OPERATION

SET POINT CONTROL SETTINGS

SET POINT (

SP

)   

 

 

 

 

 

 

Default: 70

°

F

•  The Set Point is the temperature value the SC will use to control the system.  

•  The SC will either add Stage Outputs, subtract Stage Outputs, or maintain the same number of Stage Outputs to hold the system 

temperature around the Set Point.

•  The Set Point is the average temperature the SC will maintain.  The size of the fl uctuation above and below the Set Point 

depends on the number of stages, the size of each stage, the system load, and the Sequencing mode.

•  When controlling temperature, the Set Point can be adjusted to any value in the temperature range. 

•  If the Set Point value is fl ashing, this indicates that the selected Set Point has been automatically changed. This may occur 

because of the Setback setting (see pg. 24) or the DHW mode (see pg. 25).  

•  If the Set Point displays 

OFF

 then the Outdoor Cutoff or the Shutdown is active (see below and pg. 24).

•  If it is a temperature system and the External Set Point is being used, the Set Point will vary with the 4-20mA input (see pg. 23).  

Pushing the 

UP

 or 

UP

UP

DOWN

 buttons while the Set Point is being displayed will not change the value of the Set Point.

DOWN

DOWN

OUTDOOR TEMPERATURE (

OUt

 

 

 

 

No Adjustment - Display Only

•  Use of the Outdoor Sensor is optional in the Set Point operation mode.

•  If an Outdoor sensor is installed, it can be used to provide an Outdoor Cutoff (see below).

•  If a sensor is not installed, the display will show 

OPn

, indicating that the 

OUTDOOR

 terminals are open. In this case, the SC 

will control the system to maintain the Set Point temperature.

OUTDOOR CUTOFF (

COF

 

 

 

 

 

Default: 60

°

F

•  The Outdoor Cutoff sets at what outdoor temperature the SC will begin heating. This setting will only be available if the SC does 

not register a fault from the Outdoor sensor (

OPn

 Open or 

SHt

 short). 

•  For heating, when the Outdoor temperature drops below the Outdoor Cutoff temperature, the SC will begin to Sequence stages 

for heat. It will continue to Sequence until the Outdoor temperature rises to 2°F above the Outdoor Cutoff temperature.

•  The Outdoor Cutoff temperature can be set from 40 to 100°F. In addition, an ON setting is provided to override the Outdoor 

Cutoff for continuous Sequencing, and an OFF setting can be used to temporarily prevent any Sequencing.

•  The Outdoor Cutoff has a built in 2°F differential. 

•  If the Outdoor temperature rises 2°F above the Outdoor Cutoff, the SC will not activate stages and the Set Point will read 

OFF

,  

unless there is a DHW call.

PROGRAMMED OFFSET (

PO

)   

 

 

 

 

Default: 0

°

F

External Set Point

•  The Programmed Offset can be used to fi ne tune the External Set Point reading.

•  A 4mA input signal should generate a Set Point display of 60°F (see pg. 23).

•  If a 4mA input generates a display of 62°F, then by setting the Programmed Offset to -2, the display will show 60°F.  Similarly, if 

a 4mA input generates a display of 59°F then by setting the Programmed Offset to 1, the display will show 60°F.

•  The Programmed Offset should only be used to fi ne tune the Set Point display when inputting a 4mA signal.  Do not use it to 

adjust the Set Point reading at any other mA input value.  

•  The Programmed Offset can be set from -15 to 15 degrees.

SETBACK/SHUTDOWN (

Stb

)   

 

 

 

 

Default: 0

°

F

•  For temperature applications, the terminals 

7

 and 

77

8

 can be programmed to provide either a lower Set Point temperature in 

heating or Shutdown.

•  T

are sleeping.

•  To program 

INPUT

 terminals

INPUT

INPUT

 7

 and 

 7

 7

to Shutdown, set the Setback/Shutdown value to 0. When the SC is Shutdown, the Set 

Point display will show 

OFF

.    

•  The Setback/Shutdown value can also be set from 1 to 40°F. 

•  For a nonzero value in heating, the Set Point will be reduced by the amount of the Setback. This will be indicated by the System 

Temperature display fl ashing and the Set Point display fl ashing the new value.

Summary of Contents for SC6

Page 1: ...20 ma OUTDOOR SC Non Modulating Model SC6 SC6P and SC 12 Output panel to Sequence up to 12 individual stages with lead lag and manual override capabilities Installation and Operation Instructions FOR...

Page 2: ...WITCH 8 OFF 10 SET POINT CONTROL WITH OSS SEQUENCING 11 OUTDOOR RESET WITH NORMAL SEQUENCING 12 OUTDOOR RESET WITH OSS SEQUENCING 13 SC 6 AND SC 12 OUTPUT WIRING 14 WIRING THE STAGE OUTPUTS 14 SC 6P O...

Page 3: ...ON Output 5 OFF AUTO ON Output 6 OFF AUTO ON System LEAD OUTPUT ON 4 20 ma OUTDOOR SC Digital display reads sensor value constantly Install a relay for each output stage which will be active Use these...

Page 4: ...oint control for temperature 8 Outdoor Reset Hydronic heating control with outdoor reset ON ON 1 System Pump SYSTEM relay is on based on outside temp Shutdown and DHW priority 1 Combustion Air Damper...

Page 5: ...r the enclosure through a different opening from any Class 2 voltage wiring Connect the hot line to terminal marked LINE Connect the neutral line to the terminal marked NEUT The green ground screw mus...

Page 6: ...tact the Calculated water DHW input is enabled by closing a dry contact the Calculated water DHW temperature or the Set Point will change to 200 F and the decimal point on the left most digit on the d...

Page 7: ...active The System relay will remain energized even if all Output Stages are off If an outdoor sensor is not connected or registers a fault condition The System relay will be energized when any stage i...

Page 8: ...rease the value DOWN button to decrease the value DOWN When the correct value is shown release the button and wait approximately 5 seconds If any changes were made the display will ash Set the Sequenc...

Page 9: ...WN button to decrease the value DOWN When the correct value is shown release the button and wait approximately 5 seconds If any changes were made the display will ash Set the Sequencing Mode Default N...

Page 10: ...e System Delay is adjustable from 0 to 30 minutes Default is 0 5 or 6 Times Purge Time The Purge Time should be set to the length of the unit s purge cycle The Purge Time will apply when any ON OFF un...

Page 11: ...t With a known 4mA input the offset can be set to make the External Set Point 110 F The Program Offset is adjustable between 10 F to 10 F Default is 0 F 4 or more Times Throttling Range The throttling...

Page 12: ...ill remain energized after the last Output has been turned off or the outdoor temperature rises above the Starter The System Delay is adjustable from 0 to 30 minutes 8 Times Purge Time The Purge Time...

Page 13: ...egardless of outdoor temperature or the reset curve selected The Offset is adjustable from 40 F to 40 F Default is 0 F 6 Times System Delay The System Delay controls how long the System relay will rem...

Page 14: ...lly Open N O relay contact The N O contacts are dry contacts only They do not source any voltage Each N O contact is capable of switching 6A resistive Total output of all stages including the SYSTEM m...

Page 15: ...o the Hi control circuit 3 Stage Lo Mid Hi Units Each unit has one pump relay and three stage relays associated with it Check the chart for the Pump Lo Mid and Hi OUTPUT positions OUTPUT positions OUT...

Page 16: ...nputs Pump 3 Pump 2 Pump 1 Pump 3 Pump 2 Pump 1 Connect to 120VAC see page 5 Plumbing Class 1 Wiring Class 2 Sensor Wiring The laars SC Sequencing control DOES NOT source power for boiler stages or pu...

Page 17: ...e HiFire HiFire LoMid LoMid Output 7 Limit Limit Limit Limit Limit Limit Limit Limit Limit Limit Limit HiMid HiMid Output 8 Limit Limit Limit Limit Limit HiFire HiFire HiFire MidFire MidFire HiFire Hi...

Page 18: ...not register a fault from the Outdoor sensor OPn Open or SHt short For heating when the Outdoor temperature drops below the Outdoor Cutoff temperature the SC will begin to Sequence stages for heat It...

Page 19: ...heat It will continue to Sequence until the Outdoor temperature rises to 2 F above the Outdoor Cutoff temperature The Outdoor Cutoff temperature can be set from 40 to 100 F In addition an ON setting...

Page 20: ...ature display ashing the new value NORMAL SEQUENCING SETTINGS REACTION TIME Rt Default 2 minutes The Reaction Time controls how Output Stages are Sequenced on and off based on PID type logic Shorter R...

Page 21: ...Calculated water temperature to allow the Output Stage to run longer and therefore also be off longer before restarting The Last Stage Hold provides an adjustable temperature value which is added to...

Page 22: ...Stage The Output with the green light on is currently the Lead Stage Only one Stage Output can be the Lead Stage at any given time The Lead Stage is always the rst stage brought on when there is a cal...

Page 23: ...sition OFF position OFF OUTPUT LIGHTS The row of red lights marked OUTPUT ON indicate which outputs are energized If the red light next to a Stage Output is on then its output relay should be energize...

Page 24: ...ust be continuous for any Stage Output to be active If the PROVE PROVE inputs are opened when Stage PROVE inputs are opened when Stage PROVE Outputs are active then they will immediately de energize a...

Page 25: ...will close the DHW input terminals DHW input terminals DHW If the System Output is con gured for Combustion Air Damper operation the System relay output will be closed when any Stage Output is activa...

Page 26: ...Temperature Display Outdoor Temperature Display shows SHt The SC sees a short across the input terminals Remove the wires from the OUTDOOR 11 and 12 and 12 and inputs The display should change to rea...

Page 27: ...t being energized to determine why it is not operating Red stage light is lit but the unit is not on The SC is calling for this unit to be on Follow the procedure above Red stage light is not lit but...

Page 28: ...rvice Service Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars com Litho in U S A...