background image

 

___________________________________________________________________________________________ 

EG3002F

 

SECTION 7 : TROUBLE SHOOTING 

Fault Description 

Possible Cause 

Inspection (Fault Clearing) Actions 

7.1 Starter 

motor 

engaged 

but 

engine  will  not 
start 

1. No electrical power  1. Confirm  that  Terminals  1  &  2  are  connected  to  the  genset 

battery, have normal voltage, and that polarity is correct. 

 

2. MPU  fault  (failed, 

disconnected, 
installation 
incorrect) 

2. Disconnect  wires  from  Terminals  10  &  11.  Measure  the 

resistance  between  the  two  wires.  It  must  be  between  10 

– 

1,000 Ω. If there is an open or short circuit then check whether 
the wiring between MPU and the controller is open or shorted. 

  Directly  measure  the  resistance  of  the  MPU.  It  must  be 

between 10 

– 1,000 Ω. If there is a short circuit or an open then 

change the MPU. 

  Measure the resistance between each pin of the  MPU and its 

metal housing. There should be no conductance at all. If there 
is any conductance then replace the MPU. 

  During engine start confirm that the input voltage to Terminals 

10 & 11 is greater than 1 Vac. If less than 1 Vac check the gap 
between  the  tip  of  the  MPU  and  the  flywheel  teeth.  The 
distance should be 0.037 mm to 0.127 mm. 

 

3. Actuator 

fault 

(failed, 
disconnected, etc.) 

3. If  the  two  items  above  are  both  normal  then  check  whether 

Terminals 4 & 5 have a voltage output during cranking. If there 
is  an  output  but  the  actuator  does  not  activate  then  check 
whether the wiring to the actuator is open or not. 

 

4. Actuator defective 

4. Disconnect  the  wires  from  the  controller  to  the  actuator. 

Confirm  that  the  wiring  is  not  shorted  and  also  has  no 
conductivity to the housing of the actuator. 

  Connect actuator wires directly to the battery and confirm that 

the actuator operates through its full range. 

 

5. Other causes 

5. With the engine stopped, manually toggle the actuator linkage 

to see whether the action is smooth. 

  If that item is normal then manually toggle the actuator linkage 

during  engine  cranking.  If  the  engine  still  does  not  start  then 
check  whether  engine  fuel  supply  is  normal  (fuel  level,  fuel 
valve closed, stop solenoid linkage, etc.) 

Summary of Contents for EG3002F

Page 1: ...6037 Taiwan EG3002F Electronic Engine Governor Controller User Manual Engine Start Smoke Limiting function IDLE Speed Setting For External Built in and PT Pump type actuators Newly added extreme slow response engine setting All manufacturer names and numbers are used for reference purpose only and do not imply that any part is the product of these manufacturer ...

Page 2: ...0 10 000 Hz Voltage 1 120 Vac RMS Speed Temperature Shift Less than 3 at temperature range 40 to 80 C Frequency Adjustment Speed Adjustment pot 25 turn Environment Setting range 600 9 500 Hz With DIP Switch Operating Temperature 40 to 80 C Storage Temperature 40 to 85 C Remote Speed Potentiometer Terminals 6 7 9 Relative Humidity Max 95 Max 30 5 KΩ 1 watt potentiometer Vibration 5 5Gs 60 Hz Isochr...

Page 3: ...al from the load sharing controller Must be isolated from battery power Terminal 6 is ground of load sharing controller Terminal 8 is input signal from controller 1 2 Battery Input Connect to genset battery Use14 AWG wire or larger 3 IDLE Control Contact When shorted to terminal 2 unit will go to IDLE state 4 5 Output to Actuator Use 14 AWG wire or larger INT Integral Setting DIF Differential Sett...

Page 4: ...low response SW R 3 1 2 1K 3 1 2 CCW CW ATTENTION 1 The unit must be installed by qualified technical personnel Improper installation wiring or settings could lead to injury to personnel and or damage to equipment 2 This unit has no Over Speed Protection function It is recommended to install a separate over speed protection device 3 The battery connects directly to the controller with a fuse for p...

Page 5: ...will begin to make a clicking sound but will not be damaged 6 2 Trial Run 6 2 1 Engine will not start Refer to Section 7 1 Troubleshooting below for possible causes If the engine still will not start normally then increase Run Speed setting or Frequency Range SW setting to a higher range Run Speed should be set to minimum at this time 6 2 2 If engine starts normally then slowly adjust Run Speed to...

Page 6: ...until optimal settings are achieved 3 Engine speed instability can be divided into slow oscillations once every 2 to 5 seconds and rapid oscillations 2 to 8 times per second slow oscillation is usually because GAIN is too low and or INT is too high Rapid oscillations however can occur in two ways 4 2 4 times per second GAIN setting too high 4 8 times per second DIF setting too high 6 5 Remote Spee...

Page 7: ...ce then replace the MPU During engine start confirm that the input voltage to Terminals 10 11 is greater than 1 Vac If less than 1 Vac check the gap between the tip of the MPU and the flywheel teeth The distance should be 0 037 mm to 0 127 mm 3 Actuator fault failed disconnected etc 3 If the two items above are both normal then check whether Terminals 4 5 have a voltage output during cranking If t...

Page 8: ...hether MPU is disconnected Must be directly connected to Terminals 10 11 Resistance of 10 1 000Ω is normal Check that MPU has been connected with shielded wire grounded at one end Repair wiring as required 4 Controller defective 4 With engine OFF apply power to the controller if actuator linkage moves or if there is a voltage output on Terminals 4 5 this indicates the controller is defective 7 4 E...

Reviews: