be wired into the boiler control circuit to prevent the 

boiler from firing unless the blower is operating.

     The boiler must be completely isolated and 

protected from any source of corrosive chemical 

fumes such as those emitted by trichloroethylene, 

perchloroethylene, chlorine, etc.

3B.  Venting

 

Vent Categories:

  Mini-Therm JVS is a natural draft 

appliance for Category I venting only.  JVH is a 

fan-assisted product that can be vented vertically in a 

properly-designed Category I system, or can be vented 

horizontally as a Category III appliance, per this 

installation manual.

 WARNING

This boiler must be vented in accordance with 

Part 7, Venting of Equipment, of the latest edition 

of the National Fuel Gas code, ANSI Z223.1 and 

all applicable local building codes. In Canada, 

follow CAN/CGA B149 Installation codes. 

Improper venting of this appliance can result in 

excessive levels of carbon monoxide which can 

result in severe personal injury or death!

 AVERTISSEMENT

  

Cette chaudière doit être ventilé, conformément 

aux dispositions de la partie 7, de la ventilation de 

l'équipement, de la dernière édition du National 

gaz carburant code, ANSI Z223.1 et tous les 

codes du bâtiment locaux. Au Canada, CAN/

CGA B149 codes d'installation. Une mauvaise 

ventilation de cet appareil peut entraîner des 

niveaux excessifs de monoxyde de carbone qui 

peut entraîner de graves blessures ou la mort!

     The boiler vent collar must be fastened directly to 

an unobstructed vent pipe with rustproof sheet metal 

screws no longer than 1/2” (13mm) and located to 

prevent interference with the inducer damper.

     Do not weld the vent pipe to the boiler collar. The 

weight of the stack must not rest on the boiler. The 

boiler top must be easily removable for normal boiler 

service and inspection.

 

IMPORTANT 

 

Only JVH (induced draft) models may be side-wall 

vented per Section 3D without the addition of a 

properly sized and installed power venter.

 

 JVS must be connected only using Category Type 

I methods and materials per Section 3C.  JVH may 

be connected per Category I or III (See Section 3D) 

methods and materials. See fuel gas code for more 

information regarding your venting application.

IMPORTANT

  

Seulement JVH (induits projet) modèles peut être 

paroi ventilé par chapitre 3D sans l'addition de la 

bonne taille et de puissance installée venter. JVS 

doivent être connectés uniquement en utilisant 

Type de catégorie I méthodes et matériaux par 

Section 3C. JVH peut être connecté par catégorie 

I ou III (voir section 3D) Les méthodes et les 

matériaux. Voir gaz combustible code pour plus 

d'informations concernant votre application 

d'aération.

     Avoid terminating boiler vents near air conditioning 

or air supply fans. The fans can pick up exhaust 

flue products from the boiler and return them to the 

building, creating a possible health hazard.

Avoid oversized vent pipe or extremely long runs 

WALL OR

PARAPET

CHIMNEY

CHIMNEY

RIDGE

WALL OR

PARAPET

CHIMNEY

CHIMNEY

RIDGE

10 (3.0) OR 

LESS

Figure 4. Vertical Vent Termination.

2 (0.6) MIN.

3 (0.9)

MIN.

10 (3.0)

OR LESS

2 (0.6)

MIN.

3 (0.9)

MIN.

3 (0.9)

MIN.

3 (0.9)

MIN.

2 (0.6)

MIN.

10 (3.0)

MORE THAN 10

(3.0)

MORE THAN 10

(3.0)

NOTE: NO HEIGHT 

ABOVE PARAPET

REQUIRED WHEN

FROM WALLS OR

PARAPET IS MORE 

THAN 10 FT. (3.0m)

TERMINATION 

10 FT. (3.0m)

OR LESS FROM RIDGE,

WALL OR PARAPET

Dimensions in feet (m).

Summary of Contents for Mini-Therm JVH

Page 1: ...your gas supplier from a nearby phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified i...

Page 2: ...ections 4A Gas Supply and Piping 13 4B Special Precautions for LP 15 SECTION 5 Water Connections 5A Water Piping 15 5B By pass Piping 17 5C Adjusting the bypass 17 5D Alternate Auto Bypass Operation 1...

Page 3: ...ay void the warranty If field conditions require modifications consult the factory representative before initiating such modifications ATTENTION L eau chaude chaudi re doit tre install en conformit av...

Page 4: ...or 0 5 000 Propane H 2 001 5 000 Natural I 5 001 8 000 Natural and Propane J 8 001 10 000 Natural and Propane 11th Character Country U USA Canada 12th Character Revision 2 Second Revision 1C Heater I...

Page 5: ...of the boiler and the closet door when it is closed see Figure 1 2C Flooring JVS model boilers can only be installed on noncombustible flooring JVH model boilers are designed and certified for install...

Page 6: ...nnection Gas Connection in mm in mm in mm 50 75 100 125 160 225 13 3 8 13 3 8 16 7 8 16 7 8 20 3 8 25 5 8 340 340 429 429 518 651 3 1 8 2 1 4 5 3 4 5 1 2 7 1 4 10 79 57 146 140 184 254 2 7 8 2 2 7 8 2...

Page 7: ...4 1 2 75 13 3 8 340 27 3 4 710 24 1 8 610 21 3 4 550 27 1 2 700 5 13 1 1 4 1 2 100 16 7 8 430 28 3 4 730 24 1 8 610 22 3 4 580 27 1 2 700 5 13 1 1 4 1 2 125 16 7 8 430 28 3 4 730 23 5 8 600 22 3 4 58...

Page 8: ...long as the minimum clearances are observed See Table 2JVH and Figure 1JVH for clearances required for the Mini Therm JVH See Table 2JVS and Figure 1JVS for clearances required for the Mini Therm JVS...

Page 9: ...f a blower is necessary to provide adequate combustion air to the boiler a suitable switch or equivalent must Figure 2 Chimney Venting Figure 3 Vertical Venting CHIMNEY LINER THIMBLE VENT SYSTEM BOILE...

Page 10: ...ocated to prevent interference with the inducer damper Do not weld the vent pipe to the boiler collar The weight of the stack must not rest on the boiler The boiler top must be easily removable for no...

Page 11: ...to nationally recognized standards see National Building Code or ANSI NFPA 211 4 The boiler must not be connected to a fireplace wood stove or other solid fuel burning equipment 5 When the boiler and...

Page 12: ...oduct High Temperature RTV Dow Corning Trade Mate 2 51mm wide Aluminum foil tape adhesively backed Venture Product 3243 2 51mm wide Aluminum foil tape adhesively backed 3M Product 433 Vent Sealing Mat...

Page 13: ...spect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction leakage corrosion or other deficiencies which could cause an unsafe condition Section 4...

Page 14: ...are not followed Attention Vous endommagerez la soupape de gaz si vous ne respectez pas les proc dures suivantes 3 Use the figures in Table 7 to size the gas inlet piping from the gas meter to the he...

Page 15: ...ng of the boiler 6 Disconnect the boiler and its individual shutoff valve from the gas supply system during pressure testing of the system at pressures higher than 1 2 pounds per square inch psi 3 45...

Page 16: ...System Primary Secondary Multi Zone Valve System Low Temperature Installation JV JV JV JV JV JV Primary Secondary Multi Zone Valve System KEY PUMP CHECK VALVE VALVE ZONE VALVE UNION AUTO AIR BLEEDER...

Page 17: ...nd snow melt systems 5C Adjusting the bypass Refer to Figure 10 Provide a means of measuring temperature on the inlet pipe to the boiler such as using a strap on or infrared thermometer Starting with...

Page 18: ...rculator and or primary secondary piping are required Consult factory 1 Chart is based on 30 F 17 C maximum temperature rise 2 Calculations are based on Type L copper tubing with one zone valve and ei...

Page 19: ...Valve Pump From System To System Tempering Valve with System Loop and Boiler Loop Pump JV Pump Isolation Valve Isolation Valve Tempering Valve Pump From System To System Primary Secondary System Loop...

Page 20: ...ollow the schematic in Figures 10A and 10B Remove the wire nut from the two sets of wires and connect the hot lead from the 115V power supply and the neutral lead to the white wires 4 Attach the leads...

Page 21: ...UNLESS VENT DAMPER IS TO BE INSTALLED LA CHAUDI RE NE FONCTIONNERA PAS SANS LE VOLET MOTORIS AUTOMATIQUE LE F AISCEAU DE C BLES DU VOLET MOTORIS DOIT TRE INS R DANS LA PRISE DU VOLET MOTORIS AU CANADA...

Page 22: ...az Switch Limiteur Gas Valve HW VR8304 Air Puls Voir Manuel Prise De Ventilation See Doc 1077 Power Venter Receptacle High Limit Limite Sup rieure Veilleuse Electrode Sensor with Spark Pilot Burner TH...

Page 23: ...OL FAN PROVING ROLLOUT SW GAS VALVE R 2 4 GND R BL R N JVH BK TEMP CONTROL BOILER PUMP TRANSFORMER 110V 110 VAC FUSE 1 BR INDUCER FAN TEMP CONTROL CONTROL RLY CONTROL RLY 24V 3 1 TEMP CONTROL HI LIMIT...

Page 24: ...LAARS Heating Systems Page 24 COM HEAT Figure 11 Multiple Zone Wiring Wiring with Taco Zone Valves Wiring with Honeywell Zone Valves Wiring with Multiple Zone Pumps COM HEAT COM HEAT...

Page 25: ...re falls below the wall thermostat setting the cycle will repeat Section 7 7A Filling the System It is crucial to the efficient operation of the system that all air be removed from the circuit For thi...

Page 26: ...LAARS Heating Systems Page 26 8C Operating Instructions Mini Therm JVH...

Page 27: ...Mini Therm JV Page 27 8D Operating Instructions Mini Therm JVS...

Page 28: ...ollowing data are used to calculate the target setpoint from the outdoor temperature 1 The heating curve or reset ratio RR is set by the potentiometer with a range of 0 4 to 3 6 2 The room temperature...

Page 29: ...heat exchanger is caused by incomplete combustion and is a sign of venting and or combustion air problems The heat Section 9 9A Maintenance 1 Lubricate the water circulating pump per the instructions...

Page 30: ...e terminal board Turn the wall thermostat high enough to call for heat If the meter fails to register 24 volts the thermostat or its circuit may be defective 5 Place the second lead on the purple wire...

Page 31: ...Boiler pounding or knocking Too low water flow through boiler Check temperature rise between inlet and outlet boiler piping 15 F 8 C to 25 F 14 C temperature rise is recommended If temperature rise is...

Page 32: ...UNPLUG IGNITER MEASURE VOLTAGE AT TWO BOTTOM TERMINAL OF SV9501 SV9601 24 VAC NOMINAL YES YES YES YES YES NO NO NO YES NO NO NO Troubleshooting Honeywell SV9501 SV9601 Hot Surface Pilot System JVH on...

Page 33: ...diation Isolation Valve Used to isolate the boiler from the circuit It minimizes the amount of water drained from the system Primary Secondary Piping Two or more interconnecting circulating loops each...

Page 34: ...00 Outdoor Sensor not shown E2347400 E2347400 E2347400 E2347400 E2347400 E2347400 Water System 14 Heat Exchanger R0402007 R0402008 R0402009 R0402010 R0402011 R0402012 15 Gauge Temperature Pressure A20...

Page 35: ...Page 31 ITEMS14 39 AND INSULA TION NOT SHOWN left side right side Figure 14A JVH Parts Identification 25 26 22 25 16 15 27 35 33 38 32 32 17 14 19 20 34 3 28 1 2 6 5 9 23 24 37 36 29 10 31 18A 18B 4 1...

Page 36: ...400 E2347400 E2347400 E2347400 E2347400 Water System 11 Heat Exchanger R0402001 R0402002 R0402003 R0402004 R0402005 R0402006 12 Pressure Relief Valve 30PSI R0061400 R0061400 R0061400 R0061400 R0061400...

Page 37: ...Page 37 Mini Therm JVS on left side Figure 14B JVS Parts Identification 19 17 18 20 7 8 5 22 23 2 24 26 13A 13B 3 1 4 29 14 11 12 25 28 26 21 16 15 9 6 27...

Page 38: ...stomer Service Service Advisors 20IndustrialWay Rochester NH03867 603 335 6300 Fax603 335 3355 ApplicationsEngineering 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130...

Reviews: