INSTRUCTION / TROUBLESHOOTING MANUAL FOR MODEL A75MD
PAGE 8 OF 22
The La Marche Model A75MD charger is designed to operate on a specific type of battery with a specified
number of cells. The nameplate on the charger indicates the type and number of cells required. When
connecting the DC output cables to the battery, be certain the positive terminal of the charger is connected to
the positive battery terminal, and the negative terminal is connected to the negative terminal of the battery. A
grounding connection is also provided for complete protection. Install the unit so that the flow of air through
the vents is not obstructed.
A terminal block is provided within the unit for the AC input connections. Before connecting the AC input cable,
check the line power with that specified on the nameplate of the unit. Units with multiple AC input units have
taps inside, which must be set for the proper AC setting. These taps are located on terminal blocks on the
Power Transformers and on a terminal board on the Control Transformer. See tap card inside door (BELOW).
The AC input current specified on the nameplate is for rated output.
Please see the unit schematic fort more detailed information on tap settings.
Input AC breakers must be sized based on the rated value of the rated nameplate AC Input Current.
VOLTAGE CONTROL TAPS
480V
575V
CT
H2 (B)
H1 (B)
PT
2 (A)
3 (A)