Laars Sequencing Controls

There are more than one green lead stage lights on

  Check the 120VAC power input to the SC.  Turn power to the SC off and back on.  If only one lead stage LED does not light, the 

unit may be damaged.

Lead Stage does not rotate when switch to 

INCREMENT

  Only units which have (all stages of) their 

OFF/AUTO/ON

 switches in the 

OFF/AUTO/ON

OFF/AUTO/ON

AUTO

 position and which are designated as Unit or 

Lo stages (see chart on pg. 19) can be lead.  If there is more than one stage which meets this criteria, the SC may be damaged.

Lead Stage does not rotate every 24 hours (First On/Last Off Rotation) 

  Check the dip switch is set up for First On/Last Off rotation (see pg. 4).  Check the lead stage can be rotated as described above.  

Finally, check if the 

INCREMENT/OFF/AUTO

 switch is in the 

AUTO

 position.  In the 

AUTO

 position, the lead stage should 

rotate among the possible lead stages every 12 hours after the unit is fi rst powered up, and then every 24 hours thereafter.  If the 

panel loses power, the lead stage and the rotation counters will be reset.

Lead Stage does not rotate First On/First Off 

  Check the dip switch is set up for First On/First Off rotation (see pg. 4).  Check the lead stage can be rotated as described above.  

Finally check if the 

INCREMENT/OFF/AUTO

 switch is in the 

AUTO

 position.  

STAGE OUTPUTS 

When switched to 

ON

, the unit does not come on

  Remove any wires attached to the SC output.  Check for continuity across the SC N.O. contacts.  If there is continuity, the SC 

output is working correctly.  Check the wiring and the unit being energized to determine why it is not operating.

Red stage light is lit, but the unit is not on

  The SC is calling for this unit to be on.  Follow the procedure above.

Red stage light is not lit, but the unit is on

 

SC  N.O. contacts.  If there is no continuity, the SC output is working correctly.  Check the unit for any other operating controls 

which may be causing it to run.

Stage Outputs don’t Sequence

  Make sure that the red output lights on the SC correspond to the stage’s operation.  If they don’t, follow the steps above.  

temperature is correct and the display does not read 

OFF

 or 

PrF

.  Finally, check the 

OFF/AUTO/ON

 stage switches.  Only 

OFF/AUTO/ON

OFF/AUTO/ON

units which (have all stages) switched to 

AUTO

 will be part of the automatic Sequencing.  

SYSTEM OUTPUT

When switched to 

ON

, the 

SYSTEM

 component does not come on

SYSTEM

SYSTEM

  Remove any wires attached to the  SC 

SYSTEM 

terminals.  Check for continuity across the N.O. contacts.  Then check the 

N.C. terminals are open. If both are true, the SC is working correctly.  Check the wiring and the component being energized to 

determine why it is not operating.

Red stage light is lit, but the 

SYSTEM

 component is not on

SYSTEM

SYSTEM

  The SC is calling for the unit.  Follow the procedure above.

Red stage light is not lit, but the 

SYSTEM

 component is on

SYSTEM

SYSTEM

  The SC is not calling for the unit to run.  Remove any wires attached to the SC 

SYSTEM

 output terminals.  Check the N.O. 

SYSTEM

SYSTEM

terminals are open.  Then check the N.C. terminals are closed. If both conditions are true, the SC output is working correctly.  

Check the unit for any other operating controls which may be causing it to energize.

Summary of Contents for SC6

Page 1: ...20 ma OUTDOOR SC Non Modulating Model SC6 SC6P and SC 12 Output panel to Sequence up to 12 individual stages with lead lag and manual override capabilities Installation and Operation Instructions FOR...

Page 2: ...WITCH 8 OFF 10 SET POINT CONTROL WITH OSS SEQUENCING 11 OUTDOOR RESET WITH NORMAL SEQUENCING 12 OUTDOOR RESET WITH OSS SEQUENCING 13 SC 6 AND SC 12 OUTPUT WIRING 14 WIRING THE STAGE OUTPUTS 14 SC 6P O...

Page 3: ...ON Output 5 OFF AUTO ON Output 6 OFF AUTO ON System LEAD OUTPUT ON 4 20 ma OUTDOOR SC Digital display reads sensor value constantly Install a relay for each output stage which will be active Use these...

Page 4: ...oint control for temperature 8 Outdoor Reset Hydronic heating control with outdoor reset ON ON 1 System Pump SYSTEM relay is on based on outside temp Shutdown and DHW priority 1 Combustion Air Damper...

Page 5: ...r the enclosure through a different opening from any Class 2 voltage wiring Connect the hot line to terminal marked LINE Connect the neutral line to the terminal marked NEUT The green ground screw mus...

Page 6: ...tact the Calculated water DHW input is enabled by closing a dry contact the Calculated water DHW temperature or the Set Point will change to 200 F and the decimal point on the left most digit on the d...

Page 7: ...active The System relay will remain energized even if all Output Stages are off If an outdoor sensor is not connected or registers a fault condition The System relay will be energized when any stage i...

Page 8: ...rease the value DOWN button to decrease the value DOWN When the correct value is shown release the button and wait approximately 5 seconds If any changes were made the display will ash Set the Sequenc...

Page 9: ...WN button to decrease the value DOWN When the correct value is shown release the button and wait approximately 5 seconds If any changes were made the display will ash Set the Sequencing Mode Default N...

Page 10: ...e System Delay is adjustable from 0 to 30 minutes Default is 0 5 or 6 Times Purge Time The Purge Time should be set to the length of the unit s purge cycle The Purge Time will apply when any ON OFF un...

Page 11: ...t With a known 4mA input the offset can be set to make the External Set Point 110 F The Program Offset is adjustable between 10 F to 10 F Default is 0 F 4 or more Times Throttling Range The throttling...

Page 12: ...ill remain energized after the last Output has been turned off or the outdoor temperature rises above the Starter The System Delay is adjustable from 0 to 30 minutes 8 Times Purge Time The Purge Time...

Page 13: ...egardless of outdoor temperature or the reset curve selected The Offset is adjustable from 40 F to 40 F Default is 0 F 6 Times System Delay The System Delay controls how long the System relay will rem...

Page 14: ...lly Open N O relay contact The N O contacts are dry contacts only They do not source any voltage Each N O contact is capable of switching 6A resistive Total output of all stages including the SYSTEM m...

Page 15: ...o the Hi control circuit 3 Stage Lo Mid Hi Units Each unit has one pump relay and three stage relays associated with it Check the chart for the Pump Lo Mid and Hi OUTPUT positions OUTPUT positions OUT...

Page 16: ...nputs Pump 3 Pump 2 Pump 1 Pump 3 Pump 2 Pump 1 Connect to 120VAC see page 5 Plumbing Class 1 Wiring Class 2 Sensor Wiring The laars SC Sequencing control DOES NOT source power for boiler stages or pu...

Page 17: ...e HiFire HiFire LoMid LoMid Output 7 Limit Limit Limit Limit Limit Limit Limit Limit Limit Limit Limit HiMid HiMid Output 8 Limit Limit Limit Limit Limit HiFire HiFire HiFire MidFire MidFire HiFire Hi...

Page 18: ...not register a fault from the Outdoor sensor OPn Open or SHt short For heating when the Outdoor temperature drops below the Outdoor Cutoff temperature the SC will begin to Sequence stages for heat It...

Page 19: ...heat It will continue to Sequence until the Outdoor temperature rises to 2 F above the Outdoor Cutoff temperature The Outdoor Cutoff temperature can be set from 40 to 100 F In addition an ON setting...

Page 20: ...ature display ashing the new value NORMAL SEQUENCING SETTINGS REACTION TIME Rt Default 2 minutes The Reaction Time controls how Output Stages are Sequenced on and off based on PID type logic Shorter R...

Page 21: ...Calculated water temperature to allow the Output Stage to run longer and therefore also be off longer before restarting The Last Stage Hold provides an adjustable temperature value which is added to...

Page 22: ...Stage The Output with the green light on is currently the Lead Stage Only one Stage Output can be the Lead Stage at any given time The Lead Stage is always the rst stage brought on when there is a cal...

Page 23: ...sition OFF position OFF OUTPUT LIGHTS The row of red lights marked OUTPUT ON indicate which outputs are energized If the red light next to a Stage Output is on then its output relay should be energize...

Page 24: ...ust be continuous for any Stage Output to be active If the PROVE PROVE inputs are opened when Stage PROVE inputs are opened when Stage PROVE Outputs are active then they will immediately de energize a...

Page 25: ...will close the DHW input terminals DHW input terminals DHW If the System Output is con gured for Combustion Air Damper operation the System relay output will be closed when any Stage Output is activa...

Page 26: ...Temperature Display Outdoor Temperature Display shows SHt The SC sees a short across the input terminals Remove the wires from the OUTDOOR 11 and 12 and 12 and inputs The display should change to rea...

Page 27: ...t being energized to determine why it is not operating Red stage light is lit but the unit is not on The SC is calling for this unit to be on Follow the procedure above Red stage light is not lit but...

Page 28: ...rvice Service Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars com Litho in U S A...

Reviews: