Newport Oil-Fired Heater

Page 9

WARNING:- The height should not exceed 13 feet (4m)
WARNING:- The vacuum must not exceed 11.44 HG. (11.44 
inches of Mercury). Burner is shipped from the factory set up 
for two pipe system.
Important:- An external fi lter must be placed in the fuel line 
between the fuel tank and the burner pump.

Two-Pipe
System

One-Pipe
System

Figure 5. Piping information.

Air vent

Fill pipe

Valve

Figure 5A

1¼" min.

Oil tank

"H"

Filter

"P"

Burner

Boiler

Air vent 1¼" min.

Fill pipe

Oil

tank

Figure 5B

Valve

Filter

Burner

Boiler

"H"

PIPE LENGTHS

"H"

One Pipe Gravity System

3/8" O.D.

1/2" O.D.

ft.

m

ft.

m

ft.

m

0

0

0

0

0

0

0.5

33

10.1

65

19.8

3

0.9

65

19.8

130

39.6

5

1.5

130

39.6

260

79.2

2

195

59.4

325

99

PIPE LENGTHS

"H"

Two Pipe Gravity System

3/8" O.D.

1/2" O.D.

ft.

m

ft.

m

ft.

m

0

0

0

0

0

0

0.5

115

33.0

330

100.6

3

0.9

100

30.5

330

100.6

5

1.5

80

24.4

330

100.6

2

50

15.2

295

89.9

2.9

25

7.6

100

30.5

11

3.4

20

6.1

65

19.8

OUT OF

PRODUCTION

Summary of Contents for newport

Page 1: ...ich could cause serious injury property damage or death Improper installation and or operation will void the warranty WARNING If the information in this manual is not followed exactly a fire or explos...

Page 2: ...er normally fitted 4 1 10 Installation of Alternate Nozzles for Higher Output 4 1 11 Boiler Controls normally fitted 3 1 12 Oil 3 1 13 Oil Storage and Pipe Layout 3 1 14 Electrical Wiring 4 1 15 Opera...

Page 3: ...gnee 1 3 Boiler Location The boiler should be positioned as near to the chimney as possible and have a minimum smoke pipe connector length of 18 457mm CAUTION Newport boilers must not be directly conn...

Page 4: ...unit Important Refer to burner pump instructions for detailed fuel line and pump usage information All installations must conform to local and national codes See Figures 5A and 5B Figure 5A One pipe...

Page 5: ...tire flue and venting system inspected 1 17 Cleaning the Boiler To maintain the high thermal efficiency and a long life from your boiler it should be cleaned at least once a year preferably at the end...

Page 6: ...be causing a blockage 1 19 Servicing the Burner This should only be carried out by a trained and licensed service technician in accordance with the burner maker s instructions 1 20 Maintenance of the...

Page 7: ...35 133 30 150 44 160 47 177 52 Output MBTU hr kW 90 26 105 30 116 34 130 38 139 40 154 48 Efficiency AFUE 83 6 83 1 83 1 83 7 83 0 83 0 Net Stack Temperature F C 312 156 353 178 371 188 351 177 386 1...

Page 8: ...front panel 3 with screws 2 Slide assembled jacket over boiler and secure side panels to base tray 3 Fix rear panel 4 to sides 4 Adjust corner brackets 5 on heat exchanger so they touch inside of jack...

Page 9: ...rmation Air vent Fill pipe Valve Figure 5A 1 min Oil tank H Filter P Burner Boiler Air vent 1 min Fill pipe Oil tank Figure 5B Valve Filter Burner Boiler H PIPE LENGTHS H One Pipe Gravity System 3 8 O...

Page 10: ...verload protection as required 24V Room Thermostat 1K L1 Hot Power Supply 120V L2 Circulator Switch Low Limit Circulator Hi Limit 1K2 Oil Burner Relay Heating Circulator AQUASTAT RELAY L8124A 1K1 WIRI...

Page 11: ...85 110 Use with P N 51 056 51 090 Flue Cover Assembly 85 110 52 108 Front Panel Assembly 85 110 52 116 Left Panel Assembly 85 110 52 124 Right Panel Assembly 85 110 51 128 Top Panel Assembly 85 110 5...

Page 12: ...Fax 800 559 1583 Customer Service Service Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130...

Reviews: