Page 21
N
EO
T
HERM
Residential Boilers
®
SCHED 40 METAL PIPE CAPACITY FOR 1.50 SPECIFIC GRAVITY
UNDILUTED PROPANE
NOMINAL PIPE SIZE
@
11” W.C. INLET AND 0.5” W.C. PRESSURE DROP
SIZE
1/2” 3/4” 1” 1-1/4”
1-1/2” 2”
LENGTH
MAXIMUM CAPACITY IN THOUSANDS OF BTU PER HOUR
20 200 418 787 1616 2422 4664
40 137 287 541 1111 1664
3205
60 110 231 434 892 1337
2574
80 94 197 372 763 1144
2203
100 84 175 330 677 1014
1952
Table 13.
Notes:
Consult and confirm with Applicable Fuel Gas
Code before beginning work.
Verify gas inlet pressure is between
4” W.C.
(1.0kPa)
and
13” W.C. (3.2kPa)
, before and
during operation.
Source: ANSI Z223.1-80 National Fuel Gas Code.
NOTE
: This unit and all other gas appliances sharing
the gas supply line must be firing at maximum
capacity to properly measure the inlet supply
pressure. The pressure can be measured at the
supply pressure port on the gas valve. Low gas
pressure could be an indication of an undersized
gas meter, undersized gas supply lines and/or an
obstructed gas supply line. Some Units are equipped
with low and high pressure gas switches that are
integrally vent limited. These types of devices do not
require venting to atmosphere.
Residential
table 13
Boiler Flow and Head Requirements
boiler only
Flow
H/L
Flow
H/L
Flow
H/L
Flow
H/L
Flow
H/L
Flow
H/L
Flow
H/L
Flow
H/L
Flow
H/L
Flow
H/L
gpm
feet
gpm
feet
gpm
feet
gpm
feet
gpm
feet
gpm
feet
gpm
feet
gpm
feet
gpm
feet
gpm
feet
80
10
26.8
7.6
16.9
6.1
11.7
5.1
8.65
4.3
6.5
3.8
5.28
3.4
4.3
3
3.6
2.8
3.1
2.5
2.7
105
13.3
38.8
10
23.3
8
15.6
6.7
11.3
5.7
8.48
5
6.7
4.4
5.4
4
4.5
3.6
3.8
3.3
3.2
150
19
39.4
14.3
24.1
11.4
16.3
9.5
11.9
8.1
9.03
7.1
7.19
6.3
5.9
5.7
4.9
5.2
4.2
4.8
3.6
210
26.7
28.1
20
15.6
16
9.88
13.4
6.88
11.3
4.86
9.9
3.71
8.9
3
8
2.4
7.3
2
6.7
1.6
Flow
H/L
Flow
H/L
Flow
H/L
Flow
H/L
Flow
H/L
Flow
H/L
Flow
H/L
Flow
H/L
Flow
H/L
Flow
H/L
lpm
m
lpm
m
lpm
m
lpm
m
lpm
m
lpm
m
lpm
m
lpm
m
lpm
m
lpm
m
80
37.9
8.2
28.8
5.2
23.1
3.6
19.3
2.6
16.3
2.0
14.4
1.6
12.9
1.3
11.4
1.1
10.6
0.9
9.5
0.8
105
50.3
11.8
37.9
7.1
30.3
4.8
25.4
3.4
21.6
2.6
18.9
2.0
16.7
1.6
15.1
1.4
13.6
1.2
12.5
1.0
150
71.9
12.0
54.1
7.3
43.2
5.0
36.0
3.6
30.7
2.8
26.9
2.2
23.8
1.8
21.6
1.5
19.7
1.3
18.2
1.1
210
101.1
8.6
75.7
4.8
60.6
3.0
50.7
2.1
42.8
1.5
37.5
1.1
33.7
0.9
30.3
0.7
27.6
0.6
25.4
0.5
residential
Boiler only
Boiler and Pump
Size
80
105
150
210
Size
80
105
150
210
Voltage
120V
120V
120V
120V
Voltage
120V
120V
120V
120V
FLA
2.0
2.0
2.0
2.0
FLA
2.8
3.8
3.8
4.0
MCA
2.5
2.5
2.5
2.5
MCA
3.5
4.8
4.8
5.0
MOP
15
15
15
15
MOP
15
15
15
15
40
45
50
55
60
15
20
25
30
35
8
11
14
17
19
22
25
28
31
33
Summary of Contents for NEOTHERM NTH Series
Page 4: ...LAARS Heating Systems...
Page 24: ...Page 24 LAARS Heating Systems Figure 9 Hydronic Piping Single Boiler Zoning with Circulators...
Page 33: ...Page 33 NEOTHERM Residential Boilers Figure 16 Control Panel Layout...
Page 38: ...Page 38 LAARS Heating Systems Figure 19 Ladder Diagram 7 H Ladder Diagram...
Page 67: ...Page 67 NEOTHERM Residential Boilers Figure 44 Heat Exchanger Components 68A 65 67 60 66 63 64...
Page 68: ...Page 68 LAARS Heating Systems Figure 45 Electrical Components...
Page 82: ...LAARS Heating Systems Notes...