LOKASET R
| Installation and Operation Instructions | D18067Ae
10
1
2
The Lokaset R central unit and transmitter form a device pair.
Any subsequent spare part deliveries require re-pairing.
Pair the devices by simultaneously pressing the alarm reset
button and powering the central unit. All lights on the central
unit will fl ash, indicating that the devices are being paired.
Press the function button (p. 9) on the Lokaset R transmitter.
The green light (POWER) and red light (ALARM) are on and
the blue light (SIGNAL) fl ashes. Complete the process by
pressing the central unit reset button again. The blue light
(SIGNAL) remains on and fl ashes every 8 seconds to indicate
the test mode. The Lokaset R central unit and transmitter
are now paired. The device returns to the normal operating
mode after 5 minutes.
6. Lokaset R – Alarms
Tank full alarm:
Red light (1) is on (continuous buzzer sound)
a) Reset the alarm (2)
b) Arrange tank disposal