The
OVERLOAD/CURRENT LIMIT ALARM
is triggered when the current limit or overload thresholds have
been reached.
There are no relay contacts assigned for these alarms.
When the unit is in current limit, the red
“Overload/Current Limit” indicator LED will flash.
See
Section 3.4 Settings Menu
for information on viewing and
adjusting the current limit threshold value. When the unit is in overload, the same red “Overload/Current Limit”
indicator LED will turn on solid. The overload threshold is not adjustable.
All alarms have adjustable time delays to energize; the range is 0 through 255 seconds. Refer to Table 11 for
the factory setting of each alarm.
Alarm
Delay (seconds)
AC Fail
20
Low DC Voltage
5
End of Discharge
5
EQ Timer, Mode 4
30
High Voltage Shutdown
20
High Voltage
5
Low DC Current
5
Ground Detection
5
Table 8 – Default Alarm Time Delays