Digital Phase Open & Reverse Phase & UnderVoltage Relay (GDR-JD01) User's Manual V1.10
33 / 52
Kyongbo Electronics Co., Ltd.
- 〉
M e
a
s
u
r
e m e
n
t
V a b
:
1 1 0
.
0
V
,
〈
0
.
0
º
V b c
:
1 1 0
.
0
V
,
〈
2 3 9
.
9
º
V c
a
:
1 1 0
.
0
V
,
〈
1 1 9
.
8
º
Setting Delta in P_PT_CON
- 〉
M e
a
s
u
r
e m e
n
t
V a
:
1 1 0
.
0
V
,
〈
0
.
0
º
V b
:
1 1 0
.
0
V
,
〈
2 3 9
.
9
º
V c
:
1 1 0
.
0
V
,
〈
1 1 9
.
8
º
Setting Wye in P_PT_CON
Ÿ
System Config.
▶
Power system
▶
P_PT_RAT Setting
It is a category to set the Phase side 1st voltage ratio. It can be set in the units of
0.1 from 0.1 to 3200.0. For example, if the voltage in Phase side uses 22900:11, then
set to 208.2 in P_PR_RAT setting.
Ÿ
System Config.
▶
Power system
▶
P_PT_SEC Setting
It set to Phase PT secondary rating therefore it set 0.1 unit form 63.5 to 190. For
example, if phase PT secondary rating is 110V, P_PT_SEC set 110V.
6.2.5.2
System Config.
▶
T/S Output Setting
Connection types and recovery delay time for 7 output connections can be set in
T/S Output.
Select 2. T/S Output category in System Config., then the following screen appears.
- 〉