6.  TROUBLE SHOOTING 

SYMPTOM 

CAUSE 

CORRECTION 

Residual voltage below 5VAC 

Reference from 5. Field Flashing 

F+, F

 polarity reversed 

F+ and F

 reverse the connection 

F+,  F

,  P1,  P2,  VS1,  VS2  not 

connected 

Reference from Figure 3 and 4 connection 

Burnt fuse 

Change fuse 16A 250V 

Ext. Switch (Breaker) not turned on  Switch on (ON) 

Voltage does not 

build up 

Engine RPM under speed 

Increase engine speed / frequency above25HZ 

Poor adjustment is made 

Read start procedure carefully and adjust again 

U/F protection activated 

Increase generator speed 

Out voltage low 

U/F  activated  /  Incorrect  voltage 
selection 

Read user’s manual to select correct voltage 

Poor adjustment is made 

Read start procedure carefully and adjust again 

Out voltage high 

Incorrect voltage selection 

Read user’s manual to select correct voltage 

Poor adjustment is made 

Read start procedure carefully and adjust again 

Out voltage instable 

Field  voltage  requirement  lower 
the rang of regulator 

Inquire our distributor to solve 

 

 

Use only original supplied spare protection fuse for fuse replacement.

 

 

Please  accept  our  sincere  apology  if  any  modification  in  performance,  specification  or  appearance  is 
made without prior notice. 

Summary of Contents for EA16

Page 1: ...sal 16Amp Self Excited Automatic Voltage Regulator for use in 220 380 440 480 VAC brushless generators with paralleling compatibility Headquarters No 3 Lane 201 Chien Fu ST Chyan Jenn Dist Kaohsiung TAIWAN Tel 886 7 8121771 Fax 886 7 8121775 URL http www kutai com tw ...

Page 2: ...is an update of the EA15A AVR It is similar to the original EA15A in power and voltage sensing capabilities but with new enhanced paralleling functions the user can now select the CT inputs either 1 5 Amp or use new A1 A2 analogue signal inputs terminals for use with PLC paralleling controls It has new over voltage excitation safety circuits to prevent damage caused by the accidental detachment of...

Page 3: ... the manufacture of the Paralleling control PLC 2 DROOP Select switch K or L pending on the secondary current of the CT that you are using Voltage droop works when the CT and the AVR senses that the output of the generator voltage and current waveforms are out of synch and the AVR droops the output voltage of the generator to correct it 3 STAB If the generator output voltage oscillate adjusting th...

Page 4: ...he 60 C 140 F DANGER When the AVR is working never touch or ground the heat sink on the AVR The AVR heat sink is an electrically live terminal A warning sticker is in place on top of the heat sink 5 FIELD FLASHING When operating this AVR for the first time the polarity of the residual magnetism may be reversed or too weak to achieve the necessary build up on the regulator If reversing the field co...

Page 5: ...ection P1 VR1 EXT VR Field GEN VR2 A1 A2 VS1 F P2 F K VS2 L R T N S Field EXT VR VR1 P1 VR2 A2 A1 VS1 F P2 F L VS2 K GEN T N S R EA16A EA16A GEN EXT VR K VR1 VR2 A1 F P2 P1 VS1 F VS2 A2 L T N R S EA16A Field Figure 2 Paralleling Connection Figure 4 380 480V Connection Field EXT VR EA16 VR2 VR1 A2 A1 F VS1 P1 P2 F L VS2 K GEN T N S R Aux Winding 60 300v Figure 5 Auxiliary Winding ...

Page 6: ... procedure carefully and adjust again U F protection activated Increase generator speed Out voltage low U F activated Incorrect voltage selection Read user s manual to select correct voltage Poor adjustment is made Read start procedure carefully and adjust again Out voltage high Incorrect voltage selection Read user s manual to select correct voltage Poor adjustment is made Read start procedure ca...

Reviews: