background image

8

The vaporization of propane is affected by several factors:
the sur face area of the container, the liquid level of
propane, temperature surrounding the container, and the
relative humidity.  All of these factors are specific to a site.
Therefore, a degree of experience and judgement is
required to select the proper propane supply.
Although experience is the best guide, the following

recommendations can be used as a starting point.  The
table is based on experience during winter in northern
climates.  If more or less favorable conditions prevail at a
specific site, adjustments can be made on the basis of
experience.

PROPANE GAS SUPPLY SIZING

Recommended Propane Gas Supply

Average Temp ºF

50

40

30

20

10

0    -10

Number of 100lb.

2

2

3

3

3

3       

 

 

3

Gas Cylinders to 
Use Per Heater

*  Cylinders must be manifolded together to allow simultaneous vapor withdrawal from all cylinders.

11

The heater must have the proper gas regulator for the
application.  Use only the L.B. White regulator
originally supplied with the heater.  This regulator
includes a POL fitting incorporating an excess flow
valve.  The excess flow valve is a safety device which
protects against discharge from the propane gas
supply container if the regulator is broken off.  If the
POL fitting is ever replaced, it needs to be replaced
with an L.B. White POL fitting.  Failure to do so can
result in fires, explosions, loss of property, injury or
death.

12. This heater is configured for use for propane gas vapor

withdrawal only.  Do not use the heater in an propane
gas liquid withdrawal system or application.  If you are
in doubt, contact the L.B. White Co., Inc.

13. The heater must be installed so as not to interfere

with or obstruct normal exits, emergency exits, doors
and walkways.

14. Railing, fencing or suitable substitute materials must

be used to keep the heating equipment from any
people using and visiting the structure.

15. The unit shall be located so that rain, ice, or snow

drainage from the structure does not affect equipment
operation.  If the unit is mounted outside, it must be
mounted above any pooled or standing water.  If the
unit is to be located on the ground, a surrounding
trench is recommended to drain any rain, ice or snow
away from the unit.

16. The ground and surrounding terrain must be cleared

of any combustible vegetation and other combustible
materials when the heater is mounted outside.

17.

Eventually, like all electrical/mechanical devices, the
thermostat can fail.  Thermostat failure may result in
an underheating condition.  The thermostat should be
tested to make sure it turns the heater on and off
within a temperature differential of ±3°F.

18. Take time to understand how to operate and maintain

the heater by using this Owner’s Manual.  Make sure
you know how to shut of f the gas supply to the
building and also to the individual heater.  Contact
your fuel gas supplier if you have any questions.

19. Any defects found in performing any of the service or

maintenance procedures must be eliminated and

1.

Locate accessory package with handle and screws. 

2.

Align handle to screws holes in case top.  Install four
screws and tighten securely.

Note: The handle may be relocated to the side of the
top panel for heater stacking during storage.  Do not
stack heaters more than two high.

FIG. 1

HANDLE ASSEMBLY

ALTERNATE
HANDLE HOLES

Summary of Contents for CP155

Page 1: ...Owner s Manual and Instructions Tradesman Construction Heaters ATTENTION ALL USERS This heater has been tested and evaluated by C S A International in accordance with the requirements of Standard ANS...

Page 2: ......

Page 3: ...d to property damage personal injury or loss of life GENERAL HAZARD WARNING Failure to comply with the precautions and instructions provided with this heater can result in Death Serious bodily injury...

Page 4: ...des all options and accessories commonly used on this heater When calling for technical service assistance or for other specific information always have model number configuration number and serial nu...

Page 5: ...NG CONTINUOUS OPERATION Fuel Consumption Per Hour Inlet Gas Supply Pressure Acceptable at the Inlet of the Heater for Purpose of Input Adjustment MAX MIN 10 ft 115 60 1 Heater Specifications Fuel Type...

Page 6: ...olorless and the intensity of its odor can fade under some circumstances If there is an underground leak the movement of gas through the soil can filter the odorant Propane gas odor may differ in inte...

Page 7: ...on 6 For safety this heater is equipped with an auto reset backflash switch and an air proving switch Never operate the heater with any safety device that has been bypassed Do not operate this heater...

Page 8: ...g is performed as follows Check all pipe connections hose connections fittings and adapters upstream of the gas control with approved gas leak detectors In the event a gas leak is detected check the c...

Page 9: ...plication If you are in doubt contact the L B White Co Inc 13 The heater must be installed so as not to interfere with or obstruct normal exits emergency exits doors and walkways 14 Railing fencing or...

Page 10: ...mpound suitable for use with L P gas or natural gas on the threaded connections 2 At the inlet of the regulator is a male nut and stem called a POL assembly Remove the cap from the POL Insert POL stem...

Page 11: ...ion takes place 5 Do not exceed input rating provided on dataplate or manufacturer s recommended burner manifold pressure for size orifice used Ensure that the primary air supply to heater is open and...

Page 12: ...no cost A nominal charge will be applied for wiring diagrams Maintenance Instructions 1 Before cleaning shut off all gas supply valves and disconnect electrical supply 2 The heater should have dirt or...

Page 13: ...nate method for checking the components is to perform a continuity check 5 The air proving switch must not be jumpered If jumpered the ignition control will not allow heater operation Test the air pro...

Page 14: ...mounting bracket s tab is positioned in hole adjacent to mounting screw hole FIG 9 TESTING The switch should be tested annually 1 Remove the switch assembly Holding the switch by its bracket apply a s...

Page 15: ...ENT 1 Remove ignition cable from igniter See Fig 11 FIG 11 2 Holding the igniter at its hex reach in the heater s barrel and remove the igniter s mounting nut See Fig 12 When replacing ensure ignitor...

Page 16: ...the barrel bottom See Fig 18 Guide the bulb down through the hole Handle the replacement thermostat carefully to prevent damage to the capillary and bulb FIG 18 THERMOSTAT IGNITION CONTROL 14 15 1 Re...

Page 17: ...With the heater operating the pressure gauge must read the pressures specified on the dataplate 2 Does the reading at the gas control valve agree with that specified on the dataplate If so then no fu...

Page 18: ...Components should be replaced only after each step has been completed and replacement is suggested in the flow chart Refer to the Servicing sections as necessary to obtain information on disassembly a...

Page 19: ...s Is Thermostat Above Room Temperature Set Thermostat Above Room Temperature Is Thermostat Defective Is 115 Volts Supplied to Heater Power Cord Provide 115 Volt Electrical Supply Check Circuit Breaker...

Page 20: ...air Air Proving Switch One Time Air proving Switch Contacts Are Closed before Fan Motor Starts Pattern Begins 5 Seconds After Condition Is Air Proving Switch Stuck Closed Check Continuity Is Airflow S...

Page 21: ...ive Motor or Capacitor Replace Motor or Capacitor Is Ignition Control Module Sending Proper Voltage to Switch Is Ignition Module Receiving Proper Voltage No No Is Proper Voltage Supplied to Heater Pow...

Page 22: ...gniter High Voltage Lead Connected No Is Ignitor Gap Positioned Properly No Reposition Igniter See Service Instructions No Connect High Voltage Lead Yes A Check High Voltage Lead For Continuity and Ti...

Page 23: ...ermostat Above Room Temperature No Yes Yes Is 115 Volts Supplied to Thermostat Defective On Off Switch Replace Is 115 Volts Supplied to Ignition Control Defective Thermostat Replace No No Yes Is 115 V...

Page 24: ...ied Are the Backflash Switch Contacts Closed Yes Does Gas Solenoid Valve Open Is Proper Voltage Supplied to Gas Valve Defective Wires or Connections If Good Rplace Ignition Control Defective Gas Valve...

Page 25: ...Clean Is High Voltage Lead Connected Refill Tank or Check Regulator No No Clear Obstructions to Inlet Maintain Clearances Check Circuit Breaker or Electrical Supply No Clean and Gap Igniter Replace if...

Page 26: ...G MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 302 F 150 C ELECTRICAL LADDER DIAGRAM CAUTION REFER TO THE HEATER S ELECTRICAL CONNECTION DIAGRAM WHEN SERVICING TO AVOID WIRING ERRORS HEATER MALFUN...

Page 27: ...ol Solenoid Valve House an electromagnet which is energized by voltage and opens to allow passage of gas to the burner orifice Gas Hose Flexible connector used to convey gas from supply line in buildi...

Page 28: ...27 PARTS SCHEMATIC Parts Identification...

Page 29: ...Compression 03879 20 Nut Compression 05772 21 Tube Formed Copper w Nuts and Sleeves 24641 22 Wire Red 18 in 24595 23 Direct Spark Ignition Control 24650 24 Screw Ignition Control 09043 25 Nut 86169 26...

Page 30: ...the end user Warranty is automatic if a component is found defective within 12 months of the date code marked on the part If the defect occurs more than 12 months later than the date code but within...

Page 31: ...defective parts replaced immediately The heater must be retested by properly qualified service personnel before placing the heater back into use...

Reviews: