Digital Phase Open & Reverse Phase & UnderVoltage Relay (GDR-JD01) User's Manual V1.10
32 / 52
Kyongbo Electronics Co., Ltd.
Selecting(
)5. System Config. category in Setting will display the following screen.
- 〉
S y
s
t
e m
C o n
f
i
g
.
1
.
P o w e
r
S y
s
t
e m
*
2
.
T /
S
O u
t
p u
t
3
.
P a
s
s w o
r d
Press
Key in System Config. screen, then it will exit this menu and convert to the
default screen of Setting.
6.2.5.1
System Config.
▶
Power system Setting
Power system has detail categories of FREQ(frequency), P_PT_RAT and
P_PT_SEC.
Selecting(
) 1. Power system category in System Config. will display the following
screen.
- 〉
P o w e
r
S y s
t
e m
1
.
F R E Q
:
6 0 H z
*
2
.
P _ P T _ C O N :
D e
l
t
a
3
.
P _ P T _ R A T :
1
.
0
:
1
4
.
P _ P T _ S E C :
1 1 0 V
Press
Key in Power system screen, then it will exit this menu and convert to the
upper menu.
Ÿ
System Config.
▶
Power system
▶
FREQ Setting
It is a category to set the common frequency used in the system where the relay
is used.
There are two categories, 50Hz and 60Hz, and for cable using 60Hz, select 60Hz.
Ÿ
System Config.
▶
Power system
▶
P_PT_CON Setting
It is a category to set the PT 1st line connection type. It can select 2 types of
line connections, Wye and Delta. PT 1st line connection is Wye line connection for
Wye, and PT 1st line connection is Delta line connection for Delta. Voltage means
the voltage between the lines in Delta line connection, and the voltage means high
voltage for Wye line connection.