23
Saving Settings
At any point, the user can press the BACK button from the main Settings Menu to exit the Settings Menu. When
the back button is pressed (on the main Settings Menu), the user is prompted if they would like to “Exit and Save
Settings?” If the BACK button is pressed again, the control board will return to the Settings Menu. If “YES” is
selected, the display will read “Saving Settings”, the menu will be exited and settings saved. If “NO” is selected,
the user is prompted to “Exit without Saving?” From this screen, if “YES” is selected, the user will be returned to
the DC output display and all changes to the settings will not be saved. If “NO” is selected, the user will be
returned to the Settings Menu.
3.5
Test Menu
All equipment is shipped from the factory fully tested and operational. As part of planned maintenance, users may
want to be able to re-test functionality of the alarm LEDs and relays. The Test Menu allows the user to test both
the LEDs on the display board as well as any alarm relay contacts.
3.5.1 Test LEDs
The Test LEDs menu allows the user to run a basic lamp test on the A36D. After selecting this menu, press the
“ENTER” button to light all of the LEDs on the display membrane. To end the LED test, press back.
NOTE:
Any additional LEDs on auxiliary boards will not be affected by this LED test.
3.5.2 Test Relays
The test relays menu allows the user to test the functionality of the alarm relay contacts. The menu allows for
each contact to be tested individually, or all at once. When a relay is being tested, its contacts will change state.
This means if a relay is in alarm state, it will revert to the non-alarm state during relay testing. The HVSD alarm
is not included in either of the other tests, but instead, has its own test menu.
When an alarm relay is being tested, the corresponding LED on the membrane will change state. There are no
relay contacts for the “OVERLOAD/CURR. LIMIT” or “END OF DISCHARGE” alarms; these LEDs will not be lit under
the relay test. As with the LED test, once the appropriate selection is made, press the “ENTER” button to start
the test and the “BACK” button to end the test.
< Exit and Save
Settings? NO
< Exit without
Saving? YES
< Test >
LEDs
< LED Test
Press ENTER
< End LED Test
Press BACK
< Test >
Relays
< Test ALL >
Contacts at Once
< Test Contacts>
Individually
< Test HVSD >
Alarm Contacts