background image

Mighty Max Hydronic Boiler

Page 19

Use a single, inclined manometer or digital

manometer with a 4.0 inch water column range. Install
shutoff valves at the gas orifice (regulator outlet) tap
(red), at the venturi inlet tap (blue) and at the venturi
throat tap (yellow). After installing the shutoff valves,
be certain they are closed.

1.

With the heater off, connect the positive side of
the manometer to the shutoff valve on the
venturi inlet tap (blue). Open the shutoff valve.

2.

Loosen the nut on the blower damper to allow
for adjustment. Turn the boiler on so that the
blower is running and the boiler is not firing. In
this unfired condition, adjust the damper until
the venturi inlet pressure (blue tap) is 1.2 inches
water column.

3.

Approximately 40 seconds after the blower starts
the gas valves will open. The boiler is now
firing. If the heater is not running, check all
manual gas valves and heater safety devices.
Ensure proper gas supply pressures according to
the table in Section 2.

4.

Now that the boiler is firing, use the blower
damper to readjust the venturi inlet pressure
according to the installation’s altitude in Table
10 (+1.6" w.c. at sea level).

Elevation

Venturi Inlet

Gas

Throat

Ft.

Pressure

Pressure

Differential

(Blue Tap)

Offset

Pressure

“WC H

2

0”

“WC H

2

0”

“WC H

2

0”

SEA LEVEL

+1.6

+0.4

+2.6

1000

+1.5

+0.4

+2.5

2000

+1.5

+0.4

+2.4

3000

+1.4

+0.4

+2.3

4000

+1.4

+0.3

+2.2

5000

+1.3

+0.3

+2.2

6000

+1.3

+0.3

+2.1

7000

+1.2

+0.3

+2.0

8000

+1.2

+0.3

+1.9

9000

+1.1

+0.3

+1.9

10000

+1.1

+0.3

+1.8

Table 10. Venturi Pressure Settings.

5.

Leaving the positive side of the manometer
connected to the venturi inlet tap (blue), connect
the negative side of the manometer to the shutoff
valve on the gas orifice tap (red). Open the
shutoff valve to take a pressure reading. This
reading is called the gas pressure offset. Using
the regulator only, adjust the gas pressure offset
according to the installation's altitude in Table 5
(+0.4" w.c. at sea level). REPLACE THE
REGULATOR CAP BEFORE TAKING GAS
PRESSURE READINGS. Turn the regulator
screw clockwise to decrease the gas pressure
offset, turn the regulator screw counter-
clockwise to increase the offset.

6.

Using the toggle switch, turn the heater off. Turn
the heater back on and check the gas pressure
offset after the heater has fired. If the gas offset
pressure is not according to Table 10, adjust the
regulator as needed.

7.

While the heater is still running, close the
shutoff valve on the gas orifice tap (red), then
remove the manometer hose from the shutoff
valve. Connect the negative side of the
manometer to the shutoff valve on the venturi
throat tap (yellow). This reading is called the
venturi throat differential pressure and should
appear according to altitude in Table 10 (+2.6"
w.c. at sea level). If it does not appear according
to Table 10, contact a qualified service
technician.

“Low” Side of

Manometer

“High” Side of

Manometer

Venturi Inlet

Tap (Blue)

Venturi Throat

Tap (Yellow)

Gas Orifice

Tap (Red)

Figure 15. Measurement of Venturi Throat Pressure
Differential.

After setting all pressures, turn the heater off and

replace each shutoff valve with the factory installed
threaded plugs. The venturi has now been adjusted for
proper operation.

3D. To Start Up System

(See Section 3A for Startup Requirements)

1.

Be certain the system pump is running.

2.

Set the thermostat or aquastat to its lowest
setting.

3.

Turn off electric power to the appliance.

4.

Remove the control access panel.

5.

Turn off the manual gas valve.

6.

Wait five (5) minutes to clear out any gas, then
smell for gas, including near the floor. Be sure to
smell next to the floor because some gas is
heavier than air and will settle on the floor.

Summary of Contents for Mighty Max HH1000M

Page 1: ...e technician qualified in hot water boiler installation and maintenance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property...

Page 2: ...tion Air 15 2M 3 Conversion for Ducted Combustion Air 15 2M 4 Combustion Air Piping 16 2N Electrical Wiring 16 SECTION 3 Operating Instructions 3A Start Up Requirements 16 3B Hi Limit checkout 18 3C V...

Page 3: ...ion and maintenance instruction for the Mighty Max hydronic boiler Model HH sizes 320M 400M 520M 625M 775M and 1000M Review all application and installation procedures completely before proceeding wit...

Page 4: ...lated or otherwise protected from any source of corrosive chemical fumes such as trichlorethylene perchlorethylene chlorine etc Install the boiler so that the gas ignition system components are protec...

Page 5: ...nnected to the common venting system properly vents when tested as outlined above return door windows exhaust fans fireplace dampers and any other gas burning appliances to their previous condition of...

Page 6: ...au National Fuel Gas Code ANSI Z223 1 NFPA 54 et ou aux codes d installation CAN CGA B149 Si la grosseur d une section du syst me devrait tre modifi ppour respecter les valeurs minimales des tableaux...

Page 7: ...n Used On Canadian Unit or U S Unit Requiring CSD 1 Code Automatic Main Gas Valves NOTE The boiler and all other gas appliances sharing the boiler gas supply line must be firing at maximum capacity to...

Page 8: ...h the boiler expressed in ft of H2O Shaded area is the recommended flow and temperature rise Minimum inlet temperature is 105 F Table 5 Temperature Rise TEMPERATURE RISE IN DEGREES F C MODEL 10 F 6 C...

Page 9: ...he heater which will be used to supply potable water to any heating system or components previously used with a nonpotable water heating system Do not add boiler treatment or any chemicals to the heat...

Page 10: ...diation units for one 1 hour 10 Recheck the water level in the expansion tank If the water level exceeds 1 4 of the volume of the expansion tank open the tank drainer and drain to that level 11 Shut d...

Page 11: ...nting and Combustion Air Options Vertical Venting Category I Combustion Air In Through Louvers Side View Wall NOTE All views are shown from rear of heater Horizontal Intake Terminal Detail Combustion...

Page 12: ...er Jacket Blank Plate On Flue Collector Blank Plate On Boiler Jacket Top Panel 1 Removal of Blank Plate and Adapter Plate From Boiler 3 Blank Plate Placement Over Stack Top Opening Blank Plate Flue Co...

Page 13: ...al vents must be installed in accordance with the special code requirements for Category I Fan Assisted Appliances These requirements can be found in the latest edition of ANSI Z223 1 NFPA 54 Appendix...

Page 14: ...2m horizontally from or 3 feet 0 9m above such openings 4 Locate the vent terminal so that it cannot be blocked by snow The National Fuel Gas code requires that it be at least 12 inches 305mm above g...

Page 15: ...of the Laars side wall terminal Locate the terminal within 10 feet 3 0m of the boiler vent exhaust terminal but no closer than 3 feet 0 9m centerline distance Do not locate the air inlet terminal near...

Page 16: ...in the wiring diagram supplied with the boiler see Figure 12 3 Electrically interlock the pump and boiler so the boiler cannot come on unless the pump is running 4 Connect all field installed devices...

Page 17: ...rvicing controls wiring errors can cause improper and dangerous operation Verify proper operation after operation servicing ATTENTION Au moment de l entretien des commandes tiquetez tous les fils avan...

Page 18: ...back up to its original setting and the hi limit is reset 3C Venturi and Gas Pressure Regulator System 3C 1 Overall Operation The gas control system of the Mighty Max boiler is similar to that of a ca...

Page 19: ...ake a pressure reading This reading is called the gas pressure offset Using the regulator only adjust the gas pressure offset according to the installation s altitude in Table 5 0 4 w c at sea level R...

Page 20: ...sures is far more important than their gauge value relative to the room The gas pressure offset and the gas orifice pressure differential are especially important concepts The following section descri...

Page 21: ...rence in pressure between the venturi inlet tap and the outlet of the gas regulator see Figure 17 This measurement is taken by connecting the positive side of the manometer to the venturi inlet tap an...

Page 22: ...wc at sea level Use the blower shutter to adjust the gas orifice differential 6 By adjusting the gas orifice differential the gas offset pressure will change Therefore you must repeat steps 3 5 until...

Page 23: ...vicing the heat exchanger 1 Disconnect the 120 Vac electrical supply to the heater 2 Turn off the gas supply by closing the manual gas valve on the heater 3 Disconnect and remove the wires and conduit...

Page 24: ...may need to be cleaned daily Failure to do so could result in lower heat output and potential unsafe operation SECTION 5 Troubleshooting 5A Sequence of Operation To troubleshoot the heater properly y...

Page 25: ...Mighty Max Hydronic Boiler Page 25 Figure 20 Troubleshooting Chart...

Page 26: ...irculating water and the foregoing items check out okay the trouble may be in the boiler control system IMPORTANT Disconnect power to the boiler before removing or replacing any component or wire conn...

Page 27: ...mbly 320M 20254901 400M 20254902 Item Description Part Number 520M 625M 20260100 U S 20260101 Canada 775M 20260200 U S 20260201 Canada 1000M 20265600 U S 20265601 Canada Gas Valve 320M 425M V2003900 5...

Page 28: ...Page 28 LAARS HEATING SYSTEMS Front View Right Side View 36 10 8 9 5 20 7 12 13 11 3 6 21 14 15 38 4 1 2...

Page 29: ...Mighty Max Hydronic Boiler Page 29 Front View Rear View Right Side View Left Side View 31 32 17 30 23 26 27 28 25 37 25 33 16 18 35 29 19 34 39...

Page 30: ...Left 20152900 30 Panel Access 320M 20157401 400M 20157402 520M 20157403 625M 20157404 775M 20157405 1000M 20157406 Item Description Part Number 31 Panel Back 320M 20157201 400M 20157202 520M 20157203...

Page 31: ...Mighty Max Hydronic Boiler Page 31...

Page 32: ...CA 93021 805 529 2000 FAX 805 529 5934 20 Industrial Way Rochester NH 03867 603 335 6300 FAX 603 335 3355 480 S Service Road West Oakville Ontario Canada L6K 2H4 905 844 8233 FAX 905 844 2635 www laar...

Reviews: