background image

Page 18

LAARS HEATING SYSTEMS

pre-ignition purge, while the fan clears the
combustion chamber, the igniter is turned
on. The igniter takes about 25 seconds to
heat up. You can see a glow through the
view port (see Figure 13).

NOTE: The manual gas valve must be ON for the

burner to ignite. This valve is turned ON as follows:

Size 775/1000

Valve is ON when handle is
parallel to as pipe.

Sizes 320/400

Turn counterclockwise 520/625
to ON.

c.

When the igniter is hot, the ignition control
turns on the gas valve and the burner
ignites. You can see the burner flame
through the view port (see Figure 13).

d.

The boiler operates until the aquastat
senses that the water is hot enough, and the
burner shuts off. The combustion fan runs
for about one minute to blow all
combustion products out of the boiler.

If the igniter fails to ignite the burner in step 3

(for example, if there is air in the gas line), the
ignition control shuts off the gas valve after a few
seconds of operation. The purge and ignition sequence
is automatically repeated. If there is no ignition in
three tries, the ignition control “locks out” until the
problem is corrected. Contact a qualified service
technician.

3B. Hi-Limit Checkout

After running the boiler for a long enough period

to bring the water temperature within the range of the
hi-limit, slowly back off the high limit setting until the
boiler shuts off. The main burners should re-ignite
when the hi-limit is turned back up to its original
setting and the hi-limit is reset.

3C. Venturi and Gas Pressure Regulator

System

3C-1. Overall Operation

The gas control system of the Mighty Max boiler

is similar to that of a carburetor of a gasoline engine: a
venturi pulls the gas into the combustion air stream
(see Figure 14). In this system, changes in combustion
air flow automatically change the gas flow.

Overall

Operation

Figure 14. Typical Venturi System.

Air

Equalizer

Tube

Negative

Pressure Regulator

Gas

Gas

Orifice

Air/Gas

Mixture

Junction

Box

Front View of Boiler

NOTE: Sight glass
location may vary.

Figure 13. Periodic Flame Observation.

Igniter

Sight Glass

For Flame Observation

The flow of air through the venturi creates a

pressure difference. At the narrowest point of the
venturi, the throat, high velocity creates a low
pressure condition which pulls gas in through an
orifice.

For a correct gas/air ratio, the gas pressure must

be the same as the air pressure, but with a slight
negative offset. A special gas regulator (called a
“negative pressure regulator”) which has an equalizer
tube connected to the venturi inlet, maintains the
required gas pressure.

When the system is operating, a combustion fan

forces air into the venturi, creating pressure at the
inlet. The gas regulator sets gas pressure, and gas is
pulled through the orifice. The sizes of the venturi
throat and gas orifice are factory set to provide the
correct air/gas ratio.

3C-2. Venturi Adjustment

The field checkout involves measuring gas and

venturi pressures, and observing the flame through the
sight glass. If necessary, the gas input rate can be
measured by timing the gas meter.

Summary of Contents for Mighty Max HH1000M

Page 1: ...e technician qualified in hot water boiler installation and maintenance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property...

Page 2: ...tion Air 15 2M 3 Conversion for Ducted Combustion Air 15 2M 4 Combustion Air Piping 16 2N Electrical Wiring 16 SECTION 3 Operating Instructions 3A Start Up Requirements 16 3B Hi Limit checkout 18 3C V...

Page 3: ...ion and maintenance instruction for the Mighty Max hydronic boiler Model HH sizes 320M 400M 520M 625M 775M and 1000M Review all application and installation procedures completely before proceeding wit...

Page 4: ...lated or otherwise protected from any source of corrosive chemical fumes such as trichlorethylene perchlorethylene chlorine etc Install the boiler so that the gas ignition system components are protec...

Page 5: ...nnected to the common venting system properly vents when tested as outlined above return door windows exhaust fans fireplace dampers and any other gas burning appliances to their previous condition of...

Page 6: ...au National Fuel Gas Code ANSI Z223 1 NFPA 54 et ou aux codes d installation CAN CGA B149 Si la grosseur d une section du syst me devrait tre modifi ppour respecter les valeurs minimales des tableaux...

Page 7: ...n Used On Canadian Unit or U S Unit Requiring CSD 1 Code Automatic Main Gas Valves NOTE The boiler and all other gas appliances sharing the boiler gas supply line must be firing at maximum capacity to...

Page 8: ...h the boiler expressed in ft of H2O Shaded area is the recommended flow and temperature rise Minimum inlet temperature is 105 F Table 5 Temperature Rise TEMPERATURE RISE IN DEGREES F C MODEL 10 F 6 C...

Page 9: ...he heater which will be used to supply potable water to any heating system or components previously used with a nonpotable water heating system Do not add boiler treatment or any chemicals to the heat...

Page 10: ...diation units for one 1 hour 10 Recheck the water level in the expansion tank If the water level exceeds 1 4 of the volume of the expansion tank open the tank drainer and drain to that level 11 Shut d...

Page 11: ...nting and Combustion Air Options Vertical Venting Category I Combustion Air In Through Louvers Side View Wall NOTE All views are shown from rear of heater Horizontal Intake Terminal Detail Combustion...

Page 12: ...er Jacket Blank Plate On Flue Collector Blank Plate On Boiler Jacket Top Panel 1 Removal of Blank Plate and Adapter Plate From Boiler 3 Blank Plate Placement Over Stack Top Opening Blank Plate Flue Co...

Page 13: ...al vents must be installed in accordance with the special code requirements for Category I Fan Assisted Appliances These requirements can be found in the latest edition of ANSI Z223 1 NFPA 54 Appendix...

Page 14: ...2m horizontally from or 3 feet 0 9m above such openings 4 Locate the vent terminal so that it cannot be blocked by snow The National Fuel Gas code requires that it be at least 12 inches 305mm above g...

Page 15: ...of the Laars side wall terminal Locate the terminal within 10 feet 3 0m of the boiler vent exhaust terminal but no closer than 3 feet 0 9m centerline distance Do not locate the air inlet terminal near...

Page 16: ...in the wiring diagram supplied with the boiler see Figure 12 3 Electrically interlock the pump and boiler so the boiler cannot come on unless the pump is running 4 Connect all field installed devices...

Page 17: ...rvicing controls wiring errors can cause improper and dangerous operation Verify proper operation after operation servicing ATTENTION Au moment de l entretien des commandes tiquetez tous les fils avan...

Page 18: ...back up to its original setting and the hi limit is reset 3C Venturi and Gas Pressure Regulator System 3C 1 Overall Operation The gas control system of the Mighty Max boiler is similar to that of a ca...

Page 19: ...ake a pressure reading This reading is called the gas pressure offset Using the regulator only adjust the gas pressure offset according to the installation s altitude in Table 5 0 4 w c at sea level R...

Page 20: ...sures is far more important than their gauge value relative to the room The gas pressure offset and the gas orifice pressure differential are especially important concepts The following section descri...

Page 21: ...rence in pressure between the venturi inlet tap and the outlet of the gas regulator see Figure 17 This measurement is taken by connecting the positive side of the manometer to the venturi inlet tap an...

Page 22: ...wc at sea level Use the blower shutter to adjust the gas orifice differential 6 By adjusting the gas orifice differential the gas offset pressure will change Therefore you must repeat steps 3 5 until...

Page 23: ...vicing the heat exchanger 1 Disconnect the 120 Vac electrical supply to the heater 2 Turn off the gas supply by closing the manual gas valve on the heater 3 Disconnect and remove the wires and conduit...

Page 24: ...may need to be cleaned daily Failure to do so could result in lower heat output and potential unsafe operation SECTION 5 Troubleshooting 5A Sequence of Operation To troubleshoot the heater properly y...

Page 25: ...Mighty Max Hydronic Boiler Page 25 Figure 20 Troubleshooting Chart...

Page 26: ...irculating water and the foregoing items check out okay the trouble may be in the boiler control system IMPORTANT Disconnect power to the boiler before removing or replacing any component or wire conn...

Page 27: ...mbly 320M 20254901 400M 20254902 Item Description Part Number 520M 625M 20260100 U S 20260101 Canada 775M 20260200 U S 20260201 Canada 1000M 20265600 U S 20265601 Canada Gas Valve 320M 425M V2003900 5...

Page 28: ...Page 28 LAARS HEATING SYSTEMS Front View Right Side View 36 10 8 9 5 20 7 12 13 11 3 6 21 14 15 38 4 1 2...

Page 29: ...Mighty Max Hydronic Boiler Page 29 Front View Rear View Right Side View Left Side View 31 32 17 30 23 26 27 28 25 37 25 33 16 18 35 29 19 34 39...

Page 30: ...Left 20152900 30 Panel Access 320M 20157401 400M 20157402 520M 20157403 625M 20157404 775M 20157405 1000M 20157406 Item Description Part Number 31 Panel Back 320M 20157201 400M 20157202 520M 20157203...

Page 31: ...Mighty Max Hydronic Boiler Page 31...

Page 32: ...CA 93021 805 529 2000 FAX 805 529 5934 20 Industrial Way Rochester NH 03867 603 335 6300 FAX 603 335 3355 480 S Service Road West Oakville Ontario Canada L6K 2H4 905 844 8233 FAX 905 844 2635 www laar...

Reviews: