Figure 19
– Multiple Intake/Exhaust Terminal Separation Distances
Note:
When installing multiple intake/exhaust terminals on the same wall of a building, the nearest intake
terminal must be at least 5 ft
(1.5 m)
from the nearest exhaust terminal. Spacing requirements are the same for
roof installation.
Concentric Vent Terminal Installation Procedure
WARNING
Improper installation, adjustment, service, or maintenance can cause property damage, personal injury, or death.
Consult a qualified installer, service agency, or the gas supplier for information or assistance.
This concentric terminal must be used only for terminating this water heater.
DO NOT
use this concentric terminal kit
for any other appliance. Using this concentric terminal on other appliances and/or water heaters can result in property
damage, personal injury, or death.
DO NOT
operate this water heater until the installation and assembly of this concentric terminal is complete and the
piping is completed. Failure to complete installation before operation can result in property damage, personal injury, or
death.
Before beginning any installation, be sure the main electrical disconnect switch is in the OFF position. Electrical shock
can cause personal injury or death.
DO NOT
operate this water heater with the rain cap removed or recirculation of combustion products may occur. Water
may also collect inside larger combustion-air pipe and flow to the burner assembly. Failure to follow this warning could
result in product damage, or improper operation, personal injury or death.
CAUTION
DO NOT
use field-supplied couplings to extend pipes. Airflow restriction will occur, and the water heater pressure
switches may cause intermittent problems.