ADJUSTING THE CONTROL SETTING

•   After the power up routine is complete, the display will show the system water temperature.

•  To display the other control settings, repeatedly press the center 

SELECT SETTING 

button.

•  A setting can only be adjusted when it is being displayed.

•  Use the UP and DOWN buttons to adjust the setting.

•  The display will always revert back to the actual system temperature after 30 seconds.

•  Select the appropriate page from the list below for the available control settings for your 

application:

  Set Point Control with Normal Sequencing Temperature or External Set Point 

pg. 10

  Set Point Control with Oversize System Sequencing Temperature or External Set Point 

pg. 11

  Outdoor Reset Control with Normal Sequencing 

pg. 12

  Outdoor Reset Control with Oversize System Sequencing 

pg. 13

SET POINT CONTROL WITH NORMAL SEQUENCING

Dip Switch 8 - OFF

Press SELECT 

Button

DISPLAY

Press and hold either the UP or DOWN button to adjust

Once

Set Point

The Set Point is the temperature which the SC will sequence stages to hold.  Note that if you are 

using the External Set Point, you will not be able to change the Set Point unless you adjust the 4-

20mA input. The Set Point is adjustable between -30

°

F to 250

°

F. Default is 70

°

F.

Twice

Outdoor Temp

This is the outdoor sensor temperature value.

3 Times

♦♦

Outdoor Cutoff

Available only when the outdoor sensor is installed. When the outdoor temperature falls below the 

Outdoor Cutoff value, the SC will activate stages for heat. The Outdoor Cutoff can be set ON or OFF 

and from 40 to 100°F. Default is 60°F.

3 or 4 Times

Reaction Time

The Reaction Time controls the minimum run time for a stage (1/2 the Reaction Time).  Also, it con-

trols how long should a stage run before it activates/subtracts another stage. It is adjustable from half 

a minute (0.5) to 8.0 minutes. Default is 2 minutes.

4 or 5 Times

System Delay

The System Delay controls how long the System relay will remain energized after the last Output has 

been turned off or the outdoor temperature rises above the Starter.  The System Delay is adjustable 

from 0 to 30 minutes.  Default is 0.

5 or 6 Times

Purge Time

The Purge Time should be set to the length of the unit’s purge cycle.  The Purge Time will apply 

when any ON/OFF unit is activated.  On multiple stage units, the Purge Time will only apply to the Lo 

stages.  The Purge Time is adjustable from 0.0 to 10.0 minutes.  Default is 0.

6 or 7 Times

Boiler runtime

This is the minimum amount of time any boiler will run after the Purge cycle has been completed. This 
timer does not apply when only one stage is running, the Last Stage Hold 

LSH 

applies in that case. 

The Boiler Runtime is adjustable between 0 to 60 minutes. Default is 0.

7 or 8 Times

♦♦

Program Offset

The Programmed Offset fi ne tunes the External Set Point.  With a known 4mA input, the offset can be 

set to make the External Set Point 110°F. The Program Offset is adjustable between -10

°

F to +10

°

F. 

Default is 0

°

F.

7 or more Times

Last Stage Hold

To prevent short cycling of the last stage in low load conditions, the system temperature can exceed 

the Set Point by the amount selected by the Last Stage Hold before the last stage is turned off. The 

Last Stage Hold is adjustable between 0

°

F to 20

°

F. Default is 10

°

F.

8 or more Times

♦♦

Setback

The Setback adjusts the number of degrees the Set Point water temperature will be reduced when 

Input terminals 7 and 8 are closed. If the Setback is set to 0, then the system will Shutdown on a 

closure. The Setback is adjustable from 0

°

F to 40

°

F. Default is 0°F.

8 or more Times

♦♦

DHW Priority Time

Only available when the System Output is set to System Pump (dip switch 1 is ON and dip switch 6 is 

OFF )  This setting adjusts the amount of time the System relay output will remain off during a DHW 

call. If the DHW call is not satisfi ed before the DHW priority time has elapsed, the System relay will 

energize to provide heat. The DHW Priority is adjustable from 0 to 4 hours in half hour increments.  

Default is 0.

8 or more Times

Default

The SC returns to the default display of system water temperature.

♦    

Actual temperature values are not adjustable

♦♦

  May not be available, depending on status of the outdoor sensor and dip switches.

SELECT

SETTING

UP

DOWN

Press and

Hold to

Adjust

Press to Scroll

Through Control

Settings

Control Settings

Display

Summary of Contents for SC6

Page 1: ...20 ma OUTDOOR SC Non Modulating Model SC6 SC6P and SC 12 Output panel to Sequence up to 12 individual stages with lead lag and manual override capabilities Installation and Operation Instructions FOR...

Page 2: ...WITCH 8 OFF 10 SET POINT CONTROL WITH OSS SEQUENCING 11 OUTDOOR RESET WITH NORMAL SEQUENCING 12 OUTDOOR RESET WITH OSS SEQUENCING 13 SC 6 AND SC 12 OUTPUT WIRING 14 WIRING THE STAGE OUTPUTS 14 SC 6P O...

Page 3: ...ON Output 5 OFF AUTO ON Output 6 OFF AUTO ON System LEAD OUTPUT ON 4 20 ma OUTDOOR SC Digital display reads sensor value constantly Install a relay for each output stage which will be active Use these...

Page 4: ...oint control for temperature 8 Outdoor Reset Hydronic heating control with outdoor reset ON ON 1 System Pump SYSTEM relay is on based on outside temp Shutdown and DHW priority 1 Combustion Air Damper...

Page 5: ...r the enclosure through a different opening from any Class 2 voltage wiring Connect the hot line to terminal marked LINE Connect the neutral line to the terminal marked NEUT The green ground screw mus...

Page 6: ...tact the Calculated water DHW input is enabled by closing a dry contact the Calculated water DHW temperature or the Set Point will change to 200 F and the decimal point on the left most digit on the d...

Page 7: ...active The System relay will remain energized even if all Output Stages are off If an outdoor sensor is not connected or registers a fault condition The System relay will be energized when any stage i...

Page 8: ...rease the value DOWN button to decrease the value DOWN When the correct value is shown release the button and wait approximately 5 seconds If any changes were made the display will ash Set the Sequenc...

Page 9: ...WN button to decrease the value DOWN When the correct value is shown release the button and wait approximately 5 seconds If any changes were made the display will ash Set the Sequencing Mode Default N...

Page 10: ...e System Delay is adjustable from 0 to 30 minutes Default is 0 5 or 6 Times Purge Time The Purge Time should be set to the length of the unit s purge cycle The Purge Time will apply when any ON OFF un...

Page 11: ...t With a known 4mA input the offset can be set to make the External Set Point 110 F The Program Offset is adjustable between 10 F to 10 F Default is 0 F 4 or more Times Throttling Range The throttling...

Page 12: ...ill remain energized after the last Output has been turned off or the outdoor temperature rises above the Starter The System Delay is adjustable from 0 to 30 minutes 8 Times Purge Time The Purge Time...

Page 13: ...egardless of outdoor temperature or the reset curve selected The Offset is adjustable from 40 F to 40 F Default is 0 F 6 Times System Delay The System Delay controls how long the System relay will rem...

Page 14: ...lly Open N O relay contact The N O contacts are dry contacts only They do not source any voltage Each N O contact is capable of switching 6A resistive Total output of all stages including the SYSTEM m...

Page 15: ...o the Hi control circuit 3 Stage Lo Mid Hi Units Each unit has one pump relay and three stage relays associated with it Check the chart for the Pump Lo Mid and Hi OUTPUT positions OUTPUT positions OUT...

Page 16: ...nputs Pump 3 Pump 2 Pump 1 Pump 3 Pump 2 Pump 1 Connect to 120VAC see page 5 Plumbing Class 1 Wiring Class 2 Sensor Wiring The laars SC Sequencing control DOES NOT source power for boiler stages or pu...

Page 17: ...e HiFire HiFire LoMid LoMid Output 7 Limit Limit Limit Limit Limit Limit Limit Limit Limit Limit Limit HiMid HiMid Output 8 Limit Limit Limit Limit Limit HiFire HiFire HiFire MidFire MidFire HiFire Hi...

Page 18: ...not register a fault from the Outdoor sensor OPn Open or SHt short For heating when the Outdoor temperature drops below the Outdoor Cutoff temperature the SC will begin to Sequence stages for heat It...

Page 19: ...heat It will continue to Sequence until the Outdoor temperature rises to 2 F above the Outdoor Cutoff temperature The Outdoor Cutoff temperature can be set from 40 to 100 F In addition an ON setting...

Page 20: ...ature display ashing the new value NORMAL SEQUENCING SETTINGS REACTION TIME Rt Default 2 minutes The Reaction Time controls how Output Stages are Sequenced on and off based on PID type logic Shorter R...

Page 21: ...Calculated water temperature to allow the Output Stage to run longer and therefore also be off longer before restarting The Last Stage Hold provides an adjustable temperature value which is added to...

Page 22: ...Stage The Output with the green light on is currently the Lead Stage Only one Stage Output can be the Lead Stage at any given time The Lead Stage is always the rst stage brought on when there is a cal...

Page 23: ...sition OFF position OFF OUTPUT LIGHTS The row of red lights marked OUTPUT ON indicate which outputs are energized If the red light next to a Stage Output is on then its output relay should be energize...

Page 24: ...ust be continuous for any Stage Output to be active If the PROVE PROVE inputs are opened when Stage PROVE inputs are opened when Stage PROVE Outputs are active then they will immediately de energize a...

Page 25: ...will close the DHW input terminals DHW input terminals DHW If the System Output is con gured for Combustion Air Damper operation the System relay output will be closed when any Stage Output is activa...

Page 26: ...Temperature Display Outdoor Temperature Display shows SHt The SC sees a short across the input terminals Remove the wires from the OUTDOOR 11 and 12 and 12 and inputs The display should change to rea...

Page 27: ...t being energized to determine why it is not operating Red stage light is lit but the unit is not on The SC is calling for this unit to be on Follow the procedure above Red stage light is not lit but...

Page 28: ...rvice Service Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars com Litho in U S A...

Reviews: