Mighty Stack

Page 3

SECTION 1.

General Information

In the Commonwealth of Massachusetts, this 

appliance must be installed by a licensed plumber or 

gas fitter.

1.1  Introduction

This manual provides information necessary 

for the installation, operation, and maintenance of 

Laars Heating Systems’ Mighty Stack copper tube 

appliances, sizes 199-399 MBTU/hr. Please read 

carefully before installation.

All application and installation procedures 

should be reviewed completely before proceeding with 

the installation. Consult the Laars Heating Systems 

factory, or local factory representative, with any issues 

or questions regarding this equipment. Experience 

has shown that most operating issues are caused by 

improper installation.

The Mighty Stack appliance is protected against 

over pressurization. A pressure relief valve is fitted to 

the outlet header, at the water outlet of the boiler, and 

another near the top of the tank.

IMPORTANT:

 The inlet gas pressure to the appliance 

must not exceed 13 in. w.c. (3.2 kPa).

All installations must be made in accordance with:

1) In the U.S., the " National Fuel Gas Code "ANSI 

Z223.1/NFPA54, Latest Edition and all applicable 

local codes as required by the Authorities Having 

Jurisdiction (AHJ), or 

2) In Canada, the "Natural Gas and Propane 

Installation Code", CSA B149.1, latest edition and all 

applicable local codes as required by the AHJ. 

All electrical wiring is to be done in accordance with:

1). In the U.S., the "National Electrical Code" (NEC), 

ANSI/NFPA 70, latest Edition and all applicable local 

codes as required by the AHJ, or

2). In Canada, the “Canadian Electrical Code - Part 

1”, CSA STD. C22.1 and all applicable local codes as 

required by the AHJ. 

This appliance must be electrically grounded in 

accordance with the applicable codes and standards 

referenced above.

 WARNING

To minimize the risk of electric shock, fire or other 

hazards which could result in property damage, 

injury, or death. The Mighty Stack hydronic, 

water heater or water heater 

must

 be installed in 

accordance with the procedures detailed in this 

manual, or the Laars Heating Systems warranty 

may be voided. The installation must conform to 

the requirements of the local jurisdiction having 

authority, and, in the United States, to the latest 

edition of the National Fuel Gas Code, ANSI 

Z223.1/NFPA54. In Canada, the installation must 

conform to the latest edition of the Natural Gas 

and Propane Installation Code, CSA B149.1 and/

or applicable local codes. Where required by 

the authority having jurisdiction, the installation 

of Mighty Stack appliances must conform to the 

Standard for Controls and Safety Devices for 

Automatically Fired Water heaters, ANSI/ASME 

CSD-1. Any modifications to the water heater, its 

gas controls, or wiring may void the warranty. If field 

conditions require modifications, consult the factory 

representative before initiating such modifications.

 AVERTISSEMENT

Afin de réduire au minimum les risques de 

commotion électrique, de feu ou d’autre nature, 

qui pourraient causer des dommages matériels, 

des blessures ou des accidents mortels, les 

chaudières à eau chaude ou les chauffe-eau Mighty 

Stack 

doivent 

être installés conformément aux 

directives détaillées contenues dans ce manuel, 

à défaut de quoi la garantie fournie par Laars 

Heating Systems serait annulée. L’installation doit 

être conforme aux exigences de la réglementation 

locale en vigueur et, aux États-Unis, à l’édition 

la plus récente du Natural Fuel Gas Code (Code 

pour le gaz combustible naturel) ANSI Z223.1/

NFPA54. Au Canada, l’installation doit respecter 

les exigences de la plus récente édition du Code 

d’installation du gaz naturel et du propane CSA 

B149.1, et/ou des codes locaux de construction en 

vigueur. Lorsque la réglementation locale l’exige, 

l’installation des appareils électroménagers Mighty 

Stack doit respecter les exigences du Standard 

for Controls and Safety Devices for Automatically 

Fired Water heaters (Code pour les équipements 

de commande et de sécurité des chaudières à 

combustion automatique), ANSI/ASME CSD-

1. Toute modification apportée à la chaudière, 

aux régulateurs de gaz ou au câblage, peut 

compromettre la garantie. Si certaines conditions 

particulières rendent des adaptations nécessaires, 

consulter un représentant du fabricant avant 

d’entreprendre ces modifications.

Summary of Contents for Mighty Stack MS-080

Page 1: ...r death Improper installation and or operation will void the warranty For indoor installations as an additional measure of safety Laars strongly recommends installation of suitable Carbon Monoxide det...

Page 2: ...16 4 4 Combined Water Heating potable and Space Heating 16 4 5 Freeze Protection 16 SECTION 5 Electrical Connections 5 1 Main Power 18 5 2 Field Wiring 18 SECTION 6 Operating Instructions 6 1 Filling...

Page 3: ...in this manual or the Laars Heating Systems warranty may be voided The installation must conform to the requirements of the local jurisdiction having authority and in the United States to the latest e...

Page 4: ...r concealed 1 4 Dimensions See Figure 1 1 5 Locating the Appliance The appliance should be located to provide clearances on all sides for maintenance and inspection It should not be located in an area...

Page 5: ...mensional Data Air and vent connections may be on top or back of the Mighty Stack and are field convertible Size A B C D in cm in cm in cm in cm 199 33 0 84 4 10 5 13 8 75 22 300 39 0 99 4 10 6 15 15...

Page 6: ...m 199 5 13 4 10 4 10 50 15 3 CA003101 CA003201 300 6 15 5 13 4 10 50 15 3 CA003102 CA003201 399 7 18 6 15 6 15 50 15 3 CA003103 CA003202 Table 1 Horizontal Vent Combustion Air Parameters Appliance Su...

Page 7: ...communicating with the outdoors or when communicating to the outdoors through vertical ducts each opening shall have a minimum free area of 1 square inch per 4000 Btu hr 5 5 square cm kW of total inp...

Page 8: ...dered Category III In the U S the National Fuel Gas Code ANSI Z223 1 or in Canada the Natural Gas and Propane Installation Code CSA B149 1 defines a Category I vent system and includes rules and table...

Page 9: ...living spaces common venting should not be applied and appliances should each be vented separately 2 2 4 Category III Vent When the Mighty Stack is vented with horizontal discharge it must be installe...

Page 10: ...non mechanical air supply Direct Vent Only 12 inches 30 cm inlet to building or the combustion air inlet Other Than Direct Vent 4 feet 1 2 m below or 36 inches 91 cm to any other appliance to side of...

Page 11: ...ith alarm and battery back up may be installed on the next adjacent floor level b In the event that the requirements of this subdivision cannot be met at the time of completion of installation the own...

Page 12: ...0 feet 3 0m and high enough above the roof line to prevent blockage from snow When the combustion air is taken from the roof the combustion air must terminate at least 12 30cm below the vent terminal...

Page 13: ...ventilateurs d t Fermer les registres des chemin es 4 Mettre l appareil inspect en marche Suivre les instructions d allumage R egler le thermostat de fa on continue 5 Faire fonctionner le br leur prin...

Page 14: ...Laars Heating Systems Page 14 Figure 4 Venting...

Page 15: ...upply is below sea level values 2 The maximum inlet gas pressure must not exceed 13 w c 3 2kPa The minimum inlet gas pressure is 5 in w c 1 2 kPa 3 Refer to Table 7 size supply 4 Run gas supply line i...

Page 16: ...high enough to prevent scaling but low enough to prevent tube erosion For extremely soft or hard water cupro nickel tubes are available Contact a Laars representative if you have questions or concerns...

Page 17: ...Mighty Stack Page 17 Figure 4 Suggested Plumbing Figure 5 Suggested Plumbing Three Units in first out last...

Page 18: ...ode Canadien de l lectricit 1 re partie Canadian Electrical Code Part 1 CSA C22 1 au Canada N utilisez pas les tuyauteries d eau ou de gaz pour mettre la terre les pi ces m talliques de la chaudi re d...

Page 19: ...Mighty Stack Page 19 Figure 7 Wiring Diagram ON OFF Water Heater...

Page 20: ...tches this 24V from the input 6 4 Sequence of Operation The pump time delay relay will receive a signal to initiate The pump terminals on the field wiring terminals strip will energize a pump Once the...

Page 21: ...mproper setup is not covered by the limited warranty 1 Using this manual make sure the installation is complete and fully in compliance with the instructions 2 Determine that the appliance and system...

Page 22: ...justing the air shutter Contact the Technical Services Department at number shown on back page The amount of derate will vary depending on heating value of the fuel and the elevation at the installati...

Page 23: ...functioning It is strongly recommended that a qualified service technician inspect the basic items listed below every year a Ignition control b Ignitor c Water temperature control d Automatic gas val...

Page 24: ...emove the mounting screws and remove the transformer Replace transformer in the reverse order 7 2 8 Flow Switch The Mighty Stack uses a paddle type flow switch to ensure that the unit has water flow b...

Page 25: ...ion of soot or corrosion on the outside of the heat exchanger can be easily removed Use a wire brush to remove loose soot and scale from the heat exchanger 9 NOTE While the heat exchanger is out of th...

Page 26: ...gnition If the gas supply pressure is proper and the gas valves are functioning properly then burners should be inspected There should be no distortion or perforations in the burners outside of the ac...

Page 27: ...utter Blower 2C5000 2C5000 2C5000 20 Assembly Filter Housing 40L3900 40L3900 40L3900 Assembly Removeable Filter 40L3800 40L3800 40L3800 Media Filter R2073200 R2073200 R2073200 21 Hose Duct Flexible 4...

Page 28: ...r Copper R2C4100 R3C4100 R4C4100 Assembly Tube Heat Exchanger Cupro Nickel R2C4120 R3C4120 R4C4120 2 Header Inlet Outlet 2F4122 2F4122 2F4122 3 Header Return 2C4103 2C4103 2C4103 4 Chamber Header Heat...

Page 29: ...0 E2056300 11 Block Terminal Double Row 16 Position E2327500 E2327500 E2327500 12 Jumper Terminal Block E0102000 E0102000 E0102000 13 Label Terminal Control Contacts H2339100 H2339100 H2339100 14 Harn...

Page 30: ...Laars Heating Systems Page 30 Figure 9 Combustion Chamber Components...

Page 31: ...Mighty Stack Page 31 Figure 10 Jacket Components...

Page 32: ...Laars Heating Systems Page 32 Figure 11 Heat Exchanger Components...

Page 33: ...Mighty Stack Page 33 Figure 12 Gas Train Components...

Page 34: ...Laars Heating Systems Page 34 Figure 13 Control Panel Components...

Page 35: ...Mighty Stack Page 35 Figure 14 Pump Assembly Components...

Page 36: ...603 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars com Litho in U S A Laars Heating Systems 1110 Document 2155 Dimensions and sp...

Reviews: