EA200A
13
5.4 EB500 Auto Flash Module
B-
B+
F+
F-
10 Ohm
1~8 Sec
A
B
C
5 Ohm
AC2 AC1
EB500
Flash timer adj.
Figure 10
When EB500 powered by B+ and B-, there will have excitation output on F+ and F-. The excitation output will be
terminated when AC1, AC2 reach 30VAC or the Flash time is reach flash timer setting. If re-excitation is required, the
B+ and B- must be powered off and then re-powered.
The Maximum Excitation Flash current can be set by A, B, C terminal (selected by jumper)
A
、
B
、
C (Open)
24V = 1.6A
A
−B (Short)
24V = 2.4A
B
−C (Short)
24V = 4.8A
5.5 EP4-1 Multifunctional voltage relay
EP4-1 is a DC voltage abnormal warning relay
Factory Preset Value
Under volt
:
20V
Over volt
:
28V
Under voltage delay time
:
5s
Over voltage delay time
:
5s
DIP SW
:
1
– OFF
、
2
– OFF
、
3
– ON
、
4
– ON
ATTENTION
※
EB500 Flash Current factory preset is A-B shorted
※
Due to the limitation of DC current input, do not short A
– C.
Volt
Time
Over
Under
Test
Reset
L1
Over
Under
L2
L3
V
S
Figure 11
EB500 Terminals
B+
、
B-
DC Voltage Input
F+
、
F-
Connect to Magnetic Field +
and -
AC1
、
AC2
Connect to Power Input
EB500 Adjustment
Flash timer
adj.
Adjustable range
1 to 8 seconds
A
、
B
、
C
Flash Current Selection