Cooling Circuit Connection and Filling
CAUTION
Risk of damage by using improper cooling hoses!
This may lead to damage to persons, damage to the unit or corrosion damage.
When choosing cooling hoses pay attention to sufficient burst strength and compatibility with
coolant!
Only use cooling hoses without any signs of damage!
The cooling hoses with an internal diameter of 9 mm are connected to the unit by means of hose
nipples. Water outlet and water inlet are indicated with respective symbols.
Fig. 8:
Labeling of water inlet and water outlet
1)
Connect a suitable hose to the hose nipples for water inlet and water outlet and secure it with a
clamp respectively.
2)
Connect the hoses to the corresponding nipples of the device to be cooled.
NOTE
When connecting the cooling hoses pay attention to flow direction. Follow the documentation released
by the manufacturer of the device to be cooled.
Transparent hoses stimulate algae growth that may increase the error-proneness of the components
built into the unit. Thus, only use non-transparent hoses.
Fig. 9:
Cap of coolant container
1 Cap
Water inlet
Water outlet
1