EA200A
9
SECTION 5 : SETTING AND ADJUSTMENT BEFORE START
5.1 Select and set sensing input voltage and Fan voltage
Example
:
220V Output Voltage:
S1 & S2 connect to R-T (220V)
MCCB AC1 & AC2 connect to R-T (220V)
FAN VOLT: Cross connect COM1 & 220V
SENSING VOLT: Cross connect COM2 & 220V
400V Output Voltage
:
S1 & S2 connect to R-T (400V)
MCCB AC1 & AC2 connect to S-N (230V)
FAN VOLT: Cross connect COM1 & 220V (select the closest voltage 230V)
SENSING VOLT: Cross connect COM2 & 380V (select the closest to 400V)
440V Output Voltage
:
S1 & S2 connect to R-T (440V)
MCCB AC1 & AC2 connect to S-N (254V)
FAN VOLT: Cross connect COM1 & 245V (select the closest voltage 254V)
SENSING VOLT: Cross connect COM2 & 440V
480V Output Voltage
:
S1 & S2 connect to R-T (480V)
MCCB AC1 & AC2 connect to AUX Power (180V)
FAN VOLT: Cross connect COM1 & 190V (select the most close voltage 180V)
SENSING VOLT: Cross connect COM2 & 480V
※
FAN VOLT must be selected to the closest voltage on MCCB AC1 & AC2
※
SENSING VOLT must be selected to the closest voltage on S1 & S2
ATTENTION
※
The factory preset FAN VOLT is 277Vac, SENSING VOLT factory preset is 110Vac. Make adjustment
before operation on the first time installation.
Figure 6
277V
245V
220V
190V
COM1
480V
440V
380V
220V
110V
COM2
TB5
FAN
VO
LT
SE
NS
ING
VO
LT