Digital Phase Open & Reverse Phase & UnderVoltage Relay (GDR-JD01) User's Manual V1.10
48 / 52
Kyongbo Electronics Co., Ltd.
Default
Screen
Setting
(M e n u )
1. Protection
1. UVR
1. Mode
NI
2. PickUp
90V
3. Time Dial
10
4. DT_Time
−
5. OP_MODE
DIGITAL
6. RST_MODE
OFF
7. RST_TIME
−
2. POR
1. Mode
DT
2. ANGLE
20°
3. DT Time
2.0Sec
3. RPR
1. Mode
DT
2. DT_Time
0.5Sec
2. RS-485 comm.
1. Baudrate
19200[bps]
2. Slave Addr
1
3. System Config.
1. Power System
1. FREQ
60Hz
2. P_PT_CON
Delta
3. P_PT_RAT
1:1
4. P_PT_SEC
110V
2. T/S OutPut
1. T/S1
1. CON
PROT_OR
2. RST
SELF
3. DLY
0.00Sec
2. T/S2
1. CON
UVR
2. RST
SELF
3. DLY
0.00Sec
3. T/S3
1. CON
RPR
2. RST
SELF
3. DLY
0.00Sec
4. T/S4
1. CON
POR
2. RST
SELF
3. DLY
0.00Sec
5. T/S5
1. CON
PROT_OR
2. RST
SELF
3. DLY
0.00Sec
6. T/S6
1. CON
PROT_OR
2. RST
SELF
3. DLY
0.00Sec
7. T/S7
1. CON
PROT_OR
2. RST
SELF
3. DLY
0.00Sec
3. Password
0000
Appendix 1. Factory Default Setting Values