Country Company Name Contact Person Telephone Number Email Address Primary Load Please Explain Repair Warranty Request Information Generator Leads Check One 12 10 6 4 3ø 4 1ø 3 Generator Wiring Mode Check One High Wye Low Wye Series Delta Zig Zag Double Delta Single Phase Other Terminal Voltage Residual AC Voltage Rated KW Rated KVA Genera...

Page 10: ... the purchase date and serial number of the defective part A repair request form must be sent in with the product before repairs will begin You can obtain this form by contacting Power Tronics Inc Send repairs to Power Tronics Inc 2802 Cobbler Ln Kerrville Texas USA 78028 Send in repairs only by UPS or FedEx USPS will NOT deliver to our facility Any one of the following conditions will void the wa...

Reviews: