Labkotec LOKASET R Installation And Operation Instructions Manual Download Page 5

5

LOKASET R

    |    Installation and Operation Instructions     |    D18067Ae

1

2

3

4

5

2. Lokaset R – Operation

Lokaset R is designed for use as a tank full alarm for septic tanks. 
The principle of operation is that when the probe comes into contact 
with liquid, the transmitter transmits a signal to the Lokaset R central 
unit. The signal is sent every 10 minutes and the alarm is activated by 
two consecutive notes from the probe. The relay will de-energize in 
case of an alarm.

The central unit (1) signals the alarm with a buzzer sound and an 
alarm indicator light (2). The buzzer is silenced by the alarm reset 
button (3). The alarm mode can be deactivated by emptying the 
tank. The probe should be installed in the tank at the height of the 
liquid alarm level.

The central unit is plugged to the mains (230 V). When the power is 
connected, the green power light (4) and the radio signal indicator 
(5) are on. The transmitter is battery-powered. The battery is supplied 
with the device. In normal use, the battery life is at least 10 years. The 
central unit signals an alarm when the transmitter is not powered or 
the battery needs to be replaced.

The Lokaset R probe (SET/LV) is not suitable for measuring explosive 
or corrosive liquids.

Summary of Contents for LOKASET R

Page 1: ...LOKASET R Installation and Operation Instructions D18067Ae WIRELESS TANK FULL ALARM...

Page 2: ...LOKASET R Installation and Operation Instructions D18067Ae 2...

Page 3: ...LOKASET R Installation and Operation Instructions D18067Ae Contents 1 Introduction 4 2 Operation 5 3 Installation 6 4 Operating Mode 8 5 Service and Repairs 9 6 Alarms 10 7 Technical Specifications 1...

Page 4: ...he central unit is used for controlling and monitoring device operation The enclosed transmitter transmits the alarm signal wirelessly from the probe to the central unit Lokaset R can be installed in...

Page 5: ...th a buzzer sound and an alarm indicator light 2 The buzzer is silenced by the alarm reset button 3 The alarm mode can be deactivated by emptying the tank The probe should be installed in the tank at...

Page 6: ...nd the transmitter should be tested during installation in order to ensure that the radio signal can travel freely Activate the transmitter test mode see Service instructions p 9 Immerse the measuring...

Page 7: ...ng O ring 8 69 5 x 3 0 mm NBR70 is seated properly in the groove Close the protective cover 9 with the supplied stainless steel screws 10 2 pcs 3 x 16 mm Note Proper seating of the O ring and tightnes...

Page 8: ...Lokaset R central unit has three indicator lights and one button The green light POWER is the power indicator the blue light SIGNAL the wireless transmission indicator and the red light ALARM the alar...

Page 9: ...probe is during tank emptying The probe may be cleaned using running water Operation of the Lokaset R device can be checked in conjunc tion with maintenance by activating the transmitter test mode Act...

Page 10: ...being paired Press the function button p 9 on the Lokaset R transmitter The green light POWER and red light ALARM are on and the blue light SIGNAL flashes Complete the process by pressing the central...

Page 11: ...connection values 250 V 4 A 100 VA 35 x 130 x 80 mm Class II Indoor use only Green blue and red indicator light buzzer R TTE approval CE Marking Transmitter Type model Manufacturer Supply voltage Oper...

Page 12: ...Labkotec Oy Myllyhaantie 6 33960 Pirkkala Finland Tel 358 29 006260 exchange Fax 358 29 0061260 info labkotec fi www labkotec fi We reserve the right to changes 2009 Labkotec Oy...

Reviews: