Installation
2.1
Mounting the A36D
When mounting the A36D in any configuration, consider the size and weight of the charger. The wall, rack, and/or
floor must be able to support the weight of the charger as well as an additional safety factor. Verify the weight
of the A36D charger using Tables 1, 2 and 3, and the method of mounting using Table 4 below. The location
chosen for the charger should be within an ambient temperature range of 32 to 122˚F (0 to 50˚C) with a non-
condensing relative humidity no higher than 95%. The A36D should be mounted in an area free of explosive
materials and away from drips and splatter. The A36D utilizes convection cooling, so a clearance of at least 6in
(152mm) of free air must be maintained on vented sides. Maintain 36in (914mm) or more of clearance at the
front of the charger in order to allow for operation and maintenance. The bolts or screws used to secure the
charger should be sufficient length to assure a vibration-free mounting. The preferred fastener is a machine bolt
backed with a flat washer, lock washer, and nut. All hardware should be corrosion-resistant.
Enclosure
Number
Cable Entry
Standard
Mounting
Optional
Mounting Kits
AC Input
DC Output
4D
Left Top / Back
Right Top / Back
19/23” Rack
Wall* / Floor**
39
Left Top / Back
Right Top / Back
19/23” Rack
Wall* / Floor**
9E
Left Top / Back
Right Top / Back
23” Rack
Wall* / Floor**
33
Left Top / Back
Right Top / Back
23” Rack
Wall* / Floor**
33E
Left Top / Back
Right Top / Back
23” Rack
Wall* / Floor**
43
Top Left
Top Back
Floor
44
Top Left
Top Back
Floor
72
Right/Bottom/Side
Bottom
Floor
* Wall mounting brackets required and overall height would change. Case size may differ depending on optional accessories.
** Floor mounting brackets required and overall height would change. Case size may differ depending on optional accessories.
Table 4 -
Available Mounting Methods