6. TROUBLE-SHOOTING
Problem Possible Cause Corrective Action
F. Discharge current
immediately surges to a
high value and blows DC
discharge fuses even
though the current adjust
knob is set low
Reversed polarity of battery
connection
Ensure that polarity is respected
on battery connection. If
connector has been removed
ensure that DC leads are not
reversed.
Defective discharge power
control module
With AC voltage and battery
disconnected, open unit and
remove heavy leads from
terminals on black 1”x1”
(25mmx25mm) power module.
Check resistance between
terminals with ohmmeter. If short
circuit, call Power Products
technical support.
G. The DC charge fuse
blown
Reversed polarity of battery
connection
Ensure that polarity is respected
on battery connection. If
connector has been removed
ensure that DC leads are not
reversed.
Defective charge power control
module
With AC voltage and battery
disconnected, open unit and
remove ACL leads from terminals
on black 1¾”x2¼”
(45mmx60mm) power module
(G1 and G2 tabs included).
Check resistance b and
– terminals with ohmmeter. If
short circuit, call Power Products
technical service.