80
Mascot LX Service Manual
Appendix 1 - SIT Parameter Codes (continued)
App1
cont.
Parameter
Description
Default
P31
Building management system voltage at minimum
2VDC
P32
Building management system voltage at maximum
10VDC
P33
On threshold voltage
1VDC
P34
On hysteresis voltage
0.5VDC
P35
Building management system rate at minimum voltage
20%
P36
Building management system rate at maximum voltage
100%
P37
Building management system temperature setpoint at mini-
mum voltage
70°F
P38
Building management system temperature setpoint at
maximum voltage
180°F
P39
Postcirculation time for central heat pump
30 sec.
P40
Postcirculation time for domestic hot water pump
30 sec.
P41
Postcirculation time for system pump
30 sec.
P42
Summer kick timer for central heat pump
20 sec.
P43
Summer kick timer for domestic hot water pump
20 sec.
P44
Summer kick timer for system pump
20 sec.
P45
Delta T setpoint for central heat pump speed control
20°F
P46
Minimum output voltage for central heat pump output
3.5VDC
P47
Differential maximum fan speed for hot water demand
0 rpm
P48
Differential maximum fan speed for central heat demand
0 rpm
P49
Priority time for central heat over domestic hot water
0 min.
P50
Priority time for domestic hot water over central heat
50 min.
P51
Hot water tank setpoint
180°F
P52
Stop hot water tank demand offset
0°F
P53
Start hot water tank demand offset
6°F
P54
Block hot water demand offset (Combi units only)
12°F
P55
Unblock hot water demand offset (Combi units only)
20°F
P56
Minimum user setting hot water setpoint
60°F
P57
Maximum user setting hot water setpoint
140°F
Summary of Contents for MASCOT LX
Page 2: ......
Page 6: ...Mascot LX Service Manual iv...
Page 24: ...Mascot LX Service Manual 18...
Page 38: ...32 Mascot LX Service Manual...
Page 76: ...70 Mascot LX Service Manual...
Page 93: ......